- 18 -
ОМ-310
NOVATEK-ELECTRO
Figure 2.2
-
ОМ
-310 connection to PC schematic
2.4.4.3. Communication protocol
The exchange between PC and
ОМ
-310 is effected via data packages. Data packet format is given in Table 2.1.
Table 2.1
START
silence interval – over 2msec at 9600 baud transfer rate, or over 4 msec at 19200 baud
transfer rate
ADR
ОМ
-310 communication address (8 bit)
CMD
Command code 8 bit
DATA 0
Data contents:
N*8 data bit (n<=24)
….
DATA (n-1)
CRC CHK low
CRC checksum
16 bit
CRC CHK high
END
silence interval – over 2msec at 9600 baud transfer rate, or over 4 msec at 19200 baud
transfer rate
2.4.4.4 CMD (command code) and DATA (data symbols)
Data symbols format depends on command codes.
Command code –0x03, n-words read.
For example, read 2 continuous words swapped from 210
2H in ОМ
-310 initial address with 01H communication
address (Table 2.2)
Table 2.2
Command message
Response message
ADR
0x01
ADR
0x01
CMD
0x03
CMD
0x03
Start data address
0x21
0x02
Data amount, bytes
0x04
Data amount in words
0x00
0x02
Data contents by address
0x17
0x70
CRC CHK low
0x6F
Data contents by address
0x00
0x00
CRC CHK high
0xF7
CRC CHK low
0xFE
CRC CHK high
0x5C
Command code 0x06, record – one word
Using this command is not recommended as recording incorrest data may lead to
ОМ
-310 failure.
Data recording is possible only to the programmable parameters addresses (Table 1.5), except for parameters
listed in Table 2.3.