Novus N960 Скачать руководство пользователя страница 5

N960 Controller  

NOVUS AUTOMATION 

                                                                                                                                                

 

   5/6

 

SUCCESSIVE REPETITIONS OF A PROGRAM 

The  elaborated  program  can  be  repeated  several  times,  always 
restarting immediately after each execution. 
The 

rPt.p

  (

r

e

P

ea

t

 

P

rogram)  parameter,  in  the  Program  cycle, 

configures  the  number  of  times  the  program  must  be 

REPEATED

.  It 

determines the number of executions beyond the initial execution. 
With  zero  (0),  the  program  is  executed  only  one  time.  It  will  not  be 
repeated. 
Important: After the last execution of the program, all controller outputs 
are turned off and the 

RUN

 parameter changes to 

OFF

DETERMINATION OF PID PARAMETERS 

During  the 

automatic  tuning

  the  process  is  controlled  in  ON  /  OFF 

mode in the programmed SP - the Ramp to Level function is disabled. 
The 

automatic  tuning

  may  take  many  minutes  to  the  concluded, 

particularly  in  slow  processes.  Some  recommendations  for  the 
automatic tuning process are: 

 

Program SP to a value close to the point at which the process 
will operate after tuning. 

 

Enable  automatic  tuning  on  the  “

Atvn

”  screen  by  selecting 

yes

 

Program the value 

yes

 on the “

rvn

” screen. 

The “

TUNE

” indicator on the display stays lit until the completion of the 

automatic tuning

 process. 

During  the  execution  of  automatic  tuning,  large  oscillations  can  be 
induced  in  the  process  around  the  set  point.  Check  if  the  process 
supports these oscillations. 
If the automatic tuning does not result in a satisfactory control, refer to 

Table 3

 for guidelines on how to correct the behavior of the process. 

PARAMETER 

VERIFIED PROBLEM 

SOLUTION 

Proportional Band 

Slow answer 

Decrease 

Great oscillation 

Increase 

Rate of Integration 

Slow answer 

Increase 

Great oscillation 

Decrease 

Derivative Time 

Slow answer or 

instability 

Decrease 

Great oscillation 

Increase 

Table 3

 - Guidance for manual adjustment of the PID parameters 

ALARMS FUNCTIONS 

The  minimum  and  maximum  alarms  are  used  to  signalize  extreme 
temperature values. These extreme values are defined on the “

A1SP

” 

and “

A2SP

” screens. 

Differential alarms are used to signalize deviations between temperature 
and  set  point  control  (SP).  Values  defined  by  user  on  the  “

A1SP

”  and 

A2SP

” screens represent the values of these deviations. 

Initial blocking prevents alarm  activation when  the controller is turned 
on until the temperature reaches the SP value for the first time. 
The error alarm in the sensor allows to signalize errors in the sensor. 
The Level End Function (

End.t

) determines that the alarm be activated 

the end of the level. 
With Event Alarm, an alarm is activated during execution of a certain 
program segment. 

Table 4

 illustrates the operation of each alarm function, using alarm 1 

as  an  example,  and  presents  its  identification  code  on  the  “

A1Fv

”  e 

A2Fv

” screens. 

Using the Alarm 1 as example. 

PROMPT 

TYPE 

ACTION 

Off 

Disabled 

Output is not used as alarm. 

Lo 

 Minimum 

value 

(

Lo

w) 

 

SPAn 

PV 

ON 

 

Ki 

Maximum 

value 

(

Hi

gh) 

 

SPAn 

PV 

ON 

 

Dif 

Differential 

(

diF

erential) 

 

SV 

PV 

SV + SPAn 

alarme 

SV - SPAn 

alarme 

ON 

ON 

 

 

SV 

PV 

SV - SPAn 

alarme 

SV + SPAn 

alarme 

ON 

 

Positive SPAn      

Negative SPAn      

Difl 

Minimum 

Differential  

(

diF

erential 

L

ow) 

SPAn positivo             SPAn negativo 

 

SV 

PV 

SV - SPAn 

ON 

     

 

SV 

PV 

SV - SPAn 

ON 

 

Difk 

Maximum 

Differential  

(

diF

erential 

H

igh) 

 

SV 

PV 

SV + SPAn 

ON 

 

 

SV 

PV 

SV + SPAn 

ON 

 

Positive SPAn      

Negative SPAn      

Ierr 

Sensor Break 

(

i

nput 

Err

or) 

Activated  when  the  input  signal  of  PV  is 
interrupted,  out  of  the  range  limits  or 
Pt100 in short-circuit. 

End.T 

End of Level  Activate at the end of the level time. 

Rs 

Event 

(

r

amp and 

S

oak) 

Can be activated at a specific segment of 
program. 

Table 4

 – Alarm functions 

Where SPAn refers to Setpoints of Alarm 

SPA1

 and 

SPA2

PROBLEMS WITH THE CONTROLLER 

Connection errors and inadequate programming are the most common 
errors  found  during  the  controller  operation.  A  final  review  may  avoid 
loss of time and damages. 
The  controller  displays  some  messages  to  help  the  user  identify 
problems. 

MESSAGE 

PROBLEM 

----

 

Open input. Without sensor or signal. 

Err1 

Err6

 

Configuration  or  connection  problem  in  the  Pt100 

cable 

Other error messages displayed by the controller can account for errors in 
the  input  connections  or  type  of  selected  input  non  compliant  with  the 
sensor or signal applied to the input. If errors persist, even after a review, 
contact the manufacturer. Inform also the device serial number. To find 
out the serial number, press 

 

 for more than 3 seconds.  

This information is necessary for eventual contact with the controller’s 
manufacturer. 

Содержание N960

Страница 1: ... 1300 ºC 454 to 2372 ºF R Tc R Range 50 to 1760 ºC 58 to 3200 ºF S Tc S Range 50 to 1760 ºC 58 to 3200 ºF B Tc B Range 400 to 1800 ºC 752 to 3272 ºF E Tc e Range 90 to 730 ºC 130 to 1346 ºF Pt100 Pt Range 199 9 to 850 ºC 328 to 1562 ºF Table 1 Types of sensors accepted by the controller CONTROL OUTPUTS AND ALARM OUTA OUTB OUTC AND OUTD The controller can have 2 3 or 4 outputs which can be configur...

Страница 2: ...within the cycle The upper display shows the parameter and the lower display shows the value of this parameter The and keys allow the operator to change the value of the shown parameter After accessing the last parameter of the cycle the controller returns to the Operation cycle indicating the temperature process and SP With the keyboard inactive for more than 20 seconds the controller also return...

Страница 3: ...gram SP Program SP s 0 to 9 Group of 10 values of SP that define the Ramp and Soak profile segments Pt1 Pt9 Program Time Time intervals of the program segments It defines the duration in minutes of each of the 9 program segments Configurable between 0 and 9999 minutes Pe1 Pe9 Program event Program Segment Alarm Event Alarm Parameters that define the alarm must be activated during the execution of ...

Страница 4: ...nction program the value 0 0 When the SP value is reached the controller starts to control the process in SP level by an interval of time or indefinitely The t SP parameter adjustable between 0 and 9999 minutes determines the level duration At the end of the level the control is disabled run no and all outputs are turned off With value 0 in t SP the control continues indefinitely without time limi...

Страница 5: ...n the A1SP and A2SP screens represent the values of these deviations Initial blocking prevents alarm activation when the controller is turned on until the temperature reaches the SP value for the first time The error alarm in the sensor allows to signalize errors in the sensor The Level End Function End t determines that the alarm be activated the end of the level With Event Alarm an alarm is acti...

Страница 6: ...IFICATION The sticker on the controller presents the identification of the model as described below N960 A Where A 24V for power supply 12 to 24 Vdc 24 Vac blank power supply 100 to 240 Vac dc SAFETY INFORMATION Any control system design should take into account that any part of the system has the potential to fail This product is not a protection or safety device and its alarms are not intended t...

Отзывы: