SPECIFICATIONS 

DIMENSIONS

: ................................................96 x 96 x 90 mm (1/4 DIN) 

 ............................................................... Approximate Weight: 330 g 

CUTOUT IN THE PANEL

: ............................ 93 x 93 mm (+0.5 -0.0 mm) 

POWER SUPPLY

: ........................ 100 to 240 Vac/dc (±10 %), 50/60 Hz 

Optional 24 V: ......................  12 to 24 Vdc / 24 Vac (-10 % / +20 %) 
 Consumo máximo: ...................................................................  6 VA 

ENVIRONMENTAL CONDITIONS

Operation Temperature: ..................................................  5 to 50 

Relative Humidity: .............................................. 80 % max. up 30 ºC 
For temperatures above 30 ºC, reduce 3 % for each ºC 
Internal  Use;  Category  of  installation  II,  Degree  of  pollution  2; 
altitude < 2000 m. 

INPUT

 .............................. Thermocouples, Pt100 (according to 

Table 1

Internal Resolution

: .......................................32767 levels (15 bits) 

Resolution of Display

: ......................................... 0.1 / 1 (°C / °F) 

Rate of input reading

: ...................................... up to 55 per second 

Precision @ 25 °C

: .......... 

J

K

T

,

 E

: 0.25 % of the 

span

 

1 ºC / °F 

 ......................................... 

N

R

S

B

: 0.25 % of the 

span

 

3 ºC / °F 

 ................................................................... Pt100: 0.2 % of the 

span

 

Input Impedance

: .................... Pt100 and thermocouples: >10 M

 

Measurement of Pt100

: .................. Three wires type, (

=0.00385) 

with compensation for cable length, excitation current of 0.170 mA. 
All  input  and  output  types  are  factory-calibrated.  Thermocouples 
according to standard NBR 12771 / 99, RTD’s NBR 13773 / 97; 

OUTPUTS 

OUTA / OUTB ................................. Relay SPST-NA: 3 A / 240 Vac,  
 .......................................... General use, resistive load; 100 k cycles 
OUTD .......................................... PULSE 12V / 0-20 mA or 4-20 mA 
 .................................................... 550 

 max. 31000 levels, Isolated 

ELECTROMAGNETIC COMPATIBILITY

 ............................................ EN 61326-1:1997 and EN 61326-1/A1:1998 

SAFETY

: .............................. EN61010-1:1993 and EN61010-1/A2:1995 

USB  INTERFACE

:  2.0,  CDC  class  (virtual  communications  port), 

MODBUS RTU protocol.

 

FRONT PANEL

: IP65, polycarbonate UL94 V-2;

 

CASE

: IP30, ABS+PC UL94 V-0; 

STARTS  UP  OPERATION

:  after  3  seconds  connected  to  the  power 

supply.

 

MODEL IDENTIFICATION 

The sticker on the controller presents the identification of the model, as 
described below. 

N960 - A  
Where A =

   ........................... 

24V

 for power supply 12 to 24 Vdc / 24 Vac 

 

 

 ............................................. 

blank

: power supply 100 to 240 Vac/dc 

SAFETY INFORMATION 

Any control system design should take into account that any part of the 
system has the potential to fail. This product is not a protection or safety 
device and its alarms are not intended to protect against product failures. 
Independent  safety  devices  should  be  always  provided  if  personnel  or 
property are at risk. 
Product  performance  and  specifications  may  be  affected  by  its 
environment  and  installation.  It’s  user’s  responsibility  to  assure  proper 
grounding,  shielding,  cable  routing  and  electrical  noise  filtering,  in 
accordance with local regulations, EMC standards and good installation 
practices.

 

SUPPORT AND MAINTENANCE 

This  product  contains  no  serviceable  parts  inside.  Contact  our  local 
distributor in case you need authorized service. For troubleshooting, visit 
our FAQ at m 

www.novusautomation.com

LIMITED WARRANTY AND LIMITATION OF LIABILITY 

NOVUS warrants to the original purchaser that this product is free from 
defects in material and workmanship under normal use and service within 
one  (1)  year  from  the  date  of  shipment  from  factory  or  from  its  official 
sales channel to the original purchaser. 
NOVUS liability under this warranty shall not in any case exceed the cost 
of correcting defects in the product or of supplying replacement product 
as herein provided and upon the expiration of the warranty period all such 
liability shall terminate. 
For  complete  information  on  warranty  and  liability  limitations,  check 
appropriate section in our web site: 

www.novusautomation.com/warranty

.

 

Содержание N960

Страница 1: ... 1300 ºC 454 to 2372 ºF R Tc R Range 50 to 1760 ºC 58 to 3200 ºF S Tc S Range 50 to 1760 ºC 58 to 3200 ºF B Tc B Range 400 to 1800 ºC 752 to 3272 ºF E Tc e Range 90 to 730 ºC 130 to 1346 ºF Pt100 Pt Range 199 9 to 850 ºC 328 to 1562 ºF Table 1 Types of sensors accepted by the controller CONTROL OUTPUTS AND ALARM OUTA OUTB OUTC AND OUTD The controller can have 2 3 or 4 outputs which can be configur...

Страница 2: ...within the cycle The upper display shows the parameter and the lower display shows the value of this parameter The and keys allow the operator to change the value of the shown parameter After accessing the last parameter of the cycle the controller returns to the Operation cycle indicating the temperature process and SP With the keyboard inactive for more than 20 seconds the controller also return...

Страница 3: ...gram SP Program SP s 0 to 9 Group of 10 values of SP that define the Ramp and Soak profile segments Pt1 Pt9 Program Time Time intervals of the program segments It defines the duration in minutes of each of the 9 program segments Configurable between 0 and 9999 minutes Pe1 Pe9 Program event Program Segment Alarm Event Alarm Parameters that define the alarm must be activated during the execution of ...

Страница 4: ...nction program the value 0 0 When the SP value is reached the controller starts to control the process in SP level by an interval of time or indefinitely The t SP parameter adjustable between 0 and 9999 minutes determines the level duration At the end of the level the control is disabled run no and all outputs are turned off With value 0 in t SP the control continues indefinitely without time limi...

Страница 5: ...n the A1SP and A2SP screens represent the values of these deviations Initial blocking prevents alarm activation when the controller is turned on until the temperature reaches the SP value for the first time The error alarm in the sensor allows to signalize errors in the sensor The Level End Function End t determines that the alarm be activated the end of the level With Event Alarm an alarm is acti...

Страница 6: ...IFICATION The sticker on the controller presents the identification of the model as described below N960 A Where A 24V for power supply 12 to 24 Vdc 24 Vac blank power supply 100 to 240 Vac dc SAFETY INFORMATION Any control system design should take into account that any part of the system has the potential to fail This product is not a protection or safety device and its alarms are not intended t...

Отзывы: