Novus N1100HC Скачать руководство пользователя страница 2

N1100HC Controller 

NOVUS AUTOMATION 

2/7 

A1, A2, A3 and A4 Indicators

: Status of the alarms. 

 

  - 

PROG key

: used to walk through the menu cycles 

 

  - 

BACK key

: go back to the previous displayed parameter 

 

  - 

INCREASE  and 

 

  - 

DECREASE  keys

:  Used  to  change 

parameter values. 

When the controller is turned on, its firmware version is displayed for 
3  seconds,  after  which  the  controller  starts  normal  operation.  The 
values of PV and SV are displayed and the outputs are enabled. 

Before  the  controller  is  ready  to  be  used  in  a  given  process,  it 
requires some basic configuration, such as: 

 

input  type  (TC,  Pt100,  4-20  mA,...)    at  the  “

tYPE

tYPE

tYPE

tYPE

”  prompt, 

according to 

Table 1

 

output type (relay, 0-20 mA,  4-20 mA or  pulse) at   “

I/O 1

”,  “

I/O 

2

”,... “

I/O 5

” prompts (see 

Table 2

); 

 

setpoint variable SV. Set the remaining parameters. 

 

PID parameters (or hysteresis for ON/OFF control) 

Other functions, including alarms, ramp and soak, timer, digital input, 
etc., may be useful for a better system performance. 

The parameters are grouped in 7 cycles. 

Cycle 

Access 

1- Operation 

Free access parameters * 

2- Tuning 

 

3- R&S Program 

 

4- Alarms 

Reserved access parameters ** 

5- Input Configuration 

 

6- I/Os 

 

7- Calibration 

 

*These parameters can be viewed but not changed if the cycle 
is protected. 

**Requires a key combination to access the cycle. 

Press 

 

 to advance and 

 

 to go back in the menu cycle.  

Keep pressing the 

 

 or 

 

 key to move fast forward or backward. 

Press 

 

 and 

 

 simultaneously to move from one cycle to the next 

one. 

At the end of each cycle the controller returns to the operation cycle. 

4

 

PROGRAM SECURITY  

Each menu cycle can be locked (protected) by pressing 

 

 and 

 

 

simultaneously  for  3  seconds.  Press 

 

  and 

 

  for  3  seconds  to 

unlock. A short blink of the display confirms the lock/unlock change. 
This  will  alternately  lock  or  unlock  the 

 

  and 

 

  keys  to  avoid 

tampering. 

For further protection, the unlock operation through the keypad may 
be  disabled  by  changing  the  position  of  an  internal  strap  inside  the 
controller: 

When 

PROT

  is 

OFF

,  the  user  is  allowed  to  lock  and  unlock  the 

cycles  using  the  keypad  as  explained  above.  If 

PROT

  is 

ON

,  the 

cycles lock/unlock operation is disable.  

5

 

CONFIGURATION: 

5.1

 

INPUT TYPE SELECTION 

Select the input type (in parameter “

tYPE

tYPE

tYPE

tYPE

”) from 

Table 1

 below. 

 

 

 

TYPE 

CODE 

CHARACTERISTICS 

0

0

0

 

 

 

range: -50 to 760 °C (-58 to 1400 ºF) 

1

1

1

 

 

 

range: -90 to  1370 °C (-130 to 2498 ºF) 

2

2

2

 

 

 

range: -100 to 400 °C (-148 to 752 ºF) 

3

3

3

 

 

 

range: -90 a 1300 °C (-130 a 2372 ºF) 

4

4

4

 

 

 

range: 0 a 1760 °C (32 a 3200 ºF) 

5

5

5

 

 

 

range: 0 to 1760 °C (32 to 3200 ºF) 

Pt100 

6

6

6

 

 

 

range: -199.9 to 530.0 °C (-328.0 to 986.0 ºF) 

Pt100 

7

7

7

 

 

 

range: -200 to 530 °C (-328 to 986 ºF) 

4-20 mA 

8

8

8

 

 

 

J linearization.  Programmable range: -110 to 760 °C 

4-20 mA 

9

9

9

 

 

 

K linearization. Programmable range: -150 to 1370 °C 

4-20 mA 

10

10

10

10 

 

 

 

T linearization. Programmable range: -160 to 400 °C 

4-20 mA 

11

11

11

11 

 

 

 

N Linearization. Faixa prog.: -90 a 1370 °C 

4-20 mA 

12

12

12

12 

 

 

 

R Linearization. Faixa prog.: 0 a 1760 °C 

4-20 mA 

13

13

13

13 

 

 

 

S  linearization. Programmable Range: 0 to 1760 °C 

4-20 mA 

14

14

14

14 

 

 

 

Pt100  linearization. Prog. Range:-200.0 to 530.0 °C 

4-20 mA 

15

15

15

15 

 

 

 

Pt100  linearization Prog. Range:-200 to 530 °C 

0 to 50mV 

16

16

16

16 

 

 

 

Linear.   Programmable indication -1999 to 9999 

4-20 mA 

17

17

17

17 

 

 

 

Linear.   Programmable indication -1999 to 9999 

0 to 5Vdc 

18

18

18

18 

 

 

 

Linear.   Programmable indication -1999 to 9999 

4 to 20mA 

19

19

19

19 

 

 

 

Square Root Extraction 

Table 1

 - Input Types 

5.2

 

OUTPUTS, ALARMS AND DIGITAL INPUTS CONFIGURATION 

The  controller  input/output  channels  can  assume  multiple  functions, 
depending  on  configuration:  control  output,  alarm  output,  digital 
output,  digital  input,  and  PV  or  SV  analog  retransmission.  This 
channels are identified as 

I/O1, I/O2, I/O3, I/O4 

and

 I/O 5

I/O features on standard model are the following: 

 

I/O 1-  Relay output SPST-NA; 

 

I/O 2-  Relay output SPST-NA; 
I/O 5-  current output, digital output, digital input; 

Controller accepts an optional I/O board that may be ordered with the 
following  functions.  See  product 

Identification

  topic  for  the 

appropriate identification codes: 

3R

I/O3 with relay output SPDT; 

DIO

:  I/O3 and I/O4 as input channels and digital output; 

I/O  functions  are  user  defined  according  to  options  presented  on 

Table 2

. Only valid options for the I/O channel being configured will 

be available for selection. 

I/O channels will start operation 3 seconds after controller power up. 

The description for the functions follows: 

 

CODE 0 - No function. The I/O channel programmed with code 0 
will  not  be  used  by  the  controller.  It  is  available  to  be  used  by 
serial communication as digital output. 

 

CODES  1  to  4  -  Alarm  output  -  Available  for  all  I/O  channels.  
The selected channel can be used as output to Alarms 1 to 4.  

 

CODE 5 - PWM control output 1 - Available for all I/O channels. 

 

CODE 6 - PWM control output 2 - Available for all I/O channels. 

 

CODE 7 - Digital input - Standard for I/O5 and optional for I/O3 
and I/O4. 

 Closed:  Manual control 
 Opened: Automatic control 

 

CODE 8 - Digital input - Standard for I/O5 and optional for I/O3 
and I/O4. Start/Stop input (“

rvn

rvn

rvn

rvn

”: 

YES

YES

YES

YES

 / 

no

no

no

no

). 

Closed:  outputs enabled 
Opened: outputs disabled 

Содержание N1100HC

Страница 1: ...e resistance compensation Analog output 0 20 mA or 4 20 mA 1500 levels 550 Ω max CONTROL OUTPUT Standard Version up to 3 outputs Two 3 A 250 Vac Relays 3 A 30 Vdc Isolated 0 20 mA or 4 20 mA control output or PV or SP retransmission 1500 level resolution 550 Ω max Load Logic pulse for SSR drive 0 or 20 mA Any of the above and options 1 and 2 can be selected as the main control output and the remai...

Страница 2: ...60 C 32 a 3200 ºF S 5 5 5 5 range 0 to 1760 C 32 to 3200 ºF Pt100 6 6 6 6 range 199 9 to 530 0 C 328 0 to 986 0 ºF Pt100 7 7 7 7 range 200 to 530 C 328 to 986 ºF 4 20 mA 8 8 8 8 J linearization Programmable range 110 to 760 C 4 20 mA 9 9 9 9 K linearization Programmable range 150 to 1370 C 4 20 mA 10 10 10 10 T linearization Programmable range 160 to 400 C 4 20 mA 11 11 11 11 N Linearization Faixa...

Страница 3: ...The 3 modes of operation are pulse delayed actuation oscillator The desired function can be achieved programming the parameters A1t1 A1t1 A1t1 A1t1 A1t2 A1t2 A1t2 A1t2 A2t1 A2t1 A2t1 A2t1 and A2t2 A2t2 A2t2 A2t2 see Table 4 The LEDs associated to the alarms will light when the alarm condition is recognized not following the actual state of the output which may be temporarily OFF because of the tem...

Страница 4: ...vto avto CONTROL MODE YES indicates automatic control mode closed loop PID or ON OFF NO indicates manual control mode open loop Bumpless transfer from auto to manual mode is available If in doubt program YES PV Indication Red MV Indication Green MANIPULATED VARIABLE VALUE MV The upper display shows PV value and the lower display shows the percentage of MV applied to the control output When in manu...

Страница 5: ...bla4 bla4 bla4 bla4 ALARM BLOCK 1 TO 4 This function blocks the alarm at power up when the units is first energized YES enables and NO inhibits this blocking function When enabled the alarm will not be active at power up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 xya1 xya1 xya1 ALARM 1 ...

Страница 6: ...optional hardware accessories The parameters menu will show the parameters relative to the optional hardware 0 no optionals or c RS485 only 1 relay 3 I O 3 2 Digital I O 2 inputs outputs 3 Heater break protection option Rsl REMOTE SET POINT LOW CALIBRATION Sets the Remote Set Point low calibration offset Several keystrokes at or might be necessary to increment one digit Rsx REMOTE SET POINT HIGH C...

Страница 7: ...troller resumes at the beginning of the segment it was previously 10 AUTO TUNE During auto tune the process is controlled in ON OFF mode at the programmed SetPoint SV Depending on the process characteristics large oscillations above and below SV may occur and auto tuning may take several minutes to be concluded The recommended procedure is as follows Disable the control output at the rvn rvn rvn r...

Отзывы: