Novus N1100HC Скачать руководство пользователя страница 3

N1100HC Controller 

NOVUS AUTOMATION 

3/7 

CODE 

I/O Type 

I/O Function 

0

0

0

 

 

 

Digital Output 

Digital Output to be set by the serial comm. 

1

1

1

 

 

 

Digital Output 

Alarm 1 Output 

2

2

2

 

 

 

Digital Output 

Alarm 2 Output 

3

3

3

 

 

 

Digital Output 

Alarm 3 Output 

4

4

4

 

 

 

Digital Output 

Alarm 4 Output 

5

5

5

 

 

 

Digital Output 

 PWM Control Output 1 

6

6

6

 

 

 

Digital Output 

PWM Control Output 2 

7

7

7

 

 

 

Digital Input 

Automatic/Manual mode change 

8

8

8

 

 

 

Digital Input 

Run/Stop mode change 

9

9

9

 

 

 

Digital Input 

Reserved 

10

10

10

10 

 

 

 

Digital Input 

Executes/Holds selected ramp and soak profile 

11

11

11

11 

 

 

 

Digital Input 

Enable/Disable R&S profile 1 selection 

12

12

12

12 

 

 

 

Analog Output 

4 to 20 mA Analog control output 1 

13

13

13

13 

 

 

 

Analog Output 

0 to 20 mA Analog control output 1 

14

14

14

14 

 

 

 

Analog Output 

4 to 20 mA PV retransmission 

1

1

1

15

5

5

 

 

 

Analog Output 

0 to 20 mA PV retransmission 

16

16

16

16 

 

 

 

Analog Output 

4 to 20 mA SP retransmission 

17

17

17

17 

 

 

 

Analog Output 

0 to 20 mA SP retransmission 

18

18

18

18 

 

 

 

Analog Output 

4 to 20 mA control output 2 

19

19

19

19 

 

 

 

Analog Output 

0 to 20 mA control output 2 

Table 2

 - I/O channel functions 

 

CODE 9 - Digital input - Reserved 

 

CODE 10 - Digital input - Standard for I/O5 and optional for I/O3 
and I/O4. 

    

Opened: enables R&S program 
Closed:  holds  R&S  program  (the  program  resumes 
when the contact is opened again) 

 

CODE 11 - Digital input - Standard for I/O5 and optional for I/O3 
and I/O4.  

Selects R&S program 1. 

Used  to  alternate  between  the  main  Setpoint  and  a  second 
Setpoint defined by the R&S program 1. 

    

Closed:  selects program 1 

    

Opened: uses main Setpoint 

 

CODES 12 to 13 - Control Output 1 (0-20 / 4-20 mA) - Available 
only for I/O5. 
Configures channel I/O5 to operate as control output 1 with 0-20 
or 4-20 mA signal. 

 

CODES  14  to  17  -  Analog  retransmission.  Available  only  for 
I/O5.  Configures  I/O5  to  output  a  0-20  mA  or  4-20  mA  analog 
signal proportional to PV or SP. 

 

CODES 18 to 19 – Control Output 2 (0-20 / 4-20 mA) - Available 
only for I/O5. 
Configures channel I/O5 to operate as control output 2 with 0-20 
or 4-20 mA signal. 

5.3

 

ALARM CONFIGURATION 

The  controller  has  4  alarms.  Only  alarms 

1

  and 

2

  have  front  panel 

lamps associated to them. 

The alarms can the configured to operate in any of the nine functions 
listed on 

Table 3

5.4

 

ALARM TIMER FUNCTIONS 

Alarms 1 and 2 can be programmed to have timer functions. The 3 
modes of operation are: 

- pulse  

 

- delayed actuation   

 

- oscillator 

The desired function can  be achieved programming the parameters 

A1t1

A1t1

A1t1

A1t1

”, “

A1t2

A1t2

A1t2

A1t2

”, “

A2t1

A2t1

A2t1

A2t1

” and “

A2t2

A2t2

A2t2

A2t2

” (see 

Table 4

). 

The  LEDs  associated  to  the  alarms  will  light  when  the  alarm 
condition  is  recognized,  not  following  the  actual  state  of  the  output, 
which may be temporarily OFF because of the temporization. 

TYPE 

PROMPT 

ACTION 

Disabled 

off

off

off

off

 

No active alarm. This output can be 

used as a digital output to be set by the 

serial communication. 

Sensor Break 

(

i

nput 

Err

or) 

ierr

ierr

ierr

ierr

 

Alarm will be ON if PV sensor breaks, 
input signal is out of range or Pt100 is 

shorted. 

Event Alarm 

(

r

amp and 

S

oak) 

rs

rs

rs

rs

 

Can be activated at a specific segment 

of ramp and soak program. 

Heater break 

detection 

r

esistance 

fail

 

rfail

rfail

rfail

rfail

 

Detects a heater broken condition 

 

Lo

w Alarm 

lo

lo

lo

lo

 

SPAn

PV

 

Hi

gh Alarm 

ki

ki

ki

ki

 

SPAn

PV

 

LOW  

Differential 

difl

difl

difl

difl

 

positive SPAn         

SV

PV

SV + SPAn

 

negative SPAn 

SV

PV

SV + SPAn

 

HIGH  

Differential  

difk

difk

difk

difk

 

positive SPAn         

SV

PV

SV + SPAn

 

negative SPAn       

SV

PV

SV + SPAn

 

Dif

ferential 

dif

dif

dif

dif

 

positive SPAn         

SV

PV

SV + SPAn

SV - SPAn

 

negative SPAn         

SV

PV

SV + SPAn

SV - SPAn

 

Table 3

 - Alarm functions 

Where SPAn means “

SPA1

SPA1

SPA1

SPA1

”, “

SPA2

SPA2

SPA2

SPA2

”, “

SPA2

SPA2

SPA2

SPA2

” and “

SPA4

SPA4

SPA4

SPA4

”. 

Alarm 

Function 

T1 

T2 

 

ACTION 

Normal 

Alarm Event

Alarm

Output

 

Delayed 

1 s to 

6500 s 

Alarm Event

Alarm

Output

T2

 

Pulse 

1 s to 

6500 s 

Alarm Event

Alarm

Output

T1

 

Oscillator 

1 s to 

6500 s  

1 s to 

6500 s 

Alarm Event

Alarm

Output
alarme

T1

T2

T1

 

Table 4

 - Advanced Timer Alarm (for alarms 1 or 2): 

5.5

 

ALARM INITIAL BLOCKING 

The initial blocking option inhibits the alarm from being recognized if 
an  alarm  condition  is  present  when  the  controller  is  first  energized. 
The  alarm  will  actuate  only  after  the  occurrence  of  a  non  alarm 
condition followed by a new occurrence for the alarm. 

The initial blocking is disabled for the 

sensor break

 alarm function. 

5.6

 

ANALOG RETRANSMISSION OF PV AND SP 

The analog output, when not used for control purposes, is available 
for  retransmitting  the  SV  and  SP  values  in  0-20  or  4-20  mA.  This 
analog output is electrically isolated from other inputs and outputs. 

The analog output signal is scaleable, with the output range determined 
by the values programmed in the parameters “

SPLL

SPLL

SPLL

SPLL

” and “

SPkL

SPkL

SPkL

SPkL

”. 

To  obtain  a  voltage  output,  connect  a  resistor  shunt  to  the  current 
output terminals (terminal 7 and 8). 

Содержание N1100HC

Страница 1: ...e resistance compensation Analog output 0 20 mA or 4 20 mA 1500 levels 550 Ω max CONTROL OUTPUT Standard Version up to 3 outputs Two 3 A 250 Vac Relays 3 A 30 Vdc Isolated 0 20 mA or 4 20 mA control output or PV or SP retransmission 1500 level resolution 550 Ω max Load Logic pulse for SSR drive 0 or 20 mA Any of the above and options 1 and 2 can be selected as the main control output and the remai...

Страница 2: ...60 C 32 a 3200 ºF S 5 5 5 5 range 0 to 1760 C 32 to 3200 ºF Pt100 6 6 6 6 range 199 9 to 530 0 C 328 0 to 986 0 ºF Pt100 7 7 7 7 range 200 to 530 C 328 to 986 ºF 4 20 mA 8 8 8 8 J linearization Programmable range 110 to 760 C 4 20 mA 9 9 9 9 K linearization Programmable range 150 to 1370 C 4 20 mA 10 10 10 10 T linearization Programmable range 160 to 400 C 4 20 mA 11 11 11 11 N Linearization Faixa...

Страница 3: ...The 3 modes of operation are pulse delayed actuation oscillator The desired function can be achieved programming the parameters A1t1 A1t1 A1t1 A1t1 A1t2 A1t2 A1t2 A1t2 A2t1 A2t1 A2t1 A2t1 and A2t2 A2t2 A2t2 A2t2 see Table 4 The LEDs associated to the alarms will light when the alarm condition is recognized not following the actual state of the output which may be temporarily OFF because of the tem...

Страница 4: ...vto avto CONTROL MODE YES indicates automatic control mode closed loop PID or ON OFF NO indicates manual control mode open loop Bumpless transfer from auto to manual mode is available If in doubt program YES PV Indication Red MV Indication Green MANIPULATED VARIABLE VALUE MV The upper display shows PV value and the lower display shows the percentage of MV applied to the control output When in manu...

Страница 5: ...bla4 bla4 bla4 bla4 ALARM BLOCK 1 TO 4 This function blocks the alarm at power up when the units is first energized YES enables and NO inhibits this blocking function When enabled the alarm will not be active at power up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 xya1 xya1 xya1 ALARM 1 ...

Страница 6: ...optional hardware accessories The parameters menu will show the parameters relative to the optional hardware 0 no optionals or c RS485 only 1 relay 3 I O 3 2 Digital I O 2 inputs outputs 3 Heater break protection option Rsl REMOTE SET POINT LOW CALIBRATION Sets the Remote Set Point low calibration offset Several keystrokes at or might be necessary to increment one digit Rsx REMOTE SET POINT HIGH C...

Страница 7: ...troller resumes at the beginning of the segment it was previously 10 AUTO TUNE During auto tune the process is controlled in ON OFF mode at the programmed SetPoint SV Depending on the process characteristics large oscillations above and below SV may occur and auto tuning may take several minutes to be concluded The recommended procedure is as follows Disable the control output at the rvn rvn rvn r...

Отзывы: