background image

NC400-6 Counter  

NOVUS AUTOMATION

 

7/7

 

coun.up 

Coun

ter 

Up

 

Selections of the NC400-6 counting direction. 

Note

: See 

“Counting Modes”

 for further details. 

Regressive

 (

DOWN

) starting from Set point 2 down. 

Progressive

 (

UP

) starting from offset. 

For counting modes with two inputs, the COUNT2 input 

is used as secondary counting input. 

Code 

COUNT2/HOLD 

Input 

COUNT1 

Input 

Main 

Direction 

HOLD 

SUB 

DOWN 

HOLD 

ADD 

UP 

SUB 

SUB 

DOWN 

SUB 

ADD 

UP 

ADD 

SUB 

DOWN 

ADD 

ADD 

UP 

Select ADD 

SUB or 

ADD 

DOWN 

Select SUB 

ADD or 

SUB 

UP 

12 

QUADRATURE 

DOWN 

13 

QUADRATURE 

UP 

14 

QUADRATURE 2x 

DOWN 

15 

QUADRATURE 2x 

UP 

Erase.0 

Erase 0

 

0

: Does not erase zeros on the left. 

1

: Erases zeros on the left of the first decimal point digit. 

factor 

Factor

 

Counter conversion factor is the value by which the 

input pulses are multiplied. Configurable from 

0.00001

 

to 

9.99999

. Value programmed here is the increment 

value (or decrement) applied to main counter at every 

counting pulse. 

addres 

Addres

 

NC400-6 communication address. Configurable from 1 

to 247. 

Only used in equipment with RS-485 

communication (optional)

Prot 

Prot

ection

 

Defines the parameter levels that will be protected, 

preventing changes in parameters. 

1

:  Only the 

Hardware Configuration

  level is protected 

(factory setting) 

2

Configuration

  and 

Hardware Configuration

  levels 

are protected. 

3

Hardware Configuration

Configuration

  and 

Set 

points

 levels are protected. 

Pass.c 

Pass

word 

C

hange

 

Parameter that makes  possible to change the current 

password. Can only be accessed if the right password 

was informed in 

Pass

  screen. Configurable from 

0000

 to 

9999

Ser.n.1 

Ser

ial 

N

umber 1

 

Shows the 

four first

  digits of the NC400-6 serial 

number. 

Ser.n.2 

Ser

ial 

N

umber 2

 

Shows the 

four last

  digits of the NC400-6 serial 

number. 

SPECIFICATIONS 

6-digit red display 12 mm-high. 

Three inputs

: COUNT1, COUNT2 and 

Reset

Can be configured  four  NPN, PNP, dry-contact or voltage 

pulse 

Low level: < 2 Vdc, High level: > 3 Vdc 

Input Impedance: 4700 

Maximum input voltage: ± 30 Vdc. 

Dry-contact input polarization: 5 V / 4700 

Maximum counting frequency (square wave):  

 

20 kHz in COUNT1 input for 

Coun.tY 

1

 and 

COUNT.UP

 

12

 

4 kHz in COUNT2 input for 

Coun.tY 

1

 and 

COUNT.UP

 

12

 

55 Hz for 

Coun.tY 

=

 0

 and 

Coun.UP

 < 

12

 

4 kHz for both inputs 

Coun.UP 

 12

Counting modes:

  Up, down, ADD/ADD, ADD/SUB, SUB/ADD, 

SUB/SUB, external selection of UP/DOWN Quadrature, Quadrature 

2x.. 

Response time for output activation, reset and batch count:

 0.5 to 

5 ms. 

Relay outputs

: SPST 3 A @ 250 Vac. 

Pulse output:

 5 Vdc. Output impedance 100 

Timing accuracy:

 3 %. 

Auxiliary voltage source:

 12 Vdc (± 10 %) / 50 mA. 

Power supply:

 100 to 240 Vac/dc (±10 %), 50/60 Hz  

Optional 24 V: 12 to 24 Vdc / 24 Vac (-10 % / 20 %) 

Consumption:

 9 VA max. 

Internal battery:

 Lithium CR2032.Typical battery life: 8-months. 

Configuration parameters hold:

  10-year  minimum in  E2PROM 

memory. 

Dimensions:

 48 x 48 x 110 mm. 

Panel cutout:

 45.5 x 45.5 mm. 

Material and front panel sealing:

 Polycarbonate UL94 V-2, IP65. 

Material and case sealing:

 ABS+PC UL94 V-0, IP20. 

Operating Temperature:

 0 to 50 °C 

Relative humidity: Maximum:

 80 % up to 30 ºC. For temperatures 30 

ºC, decrease 3 % per ºC. 

Panel protection:

 Complies to NEMA 4X internal use; Installation II, 

Pollution level 2; altitude < 2000 m. 

EMC:

 EN 61326-1:1997 and EN 61326-1/A1:1998 

Safety: 

 EN61010-1:1993 and EN61010-1/A2:1995 

IDENTIFICATION 

In order to identify your model of NC400-6, check the name in the 

device label, as per 

Table 2

Example: 

NC400-6 - 

RR - 

485 - 

24V 

 

A

:  Model

 

NC400-6 

B

:  Optional

 

RR

  (model with OUT1: Relay and 

OUT2: Relay) 

RP

  (model with OUT1: Pulse and 

OUT2: Relay)

 

C

:  Digital 

Communication

 

blank 

(basic version, without serial 

communication) 

485

 (version with serial RS485, Modbus 

protocol) 

D

:  Power Supply

 

blank

  (basic version, with 100 to 240 

Vac/dc power supply) 

 24V

  (version with 12 to 24 Vdc / 24 

Vac power supply)

 

Table 2

 – Identification of NC400-6 

WARRANTY 

Warranty conditions are available on our web site 

www.novusautomation.com/warranty

Содержание NC400-6

Страница 1: ...anual can be configured Manual reset can be generated by a digital input or key from the front panel DESCRIPTION The NC400 6 counter and its configuration parameters are divided in the following blocks Inputs Main counter Batch counter Totalizator counter OUT1 OUT2 Each of these blocks has its own set of configuration parameters which together determine how the device works A summary of the operat...

Страница 2: ...ions Set point 2 batches or totalizer Out2 t Time to deactivate OUT2 0 00 to 9999 99 s Out2 E Turn off options of OUT2 time OUT1 reset Out2 OP Freeze counting while OUT2 is activated yes no Out2 c OUT2 normal mode open or closed BLOCK DIAGRAM Figure 1 illustrates associations among features and resources of NC400 6 Figure 1 Diagram with features and resources of NC400 6 COUNTING MODES The Coun tY ...

Страница 3: ...the device Maximum connection distance 1000 meters NC400 6 disconnection time Maximum 2 ms after the last byte Fixed communication speed Baud Rate 9600 bps Number of data bits 8 no parity Number of stop bits 1 Transmission onset and response time maximum of 100 ms after command RS 485 signals are D1 D D B Bidirectional data line Terminal 16 D0 D A Reserved bidirectional data line Terminal 17 C Opt...

Страница 4: ... polarity and current limits before connecting external devices to the auxiliary supply Inputs 8 and 9 are internally connected not isolated CONFIGURATION The proper operation of NC400 6 depends on the proper configuration of all parameters Read the manual carefully and thoroughly before using the equipment KEYBOARD AND DISPLAY OPERATION All configuration operations are performed through the front...

Страница 5: ...ues range from 0 00000 to 999999 with configurable decimal point Sp2 c Set Point 2 Counter Set point 2 value of the main counter Values range from 0 00000 to 999999 with configurable decimal point SP bat Set Point Batch Batch counter Set point value Values range from 0 to 999999 SP tot Set Point Totalizer Set point 1 value of the totalizer counter Values range from 0 00000 to 999999 with configura...

Страница 6: ...or off 0 key does not affect the totalizer counter 1 key resets totalizer counter if configured as reset 0 Remote reset does not affect the totalizer counter 1 Remote reset resets the totalizer counter 0 Set point 2 does not affect the totalizer counter 1 Resets totalizer counter when Totalizer Set point is triggered Opt sp c Option for Counter Setpoint Set point 1 reached 0 Actions corresponding ...

Страница 7: ...onfigured four NPN PNP dry contact or voltage pulse Low level 2 Vdc High level 3 Vdc Input Impedance 4700 Ω Maximum input voltage 30 Vdc Dry contact input polarization 5 V 4700 Ω Maximum counting frequency square wave 20 kHz in COUNT1 input for Coun tY 1 and COUNT UP 12 4 kHz in COUNT2 input for Coun tY 1 and COUNT UP 12 55 Hz for Coun tY 0 and Coun UP 12 4 kHz for both inputs Coun UP 12 Counting ...

Отзывы: