background image

NC400-6 Counter  

NOVUS AUTOMATION

 

2/7

 

BATCH COUNTER 

Counts the number of times that Set point 2 for the main counter was 

reached, with manual or automatic reset. When its Set point is 

exceeded (greater than or equals to) results in configurable actions 

(enable output or increment totalizer counter).  It is always a 

progressive counter. The following configuration parameters are 

directly related to the batch counter operation. 

SP bAt 

  Batch counter Set point. 

OFF.bAt 

  Initial value (O

ffset

) for the batch counter. 

rES.bAt 

 

Reset

  options for the batch counter  (input, 

key, Set point, output, etc.). 

TOTALIZER COUNTER 

Totalizes the main counter or the number of times that the batch 

counter Set point was reached,  with manual or automatic reset. 

When its Set point is reached (greater than or equals to) it can 

activate an output. The following configuration parameters are 

directly related to the totalizer operation. 

Opt.tot 

  Totalizer  counting option  (input pulse or 

batch) 

SP tot 

  Totalizer Set point. 

OFF.t 

  Initial value (

Offset

) for the totalizer. 

rES.tot 

 

Reset

  options for the totalizer  (input,  key, 

Set point, output, etc.). 

OUT1 

This output is always associated to the main counter, and it is 

activated when Set point 1 is reached

, and disabled with time, 

reset, Set point 1 or when OUT2 is enabled. The following 

configuration parameters are directly related to the OUT1 operation. 

Out1.t 

  Time to deactivate OUT1 (

0.00

 to 

9999.99

 

s). 

Out1.E 

  Turn-off options of OUT1 (time, OUT2, 

reset

, Set point 2). 

Out1.OP 

  Freeze counting while  OUT1  is activated 

(yes, no). 

Out1.c 

  OUT1 normal state open or closed. 

OUT2

 

This output can be activated by Set point 2 of the main counter, by 

the batch counter Set point or by the totalizer Set point. It can be 

deactivated by time, reset, activation of OUT1 or Set point that 

activated it. The following configuration parameters are directly 

related to the OUT2 operation. 

Out2.SE 

  OUT2 activation options (Set point 2, batches 

or totalizer). 

Out2.t 

  Time to deactivate OUT2 (

0.00

 to 

9999.99

 

s). 

Out2.E 

  Turn-off options of OUT2  (time, OUT1, 

reset

). 

Out2.OP 

  Freeze counting while  OUT2  is activated 

(yes, no). 

Out2.c 

  OUT2 normal mode open or closed. 

 

 

 

 
 

BLOCK DIAGRAM 
Figure  1

  illustrates associations among features and resources  of 

NC400-6: 

 

Figure 1

 – Diagram with features and resources of NC400-6 

COUNTING MODES

 

The 

Coun.tY

 parameter selects the counting mode as slow or fast. 

In the slow counting mode, a filter is applied to the counting signals, 

limiting the maximum pulse frequency, which is necessary to count 

the number of activations of electromechanical contacts.  In the fast 

counting mode, NC400-6 operates up to the maximum frequency 

specified for the input signal. The frequency limits for each mode are 

defined in 

Item 5

The 

Coun.UP

 parameter defines the main counting direction (UP or 

DOWN) and the function of each input. 

Table 1

  shows options for 

this parameter. 

Code 

COUNT2/HOLD 

Input 

COUNT1 Input  Main direction 

HOLD 

SUB 

DOWN 

HOLD 

ADD 

UP 

SUB 

SUB 

DOWN 

SUB 

ADD 

UP 

ADD 

SUB 

DOWN 

ADD 

ADD 

UP 

Select ADD 

SUB or ADD 

DOWN 

Select SUB 

ADD or SUB 

UP 

12 

QUADRATURE 

DOWN 

13 

QUADRATURE 

UP 

14 

QUADRATURE 2x 

DOWN 

15 

QUADRATURE 2x 

UP 

Table 1

 – Counting modes that can be selected with the 

Coun.UP

 

parameter. 

The main counting direction affects the main counter: 
Main direction UP: 

Main counter count upstream, starting from 

the Offset value defined (usually zero). 

Actions can be programmed to take place 

in Set point 1 and 2 values. 

Main direction DOWN:  The main counter count downstream, 

starting from the Set point 2 value (

SP2C

). 

The action programmed for this Set point 

will take place when the counter reaches 

the programmed Offset value. 

The totalizer direction is always up. 

 

Operation descriptions in this manual consider that 

the NC400-6 counter is operating in the UP direction. 

To operate in DOWN direction, refer to the 

explanation above. 

You can select functions for COUNT1 and COUNT2/HOLD inputs: 
ADD: 

Progressive counting input. 

SUB: 

Regressive counting input. 

HOLD: 

Stops the counting input for COUNT1. 

Содержание NC400-6

Страница 1: ...anual can be configured Manual reset can be generated by a digital input or key from the front panel DESCRIPTION The NC400 6 counter and its configuration parameters are divided in the following blocks Inputs Main counter Batch counter Totalizator counter OUT1 OUT2 Each of these blocks has its own set of configuration parameters which together determine how the device works A summary of the operat...

Страница 2: ...ions Set point 2 batches or totalizer Out2 t Time to deactivate OUT2 0 00 to 9999 99 s Out2 E Turn off options of OUT2 time OUT1 reset Out2 OP Freeze counting while OUT2 is activated yes no Out2 c OUT2 normal mode open or closed BLOCK DIAGRAM Figure 1 illustrates associations among features and resources of NC400 6 Figure 1 Diagram with features and resources of NC400 6 COUNTING MODES The Coun tY ...

Страница 3: ...the device Maximum connection distance 1000 meters NC400 6 disconnection time Maximum 2 ms after the last byte Fixed communication speed Baud Rate 9600 bps Number of data bits 8 no parity Number of stop bits 1 Transmission onset and response time maximum of 100 ms after command RS 485 signals are D1 D D B Bidirectional data line Terminal 16 D0 D A Reserved bidirectional data line Terminal 17 C Opt...

Страница 4: ... polarity and current limits before connecting external devices to the auxiliary supply Inputs 8 and 9 are internally connected not isolated CONFIGURATION The proper operation of NC400 6 depends on the proper configuration of all parameters Read the manual carefully and thoroughly before using the equipment KEYBOARD AND DISPLAY OPERATION All configuration operations are performed through the front...

Страница 5: ...ues range from 0 00000 to 999999 with configurable decimal point Sp2 c Set Point 2 Counter Set point 2 value of the main counter Values range from 0 00000 to 999999 with configurable decimal point SP bat Set Point Batch Batch counter Set point value Values range from 0 to 999999 SP tot Set Point Totalizer Set point 1 value of the totalizer counter Values range from 0 00000 to 999999 with configura...

Страница 6: ...or off 0 key does not affect the totalizer counter 1 key resets totalizer counter if configured as reset 0 Remote reset does not affect the totalizer counter 1 Remote reset resets the totalizer counter 0 Set point 2 does not affect the totalizer counter 1 Resets totalizer counter when Totalizer Set point is triggered Opt sp c Option for Counter Setpoint Set point 1 reached 0 Actions corresponding ...

Страница 7: ...onfigured four NPN PNP dry contact or voltage pulse Low level 2 Vdc High level 3 Vdc Input Impedance 4700 Ω Maximum input voltage 30 Vdc Dry contact input polarization 5 V 4700 Ω Maximum counting frequency square wave 20 kHz in COUNT1 input for Coun tY 1 and COUNT UP 12 4 kHz in COUNT2 input for Coun tY 1 and COUNT UP 12 55 Hz for Coun tY 0 and Coun UP 12 4 kHz for both inputs Coun UP 12 Counting ...

Отзывы: