NOVENCO ARO 290 Скачать руководство пользователя страница 7

Novenco

®

  jet fan types AUO/ARO - ARP/AUZ - AUT/ART - AZT

7

7. Troubleshooting

Locate and identify problems with and 
around the fans in as much details as 
possible, before f.x. calling for service or 
ordering parts. Things to look for 
include the following.

Lacking performance

• Inlet or outlet blocked
• Auxiliary fans stopped
• Motor defective
• Motor disconnected
• Electric connection defective
• Wrong direction of rotation

Noise and vibrations

• Motor bearings defective
• Rotor in imbalance
• Rotor worn or damaged
• Loose components
• Rotor blades with different angles 

(loose blades).

• Fan operates in the stalling area, 

which may result in breakdown. 
Correct errors – see “Lacking 
performance”
.

8. Inspection and test

Extent of inspection

• Measure power consumption at full 

and half speeds

• Vibration measuring on fan casing 

(outside motor)

• Check of fan suspension
• Visual inspection of rotor, casing, 

silencers and electric connection

• Cleaning

- Internal with compressed air or 

vacuum cleaning

- External with a wrung cloth. No 

water must get in the electric 
systems or the acoustic 
insulation.

Keep a journal of all measured values 
and observations for each fan.

9. Sound

The fan sound emission depends on 
installation and operating conditions, 
hence no general data can be given.
Refer to the product catalogue and the 
technical fan specifications.

10. Safety

The jet fans must be installed according 
to Novenco’s and the current safety 
regulations. At a minimum these include 
EN 13850.
It is recommended to review and revise 
safety procedures regularly.

Safety check

• Test if safety procedures and the 

installation work correctly.

• Check if safety regulations have 

been changed and if the installation 
needs revising.

• Consider taking additional 

measures to improve the safety of 
the installation. For example, by 
mounting wire guards on inlet and 
outlet.

11. Reference documentation

Please refer to the below documents on 
the Novenco website for further 
information about the fans.

• Catalogue

Car park jet fans, standard and hot 
smoke

• Data sheets, drawings, certificates 

and declarations of performance 
for
AUZ-ARP 340
AUT-ART 400
AUO-ARO 290-380-500
AZT 280-355-450

• Technical specifications

12. Disposal

Dispose of fans suitable for scrapping in 
environmentally safe ways and in 
accordance to current regulations.
The fans and especially the electric 
motors contain a wide range of 
materials, which can all be recycled. 
Make sure worn-out motors and fan 
parts are disassembled and recycled for 
the benefit of the environment.

13. Patents and trademarks

Novenco

®

 and 

 are 

registered trademarks of Novenco 
Marine & Offshore A/S.
ZerAx

®

 is a registered trademark of 

Novenco Building & Industry A/S.
AirBox™, NoVa™ and NovAx™ are 
trademarks of Novenco Building & 
Industry A/S.
The Novenco ZerAx processes of 
manufacture, technologies and designs 

are patented by Novenco A/S or 
Novenco Building & Industry A/S.
Pending patents include India no. 821/
CHENP/2014 and 825/CHENP/2014; 
PCT no. EP2012/064908 and EP2012/
064928.
Granted patents include Brazil no. BR-
11-2012-008543-3; BR-11-2012-008545-0, 
BR-11-2012-008607-3, BR-11-2014-

002282-8 and BR-11-2014-002426-0; 

Canada no. 2.777.140, 2.777.141, 
2.777.144, 2.832.131 and 2.843.132; China 
no. ZL2010800458842, 
ZL2010800460965, ZL2010800464275 
and ZL2012800387210; EU no. 2488759, 

2488760, 2488761, 2739860 and 2739861; 
India no. 312464, 360298 and 367515; 
South Korea no. 10-1907239, 10-1933724, 
10-1980600, 10-2011515 and 10-2127529; 

US no. 8.967.983, 9.200.641, 9.273.696 B2, 
9.683.577 and 9.926.943 B2.
Granted designs include Brazil no. BR-

30-2012-003932-0; Canada no. 146333; 
China no. 1514732, 1517779, 1515003, 
1555664 and 2312963; EU no. 001622945-
0001 to 001622945-0009 and 001985391 - 
0001; India no. 246293; South Korea no. 

30-0735804; UK no. 001622945-0001 to 
001622945-0009 and 001985391 - 0001; US 
no. D665895S, D683840S, D692119S, 
D704323S, D712023S, D743018S, 
D755363S, D756500S, D821560S and 

D823452S.
The Novenco NovAx Basic jet fans 
manufacturing processes, technologies 
and designs are patented by Novenco 
A/S or Novenco Building & Industry A/
S.
Granted designs include EU no. 
001069884-0003, 001069884-0008, 
001069884-0010, 001069884-0013, 
001069884-0017, 001069884-0019, 

001069884-0022, 001069884-0026 and 
001069884-0028; United Arab Emirates 
no. D223/2009.
Other trademarks in this document are 
the property of their respective owners.
This document is provided ’as is’. 
Novenco Building & Industry A/S 
reserves the right to changes without 
further notice due to continuous product 
development.
Copyright © 1985 - 2022,
Novenco Building & Industry A/S.
All rights are reserved.

14. Quality management

Novenco is ISO 9001 and 14001 certified. 
All fans are inspected and tested, before 
leaving the production.

Содержание ARO 290

Страница 1: ...Pure competence in air ENGLISH 919044 0 NOVENCO JET FAN TYPES AUO ARO ARP AUZ AUT ART AZT INSTALLATION AND MAINTENANCE ...

Страница 2: ...e g AUO 380 160 4 Serial no Fan speed Year of manufacture Weight CE marking For smoke fans also Air performance Max temperature Working period Category or class Motor nameplate information Manufacturer information Power consumption and efficiency Voltages RPMs Weight Terminal connections Documentation and instructions from the motor manufacturer are included with the fans Refer to these when perfo...

Страница 3: ...e operational conditions and the natural frequency of the foundation and supports Follow the below guidelines to avoid resonance Soft suspension Fan is fixated through springs or dampers The natural frequency Hz of thesystemshouldbeat least20 below fan speed Soft suspensions are available from Novenco Stiffsuspension Fanisfastened to a duct or a hard surface The natural frequency of this system sh...

Страница 4: ...screws from the transport brackets in the casing 4 3 Electric connection The installation and connection to the supply network must be done by authorised personnel and according to current local legislation e g the EU standard for electromagnetic compatibility EMC Electric connection 1 Check if current legislation prescribes installation of f x an emergency stop and include this in the installatio...

Страница 5: ...he fans 3 Disconnect the power supply 4 Lock the power switches Alternatively lock access to the power switches Service of the fans can now begin 6 2 Intervals Safe and proper function of the fans requiremaintenanceat regularintervals Faulty maintenance of fans covered by warranty voids the warranty Maintenanceofthefansmustincludethe following Maintenance checklist Inspection of each complete unit...

Страница 6: ...aft Press the rotor hub to contact against the motor shaft collar Leave out use of hammers or similar as the motor bearings are sensitive to shocks 4 Use a feeler gauge to check that the blade tip clearance is the same throughout the circumference Adjust the motor position in the suspension arrangement with reference to table 7 5 Connect the cable between motor and terminal box Use same routing as...

Страница 7: ...lly safe ways and in accordance to current regulations The fans and especially the electric motors contain a wide range of materials which can all be recycled Make sure worn out motors and fan parts are disassembled and recycled for the benefit of the environment 13 Patents and trademarks Novenco and are registered trademarks of Novenco Marine Offshore A S ZerAx is a registered trademark of Novenc...

Страница 8: ...o the below directives ofthe European Council and that they comply with the below standards and regulations EU directives Ecodesign 2009 125 EU and energy labelling regulation 2017 1369 EU EMC 2014 30 EU LVD 2014 35 EU Machinery 2006 42 EU UK regulations Ecodesign for ErP 2010 and Energy Information 2011 Electrical Equipment Safety 2016 EMC 2016 Supply of Machinery Safety 2008 Applied standards AN...

Страница 9: ...otor 9 Deflector AZT Outlet cone 4 Motor 10 Suspension brackets AZT Base plate 5 Motor suspension and guide vanes 11 Wire guard 6 Terminal box 12 Centre fairing Figure 6 Main components AUO ARO ARP AUZ AUT ART AZT 10 7 6 9 4 11 1 5 3 10 8 7 5 4 1 2 3 9 1 12 9 6 10 8 6 4 1 2 3 11 7 9 6 5 11 10 1 5 2 3 4 6 7 8 9 10 1 9 5 2 12 3 4 6 7 8 1 9 10 10 11 6 5 4 11 7 3 ...

Страница 10: ...4xØR D D E 6xØR H H H Ceiling mount 2xØR Fan mount 4xØR Ceiling plate AUO ARO ARP AUZ AUT ART AZT H mm D mm E mm ØR mm AUO ARO 290 320 506 560 Ø14 M12 AUO ARO 380 420 506 720 Ø14 M12 AUO 500 540 600 830 Ø14 M12 AUZ ARP 340 422 283 520 Ø14 M12 AUT ART 340 423 779 470 Ø14 M12 AZT 280 334 417 233 Ø11 M10 AZT 355 435 500 305 Ø11 M10 AZT 450 552 610 364 Ø11 M10 ...

Страница 11: ... 14 Bolts 3 Silencers 7 Rotor 11 Guide vanes 15 Washers 4 Screws 8 Set screws 12 Rivets 16 Stiffeners Figure 8 Main components Figure 9 External terminal box and connection diagram 9 10 8 7 4 5 11 12 10 9 8 7 6 5 4 10 7 6 13 4 5 15 11 14 10 16 7 6 13 4 5 15 11 14 2 3 3 3 3 2 2 1 1 1 1 Type ARO and ARP Type AUZ Type AZT Type AUO AUO ARO ARP AUZ AUT ART AZT Motor dismoun ng AUT and ART Unit dismoun ...

Страница 12: ...ct wire guards Clean the fans Clear fans and airflow ways Replace broken parts Brief on off cycle to verify rotational direction Service the fans Brief on off cycle to verify rotational direction Start up Power on fans Troubleshooting Check for abnormal sounds and vibrations Lacking performance Measure vibrations section Vibrations on page 5 Inlet or outlet blocked After 30 min operation check for...

Страница 13: ...Pure competence in air ttt EKs E Kͳ h E KD ...

Отзывы: