background image

NOVUS AUTOMATION 

1/7 

 

 

NC400-6 Counter 

ELECTRONIC PROGRAMMABLE COUNTER – INSTRUCTIONS MANUAL – V1.2x E 

SAFETY ALARMS 

The following symbols appear in the device and throughout this 

manual to call the user’s attention as to important information related 

to safety and device use. 

 

 

CAUTION: 

Read manual carefully before 

installing and operating the device 

CAUTION OR DANGER: 

Risk of electrical shocks 

All safety recommendations must be followed as to warrant the 

individual’s safety and prevent damage to the instrument or system.  If 

the instrument is used in another way other than that specified in this 

manual, the equipment safety protections may not work properly. 

Over Temperature Protection 

When a system is designed, it is fundamental that one considers the 

consequence of  any failure in any component of such system. In 

temperature control application, danger is even higher when heating 

remains constantly on. In applications where physical damage or 

device destruction may occur, the installation of an independent 

protection  device is recommended, which has its own temperature 

sensor and can turn off the heating circuit in case of over heating. Note 

that the counter output relays of NC400-6 do not offer protection to all 

failure conditions. 

INTRODUCTION 

NC400-6 is an advanced 6-digit counter that also performs batch and 

totalizer counting operations. It has two outputs with independent and 

configurable presets that can be triggered based on counting, batch 

or totalization values. Its 2 outputs allow for an independent timed 

triggering. 
The counting input can be configured to read dry-contact, voltage 

pulse, NPN our PNP sensor connections. Sensors may be powered 

by an internal power supply. 
Counting mode can be configured as progressive, regressive, 

quadrature, ADD or SUB. Several reset modes —  automatic or 

manual — can be configured.  Manual reset can be generated by a 

digital input or key from the front panel. 
 

 

 

 

 

 

 

 

 

DESCRIPTION 

The NC400-6 counter and its configuration parameters are divided in 

the following blocks: 

 

Inputs 

 

Main counter 

 

Batch counter 

 

Totalizator counter 

 

OUT1 

 

OUT2 

Each of these blocks has its own set of configuration parameters, 

which together determine how the device works. A summary of the 

operation of each block is presented below as well as their 

parameters. 

INPUTS 

NC400-6 has three inputs that can be configured to read contacts, 

NPN sensors, PNP sensors or voltage pulse connections. All inputs 

must receive the same type of input signal. Functions of each input 

are: 
COUNT1: 

Main counting input 

HOLD/COUNT2: Input to hold counting or second counting input. The 

second counting input is required when the NC400-

6 counter increases or decreases actions are 

determined by an external signal (quadrature 

signals, for example). 

RESET: 

Input for external 

reset

 of counters and/or outputs. 

The following configuration parameters are directly related to the 

operation of inputs: 

SEnS.tY 

  Selection of type of  signal  (contact, pulse, 

NPN, PNP). 

Coun.tY 

  Selection of counting speed (slow or fast). 

Coun.UP 

  Progressive or regressive counting choice 

and use of COUNT2 input. 

MAIN COUNTER 

It counts pulses from inputs, showing the value in the display after 

multiplying it by a configurable scaling factor. Manual or automatic 

reset. Two Set points can be defined (presets); when they are 

reached they produce configurable actions (enable output, increment 

batch counter, reset counter etc.) The following configuration 

parameters are directly related to the main counter operation. 

FActor 

  Factor that multiplies the number of input 

pulses (

0.00001

 to 

9.99999

). 

SP1 C 

  Set point 1 for the main counter. 

SP2 C 

  Set point 2 for the main counter. 

OPt.SP.C 

  Condition for  Set point 1 reached  (main 

counter higher or lower than Set point 1). 

OFF.C 

  Initial value (O

ffset

) for main counter. 

rES.C 

 

Reset

  options  in the main counter  (input, 

key, Set point, output, etc.). 

Содержание NC400-6

Страница 1: ...anual can be configured Manual reset can be generated by a digital input or key from the front panel DESCRIPTION The NC400 6 counter and its configuration parameters are divided in the following blocks Inputs Main counter Batch counter Totalizator counter OUT1 OUT2 Each of these blocks has its own set of configuration parameters which together determine how the device works A summary of the operat...

Страница 2: ...ions Set point 2 batches or totalizer Out2 t Time to deactivate OUT2 0 00 to 9999 99 s Out2 E Turn off options of OUT2 time OUT1 reset Out2 OP Freeze counting while OUT2 is activated yes no Out2 c OUT2 normal mode open or closed BLOCK DIAGRAM Figure 1 illustrates associations among features and resources of NC400 6 Figure 1 Diagram with features and resources of NC400 6 COUNTING MODES The Coun tY ...

Страница 3: ...the device Maximum connection distance 1000 meters NC400 6 disconnection time Maximum 2 ms after the last byte Fixed communication speed Baud Rate 9600 bps Number of data bits 8 no parity Number of stop bits 1 Transmission onset and response time maximum of 100 ms after command RS 485 signals are D1 D D B Bidirectional data line Terminal 16 D0 D A Reserved bidirectional data line Terminal 17 C Opt...

Страница 4: ... polarity and current limits before connecting external devices to the auxiliary supply Inputs 8 and 9 are internally connected not isolated CONFIGURATION The proper operation of NC400 6 depends on the proper configuration of all parameters Read the manual carefully and thoroughly before using the equipment KEYBOARD AND DISPLAY OPERATION All configuration operations are performed through the front...

Страница 5: ...ues range from 0 00000 to 999999 with configurable decimal point Sp2 c Set Point 2 Counter Set point 2 value of the main counter Values range from 0 00000 to 999999 with configurable decimal point SP bat Set Point Batch Batch counter Set point value Values range from 0 to 999999 SP tot Set Point Totalizer Set point 1 value of the totalizer counter Values range from 0 00000 to 999999 with configura...

Страница 6: ...or off 0 key does not affect the totalizer counter 1 key resets totalizer counter if configured as reset 0 Remote reset does not affect the totalizer counter 1 Remote reset resets the totalizer counter 0 Set point 2 does not affect the totalizer counter 1 Resets totalizer counter when Totalizer Set point is triggered Opt sp c Option for Counter Setpoint Set point 1 reached 0 Actions corresponding ...

Страница 7: ...onfigured four NPN PNP dry contact or voltage pulse Low level 2 Vdc High level 3 Vdc Input Impedance 4700 Ω Maximum input voltage 30 Vdc Dry contact input polarization 5 V 4700 Ω Maximum counting frequency square wave 20 kHz in COUNT1 input for Coun tY 1 and COUNT UP 12 4 kHz in COUNT2 input for Coun tY 1 and COUNT UP 12 55 Hz for Coun tY 0 and Coun UP 12 4 kHz for both inputs Coun UP 12 Counting ...

Отзывы: