background image

NOVUS AUTOMATION 

1/5 

 

 

N1030 Temperature Controller 

INSTRUCTION MANUAL – V2.0x (*) 

(*) The V2.0x version also covers V1.05 version controllers, except 

for the points indicated in the text. 

SAFETY ALERTS 

The symbols below are used on the equipment and throughout this 

document to draw the user’s attention to important operational and 

safety information. 

 

 

CAUTION: 

Read the manual thoroughly 

before installing and operating 

the equipment. 

CAUTION OR DANGER: 

Electrical shock hazard 

All safety related instructions that appear in the manual must be 

observed to ensure personal safety and to prevent damage to either 

the instrument or the system. If the instrument is used in a manner not 

specified by the manufacturer, the protection provided by the 

equipment may be impaired.  

INSTALLATION / CONNECTIONS 

The controller should be fixed to a panel, following the sequence of 

steps below: 

 

Make a cutout in the panel according to the Specifications. 

 

Remove the controller fixing clip. 

 

Insert the controller into the cutout from the front of the panel. 

 

Replace the clip on the controller, pressing until it is well fixed. 

INSTALLATION RECOMMENDATIONS 

 

Input signal conductors should run through the plant separately 

from output and supply conductors. If possible, in grounded 

conduits. 

 

The power supply for electronic instruments must come from a 

network dedicated to the instrumentation. 

 

The use of RC FILTERS (noise suppressors) in contactor coils, 

solenoids, etc. is recommended. 

 

In control applications, it is essential to consider what can 

happen when any part of the system fails. The  controller's 

internal devices do not provide full protection.  

ELECTRICAL CONNECTIONS 

The figure below shows the connections on the back panel of the 

controller: 

 

 

 

Figure 1 –

 

Back panel connections 

FEATURES 

TEMPERATURE SENSOR (INPUT) 

The temperature sensor or input type to be used by the controller is 

defined during equipment configuration. 

Table 01

  shows the 

available options: 

TYPE 

CODE 

MEASUREMENT RANGE 

Thermocouple 

J

 

Tc j 

Range: -110 to 950 ºC (-166 to 1742 ºF) 

Thermocouple 

K

 

Tc k 

Range: -150 to 1370 ºC (-238 to 2498 ºF) 

Thermocouple 

T

 

Tc t 

Range: -160 to 400 ºC (-256 to 752 ºF) 

Pt100 

Pt 

Range: -200 to 850 ºC (-328 to 1562 ºF) 

Table 1 –

 

 

Input types 

The input type should be the first parameter to be configured. Any 

modifications on the input type will automatically change other 

related parameters. When changing the sensor type, you should 

check the overall condition of the configuration.

 

OUTPUTS  

The controller has two outputs. You can configure these outputs to 

operate as 

Control Output (

(trl

)

 or 

Alarm Output (

a1

)

.

 

 

OUT1

-

 

N1030-PR

: Output voltage pulse, 5 Vdc / 25 mA 

-

 

N1030-RR

: Output Relay SPST-NO 

 

OUT2

-

 

Output Relay SPST-NO 

CONTROL OUTPUT (

(TRL

The process control output can operate in 

ON/OFF

 mode or in 

PID

 

mode. 
To operate in 

ON/OFF

 mode, the value set in parameter 

PB

 must be 

0.0. 
With values other than zero in parameter 

PB

, the controller operates 

in 

PID

  mode. The values for the PID parameters can be set 

automatically with the help of Auto Tune (

ATvN

). 

ALARM OUTPUT (

A1

The controller has an alarm that can be directed to any of the outputs. 

When enabled, you can configure the alarm to operate with one of the 

functions described in 

Table 02

off

 

Alarm off.  

lo

 

Alarm of absolute minimum 

value.  It triggers when the 

value of measured PV is 

below

  the value defined for 

alarm Setpoint 

(SPA1)

 

SPA1 

PV 

 

ki

 

Alarm of absolute maximum 

value.  It triggers when the 

value of measured PV is 

above

  the value defined for 

alarm Setpoint (

SPA1

).  

 

SPA1 

PV 

 

 

 

Отзывы: