background image

- 18 - 

ОМ-310

 

                                                                                                                                                      

NOVATEK-ELECTRO

 

 

 

Figure  2.2

 -  

ОМ

-310 connection to PC schematic 

 

2.4.4.3. Communication protocol 
The exchange between PC and 

ОМ

-310 is effected via data packages. Data packet format is given in Table 2.1. 

 

Table 2.1 

 

START 

 silence interval – over 2msec at 9600 baud transfer rate, or over 4 msec at 19200 baud 
transfer rate  

ADR 

 

ОМ

-310 communication address (8 bit) 

CMD 

 Command code 8 bit 

DATA 0 

 Data contents: 
N*8 data bit (n<=24) 

…. 
DATA (n-1) 
CRC CHK low 

 CRC checksum 
 16 bit 

CRC CHK high 
END 

silence interval –  over 2msec at 9600 baud transfer rate, or over 4 msec at 19200 baud 
transfer rate 

  

2.4.4.4 CMD (command code) and DATA (data symbols)  

Data symbols format depends on command codes.  

Command code –0x03, n-words read. 

For example, read 2 continuous words swapped from 210

2H in ОМ

-310  initial address with 01H communication 

address (Table 2.2) 

 

Table 2.2 

 

Command message 

Response message 

ADR 

 0x01 

ADR 

 0x01 

CMD 

 0x03 

CMD 

 0x03 

Start data address 

 0x21 
 0x02 

Data amount, bytes 

 0x04 

Data amount in words 

 0x00 
 0x02 

Data contents by address 

0x17 
0x70 

CRC CHK low 

 0x6F 

Data contents by address 

0x00 
0x00 

CRC CHK high 

 0xF7 

CRC CHK low 

0xFE 

 

 

CRC CHK high 

0x5C 

 

Command code 0x06, record – one word 
Using this command is not recommended as recording incorrest data may lead to 

ОМ

-310 failure. 

Data recording is possible only to the programmable parameters addresses (Table 1.5), except for parameters 

listed in Table 2.3.  

 

 

Содержание OM-310

Страница 1: ...NOVATEK ELECTRO LTD Research and Manufacture Company POWER LIMITER OM 310 USERS MANUAL www novatek electro com...

Страница 2: ...ontrol Modes 13 2 2 2 Disabled keypad mode 14 2 2 3 MMSP mode 14 2 2 4 User level 14 2 2 5 Service Engineer Level 14 2 2 6 Restoring factory settings 15 2 3 OM 310 PRE OPERATION PROCEDURE 15 2 4 INTEN...

Страница 3: ...OM 310 is possible via OM 310 Control Panel Software that can be downloaded from the Novatek Electro website http www novatek electro com production_ htm OM 310 Control Panel software is dedicated fo...

Страница 4: ...ccuracy for wattage of rated wattage at most 5 Tripping threshold accuracy for current of rated current at most 2 Tripping threshold accuracy for voltage V at most 3 Phase imbalance detection accuracy...

Страница 5: ...V 100 300 3 V 111 112 113 Power voltage RMS values V 100 450 5 114 115 116 Positive sequence voltage V 100 300 3 B 117 Negative sequence voltage V 3 300 3 B 118 Zero sequence voltage vector sum of thr...

Страница 6: ...aggregate threshold calculation total power for all phases equals Pnn 154 Main threshold 50 150 110 155 Additional threshold 30 100 90 156 Time before load relay de energizing sec main threshold 0 300...

Страница 7: ...3 2 0 1 0 171 Protection function permission 0 2 0 0 protection function prohibited 1 protection function permitted after tripping automatic reset prohibited 2 protection function permitted after trip...

Страница 8: ...from Table 1 5 187 Min number of setting parameters mode ena ble 0 1 1 0 mode disabled 1 mode enabled The mode change is enabled in the service engineer mode only 188 Indication on OM 310 display pan...

Страница 9: ...red LED SETUP glows when the relay is in parameter setup mode 2 green LED LOAD glows when the load relay is closed 3 green LED RELAY glows when the characterizing relay is closed 4 green LED MMSP mod...

Страница 10: ...g it for connection of additional loading After 310 energizing after AR time parameter the load relay will close If during operation the active power consumed by the load crosses the main threshold fo...

Страница 11: ...on which event a or b comes first If during operation the active power consumed by the load crosses the additional threshold line 1 figure 1 3 for a time period that is longer than assigned by parame...

Страница 12: ...It is engaged when at least one of the phase current values reach the tripping threshold The protection has a time delay setting The delay can be independent constant or dependent SIT reverse depende...

Страница 13: ...time assigned by parameter 1 2 6 6 Protection based on phase sequence order trips in case of phase sequence order fault or phase coin cidence it opens the load relay and locks its further operation 1...

Страница 14: ...access mode When switching off the MMSP mode setting parameter 0 LED MMSP goes off In the user mode all parameters list is displayed but to change a parameter parform the following with DOWN and UP b...

Страница 15: ...th 5A rated output current shall be connected in accor dance with Fig 2 1 For correct OM 310 operation the current transformers polarity must be observed 2 3 2 Run all three power phase cables through...

Страница 16: ...h use of external CTs and at 2 characterizing relay operation in the mode of controlling additional load 2 4 INTENDED USE Note In the 310 operation description it is assumed that the protections descr...

Страница 17: ...0 or within 15 sec and then phase A current 1 indication is displayed again 2 4 3 Characterizing relay operation Functions performed by the characterizing relay are defined by parameter When 0 the re...

Страница 18: ...command code and DATA data symbols Data symbols format depends on command codes Command code 0x03 n words read For example read 2 continuous words swapped from 2102H in 310 initial address with 01H co...

Страница 19: ...ode 08h diagnostics 08h function provides a number of tests for checking communication system between PC and OM 310 and for OM 310 integrity control The function uses the sub function field to specify...

Страница 20: ...crc_chk unsigned char data unsigned char length int j unsigned int reg_crc 0xFFFF while length reg_crc data for j 0 j 8 j if reg_crc 0 01 reg_crc reg_crc 1 0xA001 LSB b0 1 else reg_crc reg_crc 1 retur...

Страница 21: ...f the data transferred unsupported function code etc 310 receives the request frame and forms a response with the error indicator and code A high order function field bit inserted in the unit serves a...

Страница 22: ...on in the remote control mode is defined by the parameter When 0 the load energize cutoff by means of remote breaker is prohibited When 1 310 with the open terminal of the S1 remote breaker fig 2 1 fu...

Страница 23: ...olling performed by pressing UP and DOWN buttons To exit log view mode press RECORD RESET SELECT button or the log will close automatically after 30 sec since last button was pressed Fault information...

Страница 24: ...e humidity when there are no fumes in the air that have a damaging effect on package and the equipment material The customer shall provide for the 310 equipment protection against mechanical dam age w...

Страница 25: ...25 NOVATEK ELECTRO 310 APPENDIX 1 Dependent time delay current based protection types...

Страница 26: ...26 310 NOVATEK ELECTRO...

Страница 27: ...27 NOVATEK ELECTRO 310...

Страница 28: ...28 310 NOVATEK ELECTRO...

Страница 29: ...220 240 LYQ20DC12 6031007G 6131406HQ 6 1393099 3 6 1393099 8 6 1393122 4 6 1393123 2 6 1393767 1 6 1393843 7 6 1415012 1 6 1419102 2 6 1423698 4 6 1608051 6 6 1608067 0 6 1616170 6 6 1616248 2 6 16162...

Отзывы: