NOVENCO ARO 290 Скачать руководство пользователя страница 4

4

Novenco

®

  jet fan types AUO/ARO - ARP/AUZ - AUT/ART - AZT

It is essential for the 
performances and sound levels 
that the airflows are unimpeded 

and free from eddies.

2.

Drill holes in the ceiling in 
accordance to the installation 
footprint. See figure 7 on page 10.
AZT:

 Use the ceiling plate as a 

drilling rig.

If unapproved expansion bolts 
for high temperature are to be 
used, these must be made from 

steel, must be size M8 or bigger and 
must be mounted twice as deep as 
recommended, at least 60 mm deep. 
The static load must not exceed a pull of 
more than 500 N.

3. Optional:

 Install lowering brackets 

in the ceiling, if applicable.

4.

Place the fan on a platform that can 
be raised, for example a scissor lift.

5. AUO/ARO-ARP/AUZ-AUT/ART: 

Fasten the fan in the suspension 
points to the ceiling or, if applicable, 
to lowering brackets.
Notice:

It is recommended to install 
vibration dampers. These 
are optional and not 
included as standard.

6. AZT:

 Prepare the ceiling plate for 

installation by insertion of four 
threaded bolts with washers from the 
top in the holes for fan mount.
If applicable, install lowering 
brackets in the ceiling.
Mount the ceiling plate in the two 
centre holes of the plate. See figure 7 
on page 10.

Expansion bolts certified for fire 
conditions must be used and 
loaded according to the 

approval.

Lift the fan in place and fasten it in 

the suspension bolts with nuts.

7.

Check that the rotor rotates freely in 
the fan casing.

8. AUO/ARO-ARP/AUZ:

 Remove the 

transport brackets on the underside 
of the fan casing. Reinsert the screws 
from the brackets in the casing.
AZT:

 Reinsert the screws from the 

transport brackets in the casing.

4.3 Electric connection

The installation and connection 
to the supply network must be 
done by authorised personnel 

and according to current local 
legislation, e.g. the EU standard for 
electromagnetic compatibility (EMC).

Electric connection

1.

Check if current legislation 
prescribes installation of f.x. an 
emergency stop and include this in 
the installation.

2.

Remove the lid on the external 
terminal box.

3.

Connect the motor through a thermal 
relay based on the motor nominal 
current. Refer to the following 
information.
Connection references

 

• Motor name plate
• Order specification
• Appendix “D. Wiring” on 

page 11

Make the connections directly in the 

external terminal box.

4.

Remount the lid on the terminal box.

4.4 Approval for operation

The installation must be approved with 
regard to operation and interaction. The 
person responsible for the operation of 
the system must initiate this approval 
test. The test must be confirmed.
The person responsible for the operation 
of the system must keep the approval 
test documents. For jet fans approved for 
smoke control, the documents must be 

Figure 1.

Minimum distance requirements 

for unidirectional jet fans

Figure 2.

Minimum distance requirements 

for reversible jet fans

500

500*

500

2000

500*

* Minimum 500 mm
   free for air intake

Detail
figure 4

Detail
figure 4

Use lowering brackets
in areas with high beams

Boom jet fan
= beam height

2000

2000

2000

2000

Use lowering brackets
in areas with high beams

Boom jet fan
= beam height

Figure 3.

Principle of installation

Figure 4.

AUT: Example of installation with 

vibration dampers

item 1 Jet fan

item 2 Expansion bolt

item 3 Ceiling

1

2

3

Top

Side

Vibration
dampers
Disc
Concrete
screw 10x130

Steel pipe

Figure 5.

AZT: Secure fan to ceiling plate

Содержание ARO 290

Страница 1: ...Pure competence in air ENGLISH 919044 0 NOVENCO JET FAN TYPES AUO ARO ARP AUZ AUT ART AZT INSTALLATION AND MAINTENANCE ...

Страница 2: ...e g AUO 380 160 4 Serial no Fan speed Year of manufacture Weight CE marking For smoke fans also Air performance Max temperature Working period Category or class Motor nameplate information Manufacturer information Power consumption and efficiency Voltages RPMs Weight Terminal connections Documentation and instructions from the motor manufacturer are included with the fans Refer to these when perfo...

Страница 3: ...e operational conditions and the natural frequency of the foundation and supports Follow the below guidelines to avoid resonance Soft suspension Fan is fixated through springs or dampers The natural frequency Hz of thesystemshouldbeat least20 below fan speed Soft suspensions are available from Novenco Stiffsuspension Fanisfastened to a duct or a hard surface The natural frequency of this system sh...

Страница 4: ...screws from the transport brackets in the casing 4 3 Electric connection The installation and connection to the supply network must be done by authorised personnel and according to current local legislation e g the EU standard for electromagnetic compatibility EMC Electric connection 1 Check if current legislation prescribes installation of f x an emergency stop and include this in the installatio...

Страница 5: ...he fans 3 Disconnect the power supply 4 Lock the power switches Alternatively lock access to the power switches Service of the fans can now begin 6 2 Intervals Safe and proper function of the fans requiremaintenanceat regularintervals Faulty maintenance of fans covered by warranty voids the warranty Maintenanceofthefansmustincludethe following Maintenance checklist Inspection of each complete unit...

Страница 6: ...aft Press the rotor hub to contact against the motor shaft collar Leave out use of hammers or similar as the motor bearings are sensitive to shocks 4 Use a feeler gauge to check that the blade tip clearance is the same throughout the circumference Adjust the motor position in the suspension arrangement with reference to table 7 5 Connect the cable between motor and terminal box Use same routing as...

Страница 7: ...lly safe ways and in accordance to current regulations The fans and especially the electric motors contain a wide range of materials which can all be recycled Make sure worn out motors and fan parts are disassembled and recycled for the benefit of the environment 13 Patents and trademarks Novenco and are registered trademarks of Novenco Marine Offshore A S ZerAx is a registered trademark of Novenc...

Страница 8: ...o the below directives ofthe European Council and that they comply with the below standards and regulations EU directives Ecodesign 2009 125 EU and energy labelling regulation 2017 1369 EU EMC 2014 30 EU LVD 2014 35 EU Machinery 2006 42 EU UK regulations Ecodesign for ErP 2010 and Energy Information 2011 Electrical Equipment Safety 2016 EMC 2016 Supply of Machinery Safety 2008 Applied standards AN...

Страница 9: ...otor 9 Deflector AZT Outlet cone 4 Motor 10 Suspension brackets AZT Base plate 5 Motor suspension and guide vanes 11 Wire guard 6 Terminal box 12 Centre fairing Figure 6 Main components AUO ARO ARP AUZ AUT ART AZT 10 7 6 9 4 11 1 5 3 10 8 7 5 4 1 2 3 9 1 12 9 6 10 8 6 4 1 2 3 11 7 9 6 5 11 10 1 5 2 3 4 6 7 8 9 10 1 9 5 2 12 3 4 6 7 8 1 9 10 10 11 6 5 4 11 7 3 ...

Страница 10: ...4xØR D D E 6xØR H H H Ceiling mount 2xØR Fan mount 4xØR Ceiling plate AUO ARO ARP AUZ AUT ART AZT H mm D mm E mm ØR mm AUO ARO 290 320 506 560 Ø14 M12 AUO ARO 380 420 506 720 Ø14 M12 AUO 500 540 600 830 Ø14 M12 AUZ ARP 340 422 283 520 Ø14 M12 AUT ART 340 423 779 470 Ø14 M12 AZT 280 334 417 233 Ø11 M10 AZT 355 435 500 305 Ø11 M10 AZT 450 552 610 364 Ø11 M10 ...

Страница 11: ... 14 Bolts 3 Silencers 7 Rotor 11 Guide vanes 15 Washers 4 Screws 8 Set screws 12 Rivets 16 Stiffeners Figure 8 Main components Figure 9 External terminal box and connection diagram 9 10 8 7 4 5 11 12 10 9 8 7 6 5 4 10 7 6 13 4 5 15 11 14 10 16 7 6 13 4 5 15 11 14 2 3 3 3 3 2 2 1 1 1 1 Type ARO and ARP Type AUZ Type AZT Type AUO AUO ARO ARP AUZ AUT ART AZT Motor dismoun ng AUT and ART Unit dismoun ...

Страница 12: ...ct wire guards Clean the fans Clear fans and airflow ways Replace broken parts Brief on off cycle to verify rotational direction Service the fans Brief on off cycle to verify rotational direction Start up Power on fans Troubleshooting Check for abnormal sounds and vibrations Lacking performance Measure vibrations section Vibrations on page 5 Inlet or outlet blocked After 30 min operation check for...

Страница 13: ...Pure competence in air ttt EKs E Kͳ h E KD ...

Отзывы: