N1050 Controller 

NOVUS AUTOMATION 

4/8 

TUNING CYCLE 

Atun 

Auto Tune

 

 

Enables the auto-tuning function for the PID 

parameters (

pb

,

ir

,

 

dt

). Defines the control 

strategy to be taken:  

off

     

- Turned off (no PID tuning);   

Fast

 

- Automatic tuning; 

FuLL

 

- More accurate automatic tuning. 

PB 

Proporcional  

Band

 

 

Value of the term 

P

  of the control mode PID, in 

percentage of the maximum span of the input type. 

Adjust of between 0 and 500.0 %. 

When set to zero (0), control action is ON/OFF.

  

Hyst 

Hysteresis

 

Control hysteresis.

  Hysteresis value for ON/OFF 

control. Adjustable between 0 and the width of the 

measuring range of the selected input type.  
Displayed only if proportional band = 0. 

ir 

Integral Rate

 

Value of the term 

I

 of the PID algorithm, in repetitions 

per minute (Reset). Adjustable between 0 and 24.00. 

Displayed only if proportional band 

 0.  

Dt 

Derivative Time

 

Value of the term 

D

  of the control mode PID, in 

seconds. Adjustable between 0 and 250.0 seconds.  
Displayed only if proportional band 

 0. 

Ct 

Cycle Time

 

Pulse Width Modulation (PWM) period in seconds. 

Adjustable between 0.5 and 100.0 seconds. 
With the use of contactors, the recommended value 

for the cycle time parameter must be greater than 

10 s. 
Displayed only if proportional band

 0. 

Act

 

Action

 

 

Action Control: 

re

  Control with 

Reverse Action

. Appropriate 

for 

heating

. Turns control output on when 

PV is below SP. 

dir

  Control with 

Direct Action

. Appropriate for 

cooling

. Turns control output on when PV 

is above SP. 

Sf.st 

SoftStart

 

SoftStart Function

. Time interval, in seconds, while 

the controller limits the control output (MV) rising 

rate

(Zero value disables the Soft start function). 

out1 

out2 

out3 

out4 

Output

 

Assign functions to the Output channels OUT1, 

OUT2, OUT3 and OUT4: 

off

     - Not used; 

Ctrl

 

  - Control output; 

A1

         - Alarm 1 output; 

A2

         - Alarm 2 output; 

A1.a2

  

- Alarm 1 + Alarm2 (OR logic); 

Lbd

     - Loop Break Detect Alarm. 

PROGRAM CYCLE 

Pr.tb 

Program time 

base

 

Defines the time base that will be used by all Ramp 

and Soak programs. 
  

SeC

 

- Time basis in seconds; 

  

min

  - Time basis in minutes. 

R.prg 

Program  

restore

 

Function Resume Program. Parameter that defines 

the behavior of the controller when it resumes from 

a power failure in the middle of a program execution 

of ramps and soaks. 

Prog

  - Returns at the beginning of the program; 

P.seg

 - Returns the beginning of the segment; 

t.seg

  -  Returns at the exact point where it 

stopped; 

off 

   - Return with control disabled (

RUN

 = 

No

). 

Pr n 

Program number

 

Selects the ramp and soak profile program to be 

edited/viewed. The sequence of parameters that 

follows refer to this selected program.  
Total of 5 programs possible (1 – 5). 

P.toL 

Program tolerance

 

Maximum admitted deviation of PV with respect to 

SP. If exceeded, the program execution is suspended 

(the internal timer freezes) until the deviation be 

returns back within the defined tolerance. 
The value 0 (zero) disables the function. 

P.sp0 

P.sp4 

Program SP

 

Program SP’s, 0 to  4.  Sets  of 5 SP values that 

define the program profile of ramps and soaks. 

P.t1 

P.t4

 

Program time

 

Program segment time, 1 to 4: Sets the duration 

time, in seconds or minutes, of each of the 4 

segments of the program being edited. 

P.e1 

P.e4 

Program Event

 

Alarms of Event.  Parameters that define which 

alarms are to be activated during the execution of 

a certain program segment: 

oFF

       - Do not trigger an alarm on this segment. 

A1

     

- Activate alarm 1 when program reaches 

this segment. 

A2

     

- Activate alarm 2 when program reaches 

this segment. 

A1.A2

  

- Activate alarms 1 and 2 when program 

reaches this segment. 
The alarms chosen must have its function 

configured as 

rS

Lp 

Link Program

 

Link Program. At the end of running a program, any 

other program can have its execution started 

immediately. 

0

        - Do not connect to any other program; 

1 to 5

 - Program number to be connected. 

ALARMS CYCLE 

Fu.a1

 

Fu.a2

 

Function Alarm

  

Functions of Alarms. Defines the functions for the 

alarms among the options of the 

Table 02

Sp.a1  

Sp.a2 

Setpoint Alarm

 

Alarm SP. Value that defines the point of actuation 

of the alarm outputs. For alarms programmed with 

Differential

  functions, these parameters define 

deviations. 
This parameter is not used for the alarm function 

off

ierr

 

or

 

r5

Sp1.e 

sp2.e 

Setpoint Enable

 

 

Configures display of SPA1 and SPA2 also in the 

Operation Cycle. 

YES

 - SPA1/SPA2 are displayed in the Operation    

Cycle 

No

 

-  SPA1/SPA2 are not displayed in the 

Operation  Cycle 

This parameter is not used for the alarm function 

off

ierr

 

or

 

r5

Содержание N1050

Страница 1: ...mum All electronic instruments must be powered by a clean mains supply proper for instrumentation It is strongly recommended to apply RC S FILTERS noise suppressor to contactor coils solenoids etc In any application it is essential to consider what can happen when any part of the system fails The controller features by themselves cannot assure total protection FEATURES INPUT TYPE SELECTION Table 0...

Страница 2: ...um value alarm causing the activation of the alarm soon upon the process start up an occurrence that may be undesirable The initial blocking is disabled for the sensor break alarm function ierr SAFE OUTPUT VALUE WITH SENSOR FAILURE Function that ensures that the control output is in a safe condition for the process when an error in the sensor input is identified When a fault is identified in the s...

Страница 3: ...rs are gathered into groups of affinities called parameter cycles The 6 parameter cycles are 1 Operation 2 Tuning 3 Programs 4 Alarms 5 Input 6 Calibration The key gives access to the cycles and their parameters When you hold the key down the controller will cycle from one cycle to another every 2 seconds displaying the first parameter of each cycle PV atun Pr tb fu a1 type pass PV To enter the de...

Страница 4: ... the controller when it resumes from a power failure in the middle of a program execution of ramps and soaks Prog Returns at the beginning of the program P seg Returns the beginning of the segment t seg Returns at the exact point where it stopped off Return with control disabled RUN No Pr n Program number Selects the ramp and soak profile program to be edited viewed The sequence of parameters that...

Страница 5: ...mber that identifies the controller in the serial communication network between 1 and 247 CALIBRATION CYCLE All types of input are calibrated in the factory In case a recalibration is required it shall be carried out by a specialized professional In case this cycle is accidentally accessed do not perform alteration in its parameters Pass Password This parameter is presented before the protected cy...

Страница 6: ...ogram execution of ramps and levels The restore options are Prog Returns at the beginning of the program P seg Returns the beginning of the segment t seg Returns to the point of the previous program segment the power failure off Returns with control disabled RUN No The t seg option has its performance related to the configuration adopted by the parameter P toL Thus it also has the following functi...

Страница 7: ...d by the controller SERIAL COMMUNICATION The controller can be supplied with an asynchronous RS 485 digital communication interface for master slave connection to a host computer master The controller works as a slave only and all commands are started by the computer which sends a request to the slave address The addressed unit sends back the requested reply Broadcast commands addressed to all ind...

Страница 8: ...NPUT J K T S and Pt100 according of Table 01 Internal Resolution 32767 levels 15 bits Resolution of Display 12000 levels from 1999 up to 9999 Rate of input reading up 10 per second Accuracy Thermocouples J K T 0 25 of the span 1 C Thermocouple S 0 25 of the span 3 C Pt100 0 2 of the span Input Impedance Pt100 and thermocouples 10 MΩ Measurement of Pt100 3 wire type α 0 00385 With compensation for ...

Отзывы: