N1100HC Controller 

NOVUS AUTOMATION 

5/7 

7.3

 

CONTROL # 2 PARAMETERS 

Pb2

Pb2

Pb2

Pb2 

 

 

 

PROPORTIONAL  BAND:  Percentage  of  maximum 
input span. Select zero for ON/OFF control.  

Olap

Olap

Olap

Olap 

 

 

 

(

o

ver

LAP

): defines the overlap between the heat and cool 

outputs.  The  overlap  is  given  in  engineering  units  of  the 
input type used.  

When the overlap value is negative, it represents the value 
of the dead-band instead. 

If  PB2=0,  the  overlap  parameter  is  changed  to  represent 
the hystesesis value for control #2.  

[t2

[t2

[t2

[t2 

 

 

 

CYCLE TIME: PWM period in seconds. Can only be 
viewed if proportional band is other than zero.  

A[t2

A[t2

A[t2

A[t2 

 

 

 

CONTROL ACTION: For Auto Mode only. 

  Reverse Action 

rE

rE

rE

rE

 

usually used for heating. 

  Direct Action 

dir

dir

dir

dir

 

usually used for cooling. 

O2ll

O2ll

O2ll

O2ll 

 

 

 

OUTPUT LOW LIMIT: minimum percentage value for 

MV  (Manipulated  Variable)  when  in  automatic 
control and PID. Default value: 0.0 % 

O2kl

O2kl

O2kl

O2kl 

 

 

 

OUTPUT  HIGH  LIMIT:  Maximum  percentage  value 

for MV when in automatic control and PID. Default 
value: 100.0 % 

7.4

 

RAMP AND SOAK PROFILE PROGRAMMING CYCLE  

tbas

tbas

tbas

tbas

 

TIME BASE: Selects the time base for the ramp and 
soak. Valid for all profile programs. 

  

0

0

0

 

 

 

PT1

 to 

PT7

 values are in seconds; 

  

1

1

1

1

  - 

PT1

 to 

PT7

 values are in minutes; 

Pr n

Pr n

Pr n

Pr n

 

PROGRAM  TO  BE  VIEWED:  Selects  the  ramp  and 
soak  profile  program  to  be  edited/viewed  in  the 
following cycle prompts (7 programs available).  

ptol

ptol

ptol

ptol

 

RAMP  AND  SOAK  TOLERANCE:  maximum 
deviation  between  PV  and  SV.  Whenever  this 
deviation is exceeded the time counter is halted until 
deviation  lowers  to  within  the  tolerance.  Set  zero  to 
disable this function. 

Psp0

Psp0

Psp0

Psp0

 

Psp5

Psp5

Psp5

Psp5

 

RAMP AND SOAK SET POINTS (0 to 5): Set of 8 SV 
values  which  define  the  ramp  and  soak  profile 
segments. See also 

PT1

 to 

5

 and 

PE1

 to 

5

 below. 

Pt1

Pt1

Pt1

Pt1

 

Pt5

Pt5

Pt5

Pt5

 

RAMP AND SOAK SEGMENTS TIME (1 to 5): Set of 
5  time  intervals  in  minutes  (9999  max.)  for  the  5 
segments of the ramp and soak program. 

Pe1

Pe1

Pe1

Pe1

 

Pe5

Pe5

Pe5

Pe5

 

RAMP AND SOAK EVENT (1 to 5): Set of 5 values 
that define which alarms must be activated during a 
ramp and soak program segment. 

Alarm function depends on “

rS

rS

rS

rS

” setting (

Table 3

). 

lp

lp

lp

lp

 

LINK  TO  PROGRAM:  Number  of  the  next  profile 
program  to  be  linked  to  follow  the  current  profile. 
Profiles can be linked to make larger programs of up 
to 49 segments. 

7.5

 

ALARM CYCLE 

Fva1

Fva1

Fva1

Fva1

 

ALARM 1 FUNCTION: Select options from 

Table 3

Fva2

Fva2

Fva2

Fva2

 

ALARM 2 FUNCTION: Select options from 

Table 3

Fva3

Fva3

Fva3

Fva3

 

ALARM 3 FUNCTION: Select options from 

Table 3

Fva4

Fva4

Fva4

Fva4

 

ALARM 4 FUNCTION: Select options from 

Table 3

bla1 

bla1 

bla1 

bla1 
bla2 

bla2 

bla2 

bla2 
bla3 

bla3 

bla3 

bla3 
bla4

bla4

bla4

bla4

 

ALARM  BLOCK  1  TO  4:  This  function  blocks  the 
alarm at power-up when the units is first energized. 

YES

  enables  and 

NO

  inhibits  this  blocking  function. 

When enabled the alarm will not be active at power-
up waiting for PV (Process Variable) to reach a non-
alarm situation. From this point  on the alarm will  be 
free to actuate should a new alarm situation occur. 

xya1

xya1

xya1

xya1

 

ALARM  1  HYSTERESIS:  Defines  the  differential 
range  between  the  PV  value  at  which  the  alarm  is 
turned  on  and  the  value  at  which  it  is  turned  off  (in 
engineering units). 

xya2

xya2

xya2

xya2

 

ALARM 2 HYSTERESIS:  Same as above. 

xya3

xya3

xya3

xya3

 

ALARM 3 HYSTERESIS: Same as above. 

xya4

xya4

xya4

xya4

 

ALARM 4 HYSTERESIS: Same as above. 

A1t1

A1t1

A1t1

A1t1

 

ALARM 1 TIME 1:  Defines the time (6500 sec. max.) 
during which the alarm 1 output will be 

ON

 when alarm 

1 is active. Program zero to disable this function. 

A1t2

A1t2

A1t2

A1t2

 

ALARM 1 TIME 2:  Defines the 

OFF

 state time for the 

alarm  1  output,  after  being 

ON

  during  the  time 

selected  on  ALARM  1  TIME  1.  Program  zero  to 
disable this function. 

A2t1

A2t1

A2t1

A2t1

 

ALARM 2 TIME 1: Defines the time (6500 sec. max.) 
during which the alarm 1 output will be 

ON

 when alarm 

1 is active. Program zero to disable this function  

A2t2

A2t2

A2t2

A2t2

 

ALARM 2 TIME 2:  Defines the time during which the 
alarm 2 output will be, after being 

ON

 during the time 

selected  on  ALARM  2  TIME  1.  Program  zero  to 
disable  this  function. 

Table  4

  shows  the  advanced 

features  that  can  be  achieved  with  these  time 
functions. 

7.6

 

CONFIGURATION CYCLE  

type

type

type

type

 

INPUT  TYPE:  Selects  the  input  signal  type  to  be 
connected  to  the  process  variable  input.  Refer  to 

Table 1

This is the first parameter to be set.

 

dppo

dppo

dppo

dppo

 

DECIMAL POINT POSITION: For input types 16, 17, 
18  or  19  only.  Selects  the  decimal  point  position  to 
be viewed in both PV and SV.  

vn

vn

vn

vn

 I

 I

 I

 I

    

t

t

t

t

 

TEMPERATURE INDICATION IN ºC OR ºF: Selects 
the display indication to be in ºC or ºF. Only available 
if input type is other than 16, 17, 18 or 19. 

offs

offs

offs

offs

 

SENSOR OFFSET: Offset value to  be added to the 
PV to compensate sensor error. Default value: zero. 

spll

spll

spll

spll

 

SET POINT LOW LIMIT:  

- Linear inputs: Sets the lower range for SV and PV 
indication. 

- T/C and Pt100 inputs: sets the lower range for SV. 

sp

sp

sp

spxl

xl

xl

xl

 

SET POINT HIGH LIMIT:  

- Linear inputs: Sets the upper range for SV and PV 
indication. 

- T/C and Pt100 inputs: sets the upper range for SV. 

rsll

rsll

rsll

rsll

 

REMOTE SET POINT LOW LIMIT: Selects the lower 
range for indication of the Remote Setpoint. 

rsxl

rsxl

rsxl

rsxl

 

REMOTE  SET  POINT  HIGH  LIMIT:  Selects  the 
upper range for indication of the Remote Setpoint. 

bavd

bavd

bavd

bavd

 

DIGITAL COMMUNICATON BAUD RATE 
SELECTION:  
0: 1200 bps; 1: 2400 bps; 2: 4800 bps; 3: 9600 bps; 
4: 19200 bps. 

addr

addr

addr

addr

 

SLAVE ADDRESS SELECTION:  Identifies a slave in 
the network. The possible address numbers are from 
1 to 247. 

Содержание N1100HC

Страница 1: ...e resistance compensation Analog output 0 20 mA or 4 20 mA 1500 levels 550 Ω max CONTROL OUTPUT Standard Version up to 3 outputs Two 3 A 250 Vac Relays 3 A 30 Vdc Isolated 0 20 mA or 4 20 mA control output or PV or SP retransmission 1500 level resolution 550 Ω max Load Logic pulse for SSR drive 0 or 20 mA Any of the above and options 1 and 2 can be selected as the main control output and the remai...

Страница 2: ...60 C 32 a 3200 ºF S 5 5 5 5 range 0 to 1760 C 32 to 3200 ºF Pt100 6 6 6 6 range 199 9 to 530 0 C 328 0 to 986 0 ºF Pt100 7 7 7 7 range 200 to 530 C 328 to 986 ºF 4 20 mA 8 8 8 8 J linearization Programmable range 110 to 760 C 4 20 mA 9 9 9 9 K linearization Programmable range 150 to 1370 C 4 20 mA 10 10 10 10 T linearization Programmable range 160 to 400 C 4 20 mA 11 11 11 11 N Linearization Faixa...

Страница 3: ...The 3 modes of operation are pulse delayed actuation oscillator The desired function can be achieved programming the parameters A1t1 A1t1 A1t1 A1t1 A1t2 A1t2 A1t2 A1t2 A2t1 A2t1 A2t1 A2t1 and A2t2 A2t2 A2t2 A2t2 see Table 4 The LEDs associated to the alarms will light when the alarm condition is recognized not following the actual state of the output which may be temporarily OFF because of the tem...

Страница 4: ...vto avto CONTROL MODE YES indicates automatic control mode closed loop PID or ON OFF NO indicates manual control mode open loop Bumpless transfer from auto to manual mode is available If in doubt program YES PV Indication Red MV Indication Green MANIPULATED VARIABLE VALUE MV The upper display shows PV value and the lower display shows the percentage of MV applied to the control output When in manu...

Страница 5: ...bla4 bla4 bla4 bla4 ALARM BLOCK 1 TO 4 This function blocks the alarm at power up when the units is first energized YES enables and NO inhibits this blocking function When enabled the alarm will not be active at power up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 xya1 xya1 xya1 ALARM 1 ...

Страница 6: ...optional hardware accessories The parameters menu will show the parameters relative to the optional hardware 0 no optionals or c RS485 only 1 relay 3 I O 3 2 Digital I O 2 inputs outputs 3 Heater break protection option Rsl REMOTE SET POINT LOW CALIBRATION Sets the Remote Set Point low calibration offset Several keystrokes at or might be necessary to increment one digit Rsx REMOTE SET POINT HIGH C...

Страница 7: ...troller resumes at the beginning of the segment it was previously 10 AUTO TUNE During auto tune the process is controlled in ON OFF mode at the programmed SetPoint SV Depending on the process characteristics large oscillations above and below SV may occur and auto tuning may take several minutes to be concluded The recommended procedure is as follows Disable the control output at the rvn rvn rvn r...

Отзывы: