N1100HC CONTROLLER  

HEAT/COOL PROCESS CONTROLLER 

V2.0x A

 

 

1

 

MAIN FEATURES 

 

Universal multi-sensor input without hardware change. 

 

Sensor break protection in any condition. 

 

Control outputs: relay, linear 4-20 mA, 0-20 mA, pulsed output 

 

2° control output for refrigeration, with independent proportional 
band and cycle time. 

 

Overlap adjustment for the control outputs. 

 

Up to 4 alarms. Up to 2 timer relay alarms. 

 

Process  Variable  or  Setpoint  4-20  mA  or  0-20  mA  analog 
retransmission. 

 

Auto/Manual “bumpless” transfer. 

 

Up to 3 digital inputs with 5 programmable functions. 

 

Programmable Soft Start (0 to 9999 seconds). 

 

RS-485 digital communication; RTU MODBUS protocol. 

 

Unique  electronic  8-digit  serial  number  can  be  viewed  at  the 
display. 

 

Firmware version displayed during power up. 

 

Keyboard password protection. 

2

 

SPECIFICATIONS 

 

Dimensions: 48 x 48 x 110 mm (1/16 DIN). 

 

Approximate weight: 150 g 

 

Panel cut-out: 45,5 x 45,5 mm (+0.5 -0.0 mm) 

 

Terminal connection: 18 screws accepting 6.3 mm fork lugs. 

 

Power: 100 to 240 Vac/dc, 50/60 Hz. Max. Consumption: 3 VA 

 

Operating  environment:  0  to  55 

°

C,  Relative  humidity 

(maximum):  80  %  up  to  30  ºC.  For  temperatures  above  30  ºC, 
decrease 3 % per ºC. 

INPUT 

 

Keyboard selection of input type (refer to 

Table 1

 

Internal resolution: 19500 levels 

 

Display resolution: 12000 levels (from -1999 to 9999) 

 

Input sample rate: 5 per second 

 

Accuracy:   Thermocouples J, K and T: 0.25 % of span 

±

1 ºC 

Thermocouple S: 0.25 % of span 

±

3 ºC 

Pt100: 0.2 % of span 
4-20 mA, 0-50 mV, 0-5 Vdc: 0.2 % of span. 

 

Input impedance:  0-50 mV, Pt100 and thermocouples: >10 M

 

            

0-5 V: >1 M

 

            

4-20 mA: 100 

 

 

Pt100  measurement:  DIN  43760  standard  (

α

=0.00385). 

Excitation  current:  170 

µ

A.  3-wire  circuit,  cable  resistance 

compensation.  

 

Analog output: 0-20 mA or 4-20 mA, 1500 levels, 550 

 max. 

 
 

CONTROL OUTPUT (Standard Version (up to 3 outputs): 

 

Two 3 A / 250 Vac Relays (3 A / 30 Vdc); 

 

Isolated  0-20  mA  or  4-20  mA  control  output  or  PV  or  SP 
retransmission, 1500 level resolution, 550 

 max. Load; 

 

Logic pulse for SSR drive: 0 or 20 mA; 

 

Any of the above  and  options 1 and 2   can be selected as the 
main  control  output  and  the  remaining  outputs  can  be  set  as 
alarms; 

 

Programmable PWM cycle from 0.5 sec. and 100 sec.; 

 

Start up 3 seconds after power up; 

With Option Modules (up to 5 outputs) 

 

Option 1: 3 A / 250 Vac (3 A / 30 Vdc) SPDT Relay (3rd relay); 

 

Option 2: two digital I/Os (input: dry contact; output 5 Vdc, 10 mA 
max.). Option 3: heater break detection; 

 

Option 4: RS-485, MODBUS RTU protocol, 1200 to 19200 bps; 

ALARMS

 

 

Up to 4 alarms can be set with 9 different functions for each one. 
Other alarm features are: 

 

2  Timing  alarms,  programmable  from  0  to  6500  sec.,  with 
advanced functions, ideal for servo-positioning 

 

Independent power-up inhibition of the 4 alarms 

 

Programmable hysteresis for the 4 alarms 

3

 

OPERATION 

The front panel is shown in 

Figure 1

Status Display

PV

Parameter Display

SP

messages

Keys

 

Figure 1

 - Front panel parts 

Status display/PV

: shows the value of PV (Process Variable). When 

in programming mode, shows the parameter name. 

Parameter display/SV

: shows the SV (

S

etpoint 

V

ariable) value and 

the value of other parameters of the controller. 

COM Indicator

: Flashes when communication messages are sent by 

the controller. 

TUNE  Indicator

:  Lights  during  the  execution  of  PID  automatic 

tunning. 

MAN Indicator

: Lights when the controller is in manual. 

RUN Indicator

: Lights when the controller is active, with control and 

alarm outputs enabled. 

OUT Indicator

: For relay or pulse control output, reflects the actual 

state of the output. If an analog output is assigned for control, lights 
continuously. 

Содержание N1100HC

Страница 1: ...e resistance compensation Analog output 0 20 mA or 4 20 mA 1500 levels 550 Ω max CONTROL OUTPUT Standard Version up to 3 outputs Two 3 A 250 Vac Relays 3 A 30 Vdc Isolated 0 20 mA or 4 20 mA control output or PV or SP retransmission 1500 level resolution 550 Ω max Load Logic pulse for SSR drive 0 or 20 mA Any of the above and options 1 and 2 can be selected as the main control output and the remai...

Страница 2: ...60 C 32 a 3200 ºF S 5 5 5 5 range 0 to 1760 C 32 to 3200 ºF Pt100 6 6 6 6 range 199 9 to 530 0 C 328 0 to 986 0 ºF Pt100 7 7 7 7 range 200 to 530 C 328 to 986 ºF 4 20 mA 8 8 8 8 J linearization Programmable range 110 to 760 C 4 20 mA 9 9 9 9 K linearization Programmable range 150 to 1370 C 4 20 mA 10 10 10 10 T linearization Programmable range 160 to 400 C 4 20 mA 11 11 11 11 N Linearization Faixa...

Страница 3: ...The 3 modes of operation are pulse delayed actuation oscillator The desired function can be achieved programming the parameters A1t1 A1t1 A1t1 A1t1 A1t2 A1t2 A1t2 A1t2 A2t1 A2t1 A2t1 A2t1 and A2t2 A2t2 A2t2 A2t2 see Table 4 The LEDs associated to the alarms will light when the alarm condition is recognized not following the actual state of the output which may be temporarily OFF because of the tem...

Страница 4: ...vto avto CONTROL MODE YES indicates automatic control mode closed loop PID or ON OFF NO indicates manual control mode open loop Bumpless transfer from auto to manual mode is available If in doubt program YES PV Indication Red MV Indication Green MANIPULATED VARIABLE VALUE MV The upper display shows PV value and the lower display shows the percentage of MV applied to the control output When in manu...

Страница 5: ...bla4 bla4 bla4 bla4 ALARM BLOCK 1 TO 4 This function blocks the alarm at power up when the units is first energized YES enables and NO inhibits this blocking function When enabled the alarm will not be active at power up waiting for PV Process Variable to reach a non alarm situation From this point on the alarm will be free to actuate should a new alarm situation occur xya1 xya1 xya1 xya1 ALARM 1 ...

Страница 6: ...optional hardware accessories The parameters menu will show the parameters relative to the optional hardware 0 no optionals or c RS485 only 1 relay 3 I O 3 2 Digital I O 2 inputs outputs 3 Heater break protection option Rsl REMOTE SET POINT LOW CALIBRATION Sets the Remote Set Point low calibration offset Several keystrokes at or might be necessary to increment one digit Rsx REMOTE SET POINT HIGH C...

Страница 7: ...troller resumes at the beginning of the segment it was previously 10 AUTO TUNE During auto tune the process is controlled in ON OFF mode at the programmed SetPoint SV Depending on the process characteristics large oscillations above and below SV may occur and auto tuning may take several minutes to be concluded The recommended procedure is as follows Disable the control output at the rvn rvn rvn r...