N960 Controller  

NOVUS AUTOMATION 

                                                                                                                                                

 

   2/6

 

documentation  of  your  supervisory  software  to  conduct  the 
MONITORING process. 
Follow  the  procedure  below  to  use  the  USB  communication  of  the 
equipment: 
1.

 

Download the 

NConfig

 software from our website and install it on 

your  computer.  The  USB  drivers  necessary  for  operating  the 
communication will be installed together with the software. 

2.

 

Connect the USB cable between the equipment and the computer. 
The  controller  does  not  have  to  be  connected  to  a  power  supply. 
The USB will provide enough power to operate the communication 
(other equipment functions cannot operate). 

3.

 

Open the 

NConfig

 software, configure the communication and start 

recognition of the device.  

 

 

The USB interface IS NOT SEPARATE from the signal 
input (PV) or the controller’s digital inputs and outputs. 
It  is  intended  for  temporary  use  during 
CONFIGURATION and MONITORING periods. For the 
safety  of  people  and  equipment,  it  must  only  be  used 
when  the  piece  of  equipment  is  completely 
disconnected  from  the  input/output  signals.  Using  the 
USB  in  any  other  type  of  connection  is  possible  but 
requires  a  careful  analysis  by  the  person  responsible 
for installing it. 

CONFIGURATION AND OPERATION 

Prior to first operation the controller should be fully configured. The user 
must  set  basic  parameters  as  temperature  type  (

TYPE

),  the  desired 

control set point (

SP

), the alarms set points (

A1SP

 and 

A2SP

), etc. 

The configuration can be performed directly on the controller or through 
the  USB  interface.  The 

NConfig

  software  (free)  is  the  configuration 

management  tool.  Connected  to  the  USB  of  a 

Windows

  computer,  the 

controller is recognized as a serial communications port (COM) running 
with a Modbus RTU protocol. 
Through the USB interface, even if disconnected from the power supply, 
the configuration performed in a piece of equipment can be can be saved 
in a file and repeated in other pieces of equipment that require the same 
configuration. 

PARAMETERS FLOW CHART 

The  programming  parameters  are  organized  in  5  different  levels 
(parameter groups): 

- Operation level 
- Tuning level 
- Program level 
- Input level 
- Calibration level 

When  Turned  On,  the  controller  displays  the  first  screen  of  the 
Operation  Cycle.  This  screen  shows  on  the  red  display  (top),  the 
measured temperature value (PV) and also the 

Set Point

 value of the 

process  (desired  temperature  for  the  process)  on  the  green  display 
(bottom).  During  operation,  the  controller  continues  showing  this 
screen. In order to access other screens of this cycle, just press 

All  other  Cycles  are  accessed  when  changes  are  required  to  the 
controller’s  configuration.  In  order  to  access  these  cycles  just 

hold 

down

 the 

 key for approximately three seconds. After this time, the 

controller displays the first parameter of the next cycle (Tuning Cycle). 
Holding the key down for three seconds, the next cycle (Input Cycle) is 
also accessed. 
Release the 

 key in the desired cycle. Press the 

 key again to 

access all other parameters of this cycle. The 

 key allows to return 

parameters within the cycle. 
The upper display shows  the  parameter  and the lower  display shows 
the value of this parameter. The 

 and 

 keys allow the operator 

to change the value of the shown parameter. 
After accessing the last parameter of the cycle, the controller returns to 
the Operation cycle, indicating the temperature process and SP. With 
the  keyboard  inactive  for  more  than  20  seconds,  the  controller  also 
returns to the Operation cycle.  

The  value  of  the  changed  parameter  is  saved  to  permanent  memory 
and used by the controller when going to the next parameter, or if no 
key is pressed within 20 seconds. 

PROTECTION OF CONFIGURATION 

The  controller  allows  to  protect  the  configuration  elaborated  by  the 
user,  avoiding  unauthorized  changes.  The  parameter 

Protection

 

(

PROt

),  in  the  Calibration  level,  determines  the  protection  strategy, 

limiting the access to particular levels, as shown by the table below. 

Protection 

Level 

Protected Cycles 

Only the Calibration level is protected. 

Input and Calibration level. 

Program, Input and Calibration level. 

Tuning, Program, Input and Calibration level. 

All levels are protected. 

 All cycles are protected. 

Table 2

 – Levels of Protection for the Configuration 

Access Password 

The protected levels, when accessed, request the user to provide the 

Access Password

 for granting permission to change the configuration 

of the parameters on these levels. 
The prompt 

PASS

 precedes the parameters on the protected levels.  

If no password is entered, the parameters of the protected levels can 
only be visualized. 
The  Access  Password  is  defined  by  the  user  in  the  parameter 
Password Change (

PAS.(

), present in the Calibration level. 

The new controllers leave the factory with the access password defined 
as 

1111

Protection of the access password 

The  controller  provides  a  security  system  that  helps  prevent  input  of 
numerous passwords trying to get the correct password. When 5 invalid 
passwords  in  a  row  are  identified,  the  controller  stops  accepting 
passwords for 10 minutes. 

Master Password 

The Master Password is intended for allowing the user to define a new 
password  in  the  event  of  it  being  forgotten.  The  Master  Password 
doesn’t grant access to all parameters, only to the Password Change 
parameter  (

PAS(

).  After  defining  the  new  password,  the  protected 

parameters may be accessed (and modified) using this new password. 
The master password is made up by the last three digits of the serial 
number of the controller 

added

 to the number 9000. 

As  an  example,  for  the  equipment  with  serial  number  07154321,  the 
master password is 9 3 2 1. 

OPERATION LEVEL 

TEMPERATURE 

INDICATION 

Control S

et 

P

oint 

Temperature indication (PV)

 

and control set point 

When  turned  on,  the  controller  indicates  the  process 
temperature  on  the  upper  display.  The  lower  display 
shows the SP value, which is the desired temperature 

for the process. 

rate

 

Rate

 

Temperature increase rate

. It allows the user to define 

the  increase  or  decrease  characteristic  of  the  process 
temperature,  the  current  value  to  the  value 
programmed in SP. The rate is defined in 

Degrees per 

minute

.  It  is  adjustable  from  0.0  to  100.0  °C  per 

minute. 
It  is  available  when  the 

Rate

  option  is  selected  in  the 

Pr.ty

 parameter of the Input cycle. 

Содержание N960

Страница 1: ... 1300 ºC 454 to 2372 ºF R Tc R Range 50 to 1760 ºC 58 to 3200 ºF S Tc S Range 50 to 1760 ºC 58 to 3200 ºF B Tc B Range 400 to 1800 ºC 752 to 3272 ºF E Tc e Range 90 to 730 ºC 130 to 1346 ºF Pt100 Pt Range 199 9 to 850 ºC 328 to 1562 ºF Table 1 Types of sensors accepted by the controller CONTROL OUTPUTS AND ALARM OUTA OUTB OUTC AND OUTD The controller can have 2 3 or 4 outputs which can be configur...

Страница 2: ...within the cycle The upper display shows the parameter and the lower display shows the value of this parameter The and keys allow the operator to change the value of the shown parameter After accessing the last parameter of the cycle the controller returns to the Operation cycle indicating the temperature process and SP With the keyboard inactive for more than 20 seconds the controller also return...

Страница 3: ...gram SP Program SP s 0 to 9 Group of 10 values of SP that define the Ramp and Soak profile segments Pt1 Pt9 Program Time Time intervals of the program segments It defines the duration in minutes of each of the 9 program segments Configurable between 0 and 9999 minutes Pe1 Pe9 Program event Program Segment Alarm Event Alarm Parameters that define the alarm must be activated during the execution of ...

Страница 4: ...nction program the value 0 0 When the SP value is reached the controller starts to control the process in SP level by an interval of time or indefinitely The t SP parameter adjustable between 0 and 9999 minutes determines the level duration At the end of the level the control is disabled run no and all outputs are turned off With value 0 in t SP the control continues indefinitely without time limi...

Страница 5: ...n the A1SP and A2SP screens represent the values of these deviations Initial blocking prevents alarm activation when the controller is turned on until the temperature reaches the SP value for the first time The error alarm in the sensor allows to signalize errors in the sensor The Level End Function End t determines that the alarm be activated the end of the level With Event Alarm an alarm is acti...

Страница 6: ...IFICATION The sticker on the controller presents the identification of the model as described below N960 A Where A 24V for power supply 12 to 24 Vdc 24 Vac blank power supply 100 to 240 Vac dc SAFETY INFORMATION Any control system design should take into account that any part of the system has the potential to fail This product is not a protection or safety device and its alarms are not intended t...