background image

N1050 Controller 

NOVUS AUTOMATION 

6/8 

ACCESS PASSWORD 

The protected levels, when accessed, request the user to provide the 

Access Password

  for granting permission to change the 

configuration of the parameters on these levels. 
The prompt 

PASS

 precedes the parameters on the protected levels. 

If no password is entered, the parameters of the protected levels can 

only be visualized. 
The Access Password is defined by the user in the parameter 

Password Change

  (

PAS.C

), present in the Calibration Level. 

The 

factory default for the password code is 1111.

 

PROTECTION ACCESS PASSWORD 

The protection system built into the controller blocks for 10 minutes 

the access to protected parameters after 5 consecutive frustrated 

attempts of guessing the correct password. 

MASTER PASSWORD 

The Master Password is intended for allowing the user to define a 

new password in the event of it being forgotten. The Master 

Password doesn’t grant access to all parameters, only to the 

Password Change

  parameter (

PASC

). After defining the new 

password, the protected parameters may be accessed (and 

modified) using this new password. 
The master password is made up by the last three digits of the serial 

number of the controller 

added

 to the number 9000.  

As an example, for the equipment with serial number 07154321, the 

master password is 9 3 2 1.  

RAMP AND SOAK PROGRAMS 

Characteristic that allows the elaboration of a behavior profile for the 

process. Each program consists of a set of up to 4 segments, called 

RAMPS AND SOAKS  PROGRAM, defined by SP values and time 

intervals. 
Up to 5 different ramp and soak programs can be created. The figure 

below displays a profile model: 

 

Fig. 03

 - Example of a Ramp and Roak 

Once the program is defined and executed, the controller 

automatically generates the SP according to the program. 
To execute a program with a number of segments smaller than 4 

(four), simply program 0 (zero) for the next segment time to the last 

desired segment. 
The program tolerance function 

P.toL

  defines the maximum 

deviation between PV and SP during program execution. If this 

deviation is exceeded, the time count is interrupted until the deviation 

is within the programmed tolerance (gives SP priority). If zero is set 

in the tolerance, the controller executes the defined program without 

considering any deviations between PV and SP (gives priority to 

time). 

Restore Program after Power Failure (Program restore) 

Function that defines the behavior of the controller when it resumes 

from a power failure in the midst of a program execution of ramps 

and levels. The restore options are: 

Prog

   - Returns at the beginning of the program; 

P.seg

  - Returns the beginning of the segment; 

t.seg

 - Returns to the point of the previous program segment the 

power failure; 

off 

    - Returns with control disabled (

RUN

 = 

No)

The 

t.seg

 option has its performance related to the configuration 

adopted  by  the parameter 

P.toL

. Thus, it also  has the following 

functions: 

1- With 

P.toL

 set to zero, the controller resumes the execution 

of the program immediately after the energy return  (from the 

point and segment where it stopped), regardless of the 

PV

 value 

at that time. 
2- With 

P.toL

 non-zero, the controller waits until 

PV

 enters the 

deviation range defined by the value of 

P.toL

  and then 

resumes the program execution. 

Link

 of programs 

It is possible to create a large, more complex program with up to 20 

segments connecting the 5 programs. Thus, at the end of the 

execution of a program, the controller immediately starts executing 

another program. 
In the elaboration of a program it was defined in the screen

  LP

 

whether or not there will be connection to another program. 
In order for the controller to be able to run a certain program or 

programs continuously, simply connect a program to itself or the last 

program to the first one. 

 

Fig. 04

 – Link programs example 

Event Alarm 

The Event Alarm function allows you to program the triggering of 

alarms in specific segments of a program. 
For this function to operate, the alarms to be triggered must have their 

function set to 

rS

 and are configured in parameters 

PE1

 to 

PE4

Hold Program Function 

This function stops program execution when the 

 key is pressed. 

The 

H.Prg

 parameter of the Calibration Cycle enables the   key 

to perform this function. Pressing the 

  key for 3 seconds will 

immediately program the program. A new press, also of 3 seconds, 

resumes its execution. 

DETERMINATION OF PID PARAMETERS 

During the process of determining automatically the PID parameters, 

the system is controlled in 

ON/OFF

 in the programmed Setpoint. The 

auto-tuning process may take several minutes to be completed, 

depending on the system. The steps for executing the PID auto-

tuning are: 

 

Select the process Setpoint. 

 

Enable auto-tuning at the parameter 

Atun

, selecting 

FAST

 

or

 

FULL

The option 

FAST

 

performs the tuning in the minimum possible time, 

while the option 

FULL

 gives priority to accuracy over the speed.  

The sign TUNE remains lit during the whole tuning phase. The user 

must wait for the tuning to be completed before using the controller.  
During auto tuning period the controller will impose oscillations to the 

process. PV will oscillate around the programmed set point and 

controller output will switch on and off many times. 

Содержание N1050

Страница 1: ...mum All electronic instruments must be powered by a clean mains supply proper for instrumentation It is strongly recommended to apply RC S FILTERS noise suppressor to contactor coils solenoids etc In any application it is essential to consider what can happen when any part of the system fails The controller features by themselves cannot assure total protection FEATURES INPUT TYPE SELECTION Table 0...

Страница 2: ...um value alarm causing the activation of the alarm soon upon the process start up an occurrence that may be undesirable The initial blocking is disabled for the sensor break alarm function ierr SAFE OUTPUT VALUE WITH SENSOR FAILURE Function that ensures that the control output is in a safe condition for the process when an error in the sensor input is identified When a fault is identified in the s...

Страница 3: ...rs are gathered into groups of affinities called parameter cycles The 6 parameter cycles are 1 Operation 2 Tuning 3 Programs 4 Alarms 5 Input 6 Calibration The key gives access to the cycles and their parameters When you hold the key down the controller will cycle from one cycle to another every 2 seconds displaying the first parameter of each cycle PV atun Pr tb fu a1 type pass PV To enter the de...

Страница 4: ... the controller when it resumes from a power failure in the middle of a program execution of ramps and soaks Prog Returns at the beginning of the program P seg Returns the beginning of the segment t seg Returns at the exact point where it stopped off Return with control disabled RUN No Pr n Program number Selects the ramp and soak profile program to be edited viewed The sequence of parameters that...

Страница 5: ...mber that identifies the controller in the serial communication network between 1 and 247 CALIBRATION CYCLE All types of input are calibrated in the factory In case a recalibration is required it shall be carried out by a specialized professional In case this cycle is accidentally accessed do not perform alteration in its parameters Pass Password This parameter is presented before the protected cy...

Страница 6: ...ogram execution of ramps and levels The restore options are Prog Returns at the beginning of the program P seg Returns the beginning of the segment t seg Returns to the point of the previous program segment the power failure off Returns with control disabled RUN No The t seg option has its performance related to the configuration adopted by the parameter P toL Thus it also has the following functi...

Страница 7: ...d by the controller SERIAL COMMUNICATION The controller can be supplied with an asynchronous RS 485 digital communication interface for master slave connection to a host computer master The controller works as a slave only and all commands are started by the computer which sends a request to the slave address The addressed unit sends back the requested reply Broadcast commands addressed to all ind...

Страница 8: ...NPUT J K T S and Pt100 according of Table 01 Internal Resolution 32767 levels 15 bits Resolution of Display 12000 levels from 1999 up to 9999 Rate of input reading up 10 per second Accuracy Thermocouples J K T 0 25 of the span 1 C Thermocouple S 0 25 of the span 3 C Pt100 0 2 of the span Input Impedance Pt100 and thermocouples 10 MΩ Measurement of Pt100 3 wire type α 0 00385 With compensation for ...

Отзывы: