N1030 Controller  

NOVUS AUTOMATION 

3/5 

dt 

 

Derivative Time. Value of the term 

D

 of the control mode 

PID, in seconds.  
Adjustable between 0 and 250 seconds.  
Displayed only if proportional band 

 0. 

(t

 

 

Cycle time. Pulse Width Modulation (PWM) period in 

seconds.  
Adjustable between 0.5 and 100.0 seconds.  
Displayed only if proportional band 

 0. 

kyst 

 

Control hysteresis.  Hysteresis value in degrees for 

ON/OFF control.  
Adjustable between 0 and the measurement range 

width of the selected input type. 

A(t 

 

Action control: 

re

  Control with 

Reverse Action

. Appropriate for 

heating

. Turns control output on when PV is 

below SP. 

dir

  Control with 

Direct Action

. Appropriate for 

cooling

. Turns control output on when PV is 

above SP. 

0vt1 

 

Operation mode of OUT1 and OUT2 outputs: 

Off

    Not used. 

A1   

Alarm output. 

(trL  

Control output. 

0vt2 

 

INPUT CYCLE 

Type 

 

Input type. Sets the input type used by the controller. 

Refer to 

Table 01

Dp.po 

 

Decimal point. Sets  the presentation mode of the 

decimal point. 

vn

i

 t 

 

Sets the temperature unit to be used: 

(

   Indication in Celsius. 

f

   Indication in Fahrenheit. 

0ffs 

 

Offset. Parameter that allows you to make corrections to 

the indicated PV value. 

Spll 

SP Low/High Limit. Sets  the lower/upper limits for 

adjustments to the control SP value. 
Does not limit the setting of the Alarm SP value. 

Spxl 

Fva1 

 

Alarm  functions.  Sets the alarm functions from the 

options in 

Table 02

Sp.a1 

Alarm SP.  Sets  the alarm actuation point. For 

Differential

 type functions, this parameter defines the 

error (*). 

Bla1 

 

Blocking Alarm. This function blocks the alarms (*). 

YES

   Enables initial blocking.  

 

NO

    Inhibits initial blocking

Xya1 

 

Alarm hysteresis. Sets the difference between the PV 

value at which the alarm is turned on and the value at 

which it is turned off (*). 

Sp1.e 

Allows to display 

Sp.a1 

parameter  in the controller 

Operation Cycle (*) (**). 

YES

  Displays 

Sp.a1 

parameter in the Operation 

Cycle. 

No

   Does not display 

Sp.a1 

parameter  in  the 

Operation Cycle. 

(*) This parameter is not displayed when the alarm function is set to 

off 

or 

ierr

(**) This parameter is not available for version 1.0x of the controller. 

CALIBRATION CYCLE 
All input types are calibrated at the factory. If a recalibration is 

necessary, it must be performed by a specialized professional. If 

this cycle is accessed accidentally, do not promote changes in 

its parameters.  

pass 

Password.  This parameter is shown before the 

protected cycles. See 

Configuration  Protection

 

chapter. 

(al 

Calibration.  Allows you to enable the function to 

calibrate the controller. When the function is not 

enabled, the calibration of the related parameters will 

remain hidden. 

inL( 

Input Low Calibration. Allows you to enter the value 

corresponding to the low scale signal applied to the 

analog input. 

ink( 

Input High Calibration. Allows you to enter the value 

corresponding to the full-scale  signal  applied to the 

analog input. 

rstr 

Restore.  Allows you to reset the input factory 

calibrations, disregarding all changes made. 

Pas.( 

Password Change.  Allows  you to set a new access 

password, always different from zero. 

Prot 

Protection.  Allows you to define  the  protection  cycle. 

See 

Table 03

.  

CONFIGURATION PROTECTION 

The controller allows you to protect its configuration, preventing 

undue changes. In the Calibration cycle, the 

Protection

  parameter 

(

PROt

) determines the protection cycle  to be adopted, limiting 

access to the cycles, as shown in the table below: 

PROTECTION 

CYCLE 

PROTECTION CYCLE  

Only Calibration cycle is protected. 

Calibration and Input cycles are protected.  

Calibration, Input,  and Tuning cycles  are 

protected. 

All cycles (including SP) are protected. 

Table 3 –

 

 

Protection cycles  

ACCESS PASSWORD 

To access the Calibration cycle, a password is required. If entered 

correctly, it allows changing the configuration of the parameters of 

these cycles, including the 

Protection

 parameter (

PROt

). 

You can set the password in the 

Password Change

  parameter 

(

PAS.(

), which is also present in the Calibration cycle. 

The 

controllers leave the factory with the password set to 1111

PROTECTION ACCESS PASSWORD 

The controller has a security system that helps prevent the entry of 

numerous passwords to guess the correct password. Once 5 

consecutive invalid passwords are identified, the controller stops 

accepting passwords for 10 minutes.  

MASTER PASSWORD 

If you forget the password, you can use the Master Password 

feature. When entered, this password gives access and allows 

changing the 

Password Change

  parameter (

PAS(

). This makes it 

possible to set a new password for the controller. 
The master password is formed by the last three digits of the 

controller serial number 

plus

 the number 9000. 

Example:  For a device with serial number 07154321, the master 

password is 9321. 
You can get the serial number of the controller by pressing 

 

 key 

for 5 seconds. 