Novus NC400-6 Скачать руководство пользователя страница 3

NC400-6 Counter  

NOVUS AUTOMATION

 

3/7

 

Select ADD/SUB: 

COUNT2 input defines if COUNT1 input is 

progressive or regressive. 

QUADRATURE: 

Bidirectional counting mode that uses two 

counting inputs to determine if counting is 

progressive or regressive. In this counting 

mode, the 

Coun.tY

  parameter is ignored 

and the counting mode is always fast. 

QUADRATURE 2X: 

The same as the QUADRATURE mode, 

but it counts twice as fast, increasing 

resolution. In this counting mode, the 

Coun.tY

  parameter is ignored and the 

counting mode is always fast. 

The counter is incremented or decremented whenever the voltage 

level in the counting inputs increases (rising edge) except in the fast 

counting mode (

Coun.tY

 = 

1

) in COUNT1 input. 

The most representative counting modes are shown in 

Figures 2

 to 

5

. Low and High levels in the following figures correspond to voltage 

levels in these inputs with PNP sensor or Voltage pulse. For the case 

of NPN sensors or dry contact, signals will be reversed. 

 

Figure 2

 – Counting modes 1 and 5 

 

 

 

Figure 3

 – Counting modes 7 and 8 

 

Figure 4

 – Counting mode 13 (quadrature) 

 

Figure 5

 – Counting mode 15 (quadrature 2x) 

SERIAL COMMUNICATION (OPTIONAL) 

Optionally, NC400-6 can be delivered with an asynchronous master-

slave serial communication interface RS-485 to communicate with a 

supervisor computer (master). The counter is always the slave. 

Communication always start with the master, which sends a 

command to the slave address with whom it wants to communicate. 

The addressed slave undertakes the command and sends the 

response to the master. NC400-6 also accepts 

broadcast

 

commands. 

FEATURES 

 

Signals compliant with the RS-485 standard. MODBUS (RTU) 

protocol. 2 wire connection between 1 master and up to 31 (able 

to address up to 247) instruments in bus topology. 

Communication signals are electrically isolated from the rest of 

the device; 

 

Maximum connection distance: 1000 meters; 

 

NC400-6 disconnection time: Maximum 2 ms after the last byte; 

 

Fixed communication speed (

Baud Rate

): 9600 bps; 

 

Number of data bits: 8, no parity. Number of 

stop

 bits: 1; 

 

Transmission onset and response time: maximum of 100 ms 

after command. 

RS-485 signals are: 

D1  D  D +  B 

Bidirectional data line.

 

Terminal 16 

D0    D -  A 

Reserved bidirectional data line.

 

Terminal 17 

Optimal connection that enhances 

the communication performance.

 

Terminal 18 

GND 

CONFIGURATION OF SERIAL COMMUNICATION PARAMETERS 

Parameter that must be configured when the serial communication 

used: 

Addres 

  NC400-6 counter communication address. 

OVERFLOW AND UNDERFLOW 

If the counter is at 

0

  and it receives a pulse to decrement, the 

counter will show 

999.999

 and turn the OVFL flag on. This means 

that the counter rolls to 

999.999

. If it increments beyond this, it will 

roll back to 

0

, clearing OVFL flag. 

On a similar way, when the counter is at 

999.999

  and it is 

increased, it will roll to 

0

  and turn the OVFL flag on. When it 

decreases again below 

0

, it will turn the flag off and roll back to 

999.999

Note

: The setpoints and output control have no effect while OVFL 

flag is on, except those who are cleared by time. 

INSTALLATION 

PANEL MOUNT

 

NC400-6  must be installed in a papel. To install, follow the steps 

below: 
1.

 

Make a panel cutout of 45.5 x 45.5 mm; 

2.

 

Remove the clips from NC400-6; 

3.

 

Insert NC400-6 in the frontal panel cutout; 

4.

 

Replace clips in  NC400-6  and press them tightly to clamp the 

counter to the panel. 

INSTALLATION RECOMMENDATIONS 

 

Input signal wires must be installed in grounded conduits and 

away from power or contactor wires+ 

 

Instruments must be powered only by an exclusive power supply. 

 

System failure should always be taken into account when 

designing a control panel to avoid irreversible damage to 

equipment or people.  The output internal relay does not warrant 

total protection. 

 

Installing RC filters (47 Ohms and 100 nF, serial) is strongly 

recommended at contactor coils or any other inductors. 

Содержание NC400-6

Страница 1: ...anual can be configured Manual reset can be generated by a digital input or key from the front panel DESCRIPTION The NC400 6 counter and its configuration parameters are divided in the following blocks Inputs Main counter Batch counter Totalizator counter OUT1 OUT2 Each of these blocks has its own set of configuration parameters which together determine how the device works A summary of the operat...

Страница 2: ...ions Set point 2 batches or totalizer Out2 t Time to deactivate OUT2 0 00 to 9999 99 s Out2 E Turn off options of OUT2 time OUT1 reset Out2 OP Freeze counting while OUT2 is activated yes no Out2 c OUT2 normal mode open or closed BLOCK DIAGRAM Figure 1 illustrates associations among features and resources of NC400 6 Figure 1 Diagram with features and resources of NC400 6 COUNTING MODES The Coun tY ...

Страница 3: ...the device Maximum connection distance 1000 meters NC400 6 disconnection time Maximum 2 ms after the last byte Fixed communication speed Baud Rate 9600 bps Number of data bits 8 no parity Number of stop bits 1 Transmission onset and response time maximum of 100 ms after command RS 485 signals are D1 D D B Bidirectional data line Terminal 16 D0 D A Reserved bidirectional data line Terminal 17 C Opt...

Страница 4: ... polarity and current limits before connecting external devices to the auxiliary supply Inputs 8 and 9 are internally connected not isolated CONFIGURATION The proper operation of NC400 6 depends on the proper configuration of all parameters Read the manual carefully and thoroughly before using the equipment KEYBOARD AND DISPLAY OPERATION All configuration operations are performed through the front...

Страница 5: ...ues range from 0 00000 to 999999 with configurable decimal point Sp2 c Set Point 2 Counter Set point 2 value of the main counter Values range from 0 00000 to 999999 with configurable decimal point SP bat Set Point Batch Batch counter Set point value Values range from 0 to 999999 SP tot Set Point Totalizer Set point 1 value of the totalizer counter Values range from 0 00000 to 999999 with configura...

Страница 6: ...or off 0 key does not affect the totalizer counter 1 key resets totalizer counter if configured as reset 0 Remote reset does not affect the totalizer counter 1 Remote reset resets the totalizer counter 0 Set point 2 does not affect the totalizer counter 1 Resets totalizer counter when Totalizer Set point is triggered Opt sp c Option for Counter Setpoint Set point 1 reached 0 Actions corresponding ...

Страница 7: ...onfigured four NPN PNP dry contact or voltage pulse Low level 2 Vdc High level 3 Vdc Input Impedance 4700 Ω Maximum input voltage 30 Vdc Dry contact input polarization 5 V 4700 Ω Maximum counting frequency square wave 20 kHz in COUNT1 input for Coun tY 1 and COUNT UP 12 4 kHz in COUNT2 input for Coun tY 1 and COUNT UP 12 55 Hz for Coun tY 0 and Coun UP 12 4 kHz for both inputs Coun UP 12 Counting ...

Отзывы: