Novus N1100HC Скачать руководство пользователя страница 4

N1100HC Controller 

NOVUS AUTOMATION 

4/7 

5.7

 

SOFT-START

 

Defines  the  time  interval  for  the  output  to  reach  its  maximum  value 
(100  %).  The  soft-start  value  is  programmed  in  the  “

SfSt

SfSt

SfSt

SfSt

” 

parameter. 

The 

Soft-start

 is important to processes which require a slow rate of 

increase in the applied power, preventing the application of 100% of 
the power at start-up. 

The  control  output  is  primarily  determined  by  the  PID  loop  control; 
the 

Soft-start

 simply limits this output. See also parameters  “

o1ll

o1ll

o1ll

o1ll

” 

and “

o1kl

o1kl

o1kl

o1kl

”. 

5.8

 

SQUARE ROOT EXTRACTION 

Available when input type 19 is selected. The indicator displays the 
square root of the current signal input applied to terminals 10 and 11. 

6

 

INSTALLATION 

Insert  the  unit  into  the  panel  cut-out  and  slide  the  mounting  clamp 
from the rear to a firm grip at the panel. 

6.1

 

ELECTRICAL CONNECTIONS 

0-20mA OR 4-20mA OUTPUT

PULSE OUTPUT

RELAY

OUTPUTS

SERIAL COMMUNICATION (OPTIONAL)

RELAY OR I/O DIGITAL (OPTIONAL)

D1

I/

O

 4

D0

G

N

D

C

 SENSOR INPUT

T/C, RTD

4-20mA, 0-50mV, 0-5V

POWER

mA

 

Figure 2

 - Backpannel terminals 

 

Thermocouple  and  voltage  (Volts  and  mV)  input  connect  as  in 

Figure 3

T/C, 0-50mV, 0-5V

 

Pt100

 

Figure 3

 – thermocouple and Voltage 

wiring 

Figure 4

 - RTD input wiring 

 

RTD (Pt100) 

Figure 4

 shows the Pt100 wiring, for 3 conductors. Terminals 10, 

11 and 12 must have the same wire resistance for proper cable 
length compensation. For 2 wire Pt100, short circuit terminals 11 
and 12. 

 

4-20 mA 

Refer to 

Figure 5

. (The controller provides an internal electronic 

shunt  for  the  input  current.  No  changes  in  the  circuit  are 
necessary). 

4-20mA

 

Figure 5

 – Input current wiring 

 

Digital Input 

Refer to 

Figure 8

 on how to use channels I/O3, I/O4 or I/O5 as 

digital inputs. See also explanations on section 5.2

 

7

 

CONFIGURATION PARAMETERS 

7.1

 

OPERATION CYCLE 

 

PV Indication 

(Red) 

SV Indication 

(Green) 

 

PV AND SV INDICATION: The status display shows 
the  present  value  of  PV  (Process  Variable).  The 
parameter display shows SV (Set Variable). 

The  status  display  shows  “

-  -  -  -

“  whenever  PV 

exceeds the maximum range or there is no signal at 
the input. In case of hardware error the status display 
will show 

Ern

Ern

Ern

Ern

, where n is the error code. 

avto

avto

avto

avto 

 

 

 

CONTROL  MODE: 

YES

  indicates  automatic  control 

mode  (closed  loop,  PID  or  ON/OFF). 

NO

  indicates 

manual control mode (open loop). Bumpless transfer 
from auto 

 to manual mode is available. If in doubt 

program 

YES

 

PV Indication 

(Red) 

MV Indication 

(Green) 

 

MANIPULATED VARIABLE VALUE (MV): The upper 
display shows PV value and the lower display shows 
the  percentage  of  MV  applied  to  the  control  output. 
When  in  manual  control  the  MV  value  can  be 
manually changed. When in auto mode the MV value 
can only be viewed. 

To  distinguish  the  MV  display  from  the  SV  display, 
the MV is shown flashing intermittently. 

Pr n

Pr n

Pr n

Pr n

 

RAMP AND SOAK PROGRAM SELECTION: Selects 
the  ramp  and  soak  program  to  be  executed  (4 
programs  possible).  Refer  to  chapter  7  for  R&S 
description. 

rvn

rvn

rvn

rvn

 

CONTROL  ENABLE: 

YES

  means  that  the  control 

output and alarms are enabled and 

NO

 means they 

are disabled. 

7.2

 

AUTO TUNING CYCLE 1 

atvn

atvn

atvn

atvn

 

AUTO-TUNE:

  YES

  enables  the  auto  tuning  of  the 

PID parameters and 

NO

 disables it. 

Pb1

Pb1

Pb1

Pb1

 

PROPORTIONAL  BAND:  Percentage  of  maximum 
input span. Select zero for ON/OFF control.  

xyst

xyst

xyst

xyst

 

CONTROL HYSTERESIS (in engIneering. units): This 
parameter is only shown for ON/OFF control (Pb=0). 

‘ ir‘ 

‘ ir‘ 

‘ ir‘ 

‘ ir‘ 

INTEGRAL  RATE:  Integral  time  constant  in 
repetitions per minute (Reset).  

dt

dt

dt

dt 

 

 

 

DERIVATIVE  TIME:  Derivative  time  constant,  in 
seconds. 

(t1

(t1

(t1

(t1

 

CYCLE TIME: PWM period in seconds. Can only be 
viewed if proportional band is other than zero.  

act

act

act

act

 

CONTROL ACTION: For Auto Mode only. 

  Reverse Action 

rE

rE

rE

rE

 

usually used for heating. 

  Direct Action 

dir

dir

dir

dir

 

usually used for cooling. 

ovll

ovll

ovll

ovll

 

OUTPUT LOW LIMIT: minimum percentage value for 
MV (Manipulated Variable) when in automatic control 
and PID. Default value: 0.0 % 

ovxl

ovxl

ovxl

ovxl

 

OUTPUT  HIGH  LIMIT:  Maximum  percentage  value 
for  MV  when  in  automatic  control  and  PID.  Default 
value: 100.0 % 

sfst

sfst

sfst

sfst 

 

 

 

 

SOFT  START:  Time  in  seconds  during  which  the 
controller limits the MV value progressively from 0 to 
100 %. It is enabled at power up or when the control 
output is activated. If in doubt set zero. 

Sp.a1

Sp.a1

Sp.a1

Sp.a1

 

 

ALARM 1 PRESET: Tripping point for alarm 1. 

Sp.a2

Sp.a2

Sp.a2

Sp.a2

 

ALARM 2 PRESET: Tripping point for alarm 2. 

Sp.a3

Sp.a3

Sp.a3

Sp.a3

 

ALARM 3 PRESET: Tripping point for alarm 3. 

Sp.a4

Sp.a4

Sp.a4

Sp.a4

 

ALARM 4 PRESET: Tripping point for alarm 4. 

Содержание N1100HC

Страница 1: ...e resistance compensation Analog output 0 20 mA or 4 20 mA 1500 levels 550 Ω max CONTROL OUTPUT Standard Version up to 3 outputs Two 3 A 250 Vac Relays 3 A 30 Vdc Isolated 0 20 mA or 4 20 mA control output or PV or SP retransmission 1500 level resolution 550 Ω max Load Logic pulse for SSR drive 0 or 20 mA Any of the above and options 1 and 2 can be selected as the main control output and the remai...

Страница 2: ...60 C 32 a 3200 ºF S 5 5 5 5 range 0 to 1760 C 32 to 3200 ºF Pt100 6 6 6 6 range 199 9 to 530 0 C 328 0 to 986 0 ºF Pt100 7 7 7 7 range 200 to 530 C 328 to 986 ºF 4 20 mA 8 8 8 8 J linearization Programmable range 110 to 760 C 4 20 mA 9 9 9 9 K linearization Programmable range 150 to 1370 C 4 20 mA 10 10 10 10 T linearization Programmable range 160 to 400 C 4 20 mA 11 11 11 11 N Linearization Faixa...

Страница 3: ...The 3 modes of operation are pulse delayed actuation oscillator The desired function can be achieved programming the parameters A1t1 A1t1 A1t1 A1t1 A1t2 A1t2 A1t2 A1t2 A2t1 A2t1 A2t1 A2t1 and A2t2 A2t2 A2t2 A2t2 see Table 4 The LEDs associated to the alarms will light when the alarm condition is recognized not following the actual state of the output which may be temporarily OFF because of the tem...

Страница 4: ...vto avto CONTROL MODE YES indicates automatic control mode closed loop PID or ON OFF NO indicates manual control mode open loop Bumpless transfer from auto to manual mode is available If in doubt program YES PV Indication Red MV Indication Green MANIPULATED VARIABLE VALUE MV The upper display shows PV value and the lower display shows the percentage of MV applied to the control output When in manu...

Страница 5: ...bla4 bla4 bla4 bla4 ALARM BLOCK 1 TO 4 This function blocks the alarm at power up when the units is first energized YES enables and NO inhibits this blocking function When enabled the alarm will not be active at power up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 xya1 xya1 xya1 ALARM 1 ...

Страница 6: ...optional hardware accessories The parameters menu will show the parameters relative to the optional hardware 0 no optionals or c RS485 only 1 relay 3 I O 3 2 Digital I O 2 inputs outputs 3 Heater break protection option Rsl REMOTE SET POINT LOW CALIBRATION Sets the Remote Set Point low calibration offset Several keystrokes at or might be necessary to increment one digit Rsx REMOTE SET POINT HIGH C...

Страница 7: ...troller resumes at the beginning of the segment it was previously 10 AUTO TUNE During auto tune the process is controlled in ON OFF mode at the programmed SetPoint SV Depending on the process characteristics large oscillations above and below SV may occur and auto tuning may take several minutes to be concluded The recommended procedure is as follows Disable the control output at the rvn rvn rvn r...

Отзывы: