- 22 - 

ОМ-310

 

                                                                                                                                                      

NOVATEK-ELECTRO

 

When 



=1, the ОМ

-310 device after power-on works similarly as when the remote control is off (normal oper-

ation), but writing to the R_COMMAND command register is permitted. 

 When 



=2, ОМ

-310 will energize load only after the corresponding command via RS-232/RS-485 has been 

received. 

The R_COMMAND value is regarded by the 

ОМ

-310  operation algorithm when 



=1, 



=2. If 



=0 and the 

user sets 



=1 or 



=2, then 0 will be recorded to R_COMMAND. 

The list of possible command register settings is shown in Table 2.7 
 

 Table 2.7 

 

R_COMMAND command 
register Address=220 

Actions performed 

De-energize load. If the load is de-energized, then before a power-on command 
from the Remote Control has been received, the load will not energize. If the load is 
energized, it will be de-energized. 

Normal device operation. 
If the load was de-energized by the remote control command or by pressing  DOWN, 
UP buttons (while 



=3), or in case of a failure after which automatic restart is per-

mitted, then the load will be energized within specified automatic restart time from 
the moment of de-energizing while “1” is recorded in the R_COMMAND register.  

Early load energizing. Value “2” record will lead to load power-on until expiration of 
the automatic reset time period. After load power-on, R_COMMAND =1. 

 

 

If 



=1, then after energizing “1” value (device normal operation) will be recorded in the command register. 

If 



=2, then after energizing “0” value (load de-energized until the command to energize is received) will be 

recorded in the command register. 

In case of an emergency load shutdown by simultaneous pressing DOWN, UP buttons, (while 



=2, 



=3), 

the command register will be reset to 0. 

 

2.4.6 Load energize/de-energize via remote breaker 
ОМ

-310 operation in the remote control mode is defined by the 



 parameter. 

When 



=0, the load energize/cutoff by means of remote breaker is prohibited. 

When 



=1, 

ОМ

-310 with the open terminal of the  S1  remote breaker (fig.2.1) functions the same way as dur-

ing normal operation mode. When the remote breaker terminal is closed the load relay opens (when 



=2 besides 

the load relay, the characterizing relay will also open).  

 When 



=2, 

ОМ

-310 with the closed terminal of the  S1  remote breaker (fig.2.1) functions the same way as 

during normal device operation. When the remote breaker terminal is open the load relay opens (when 



=2 be-

sides the load relay, the characterizing relay will also open). 

 When 



 =3 and 



= 4 

ОМ

-310 functions the same way as 



 =1 and 



= 2 accordingly, but AR after the 

remote motor de-energizing is forbidden. 

 

2.4.7 Fault conditions system 

In case of fault condition occurrence, the 

ОМ

-310 performs following actions: 

-mnemonic indicator displays error code according to Table 2.8; 
-value indicator displays value of the faulty parameter (if given fault does not have numeric value, the indicator 

displays “

----

“); 

-red LED FAULT lights (glows continuously if AR will not initiate, and flickers if AR is expected); 
- load relay opens; 

-

  characterizing relay closes (when 



=0). 

If 

ОМ

-310  defines several types of faults simultaneously, the error codes and parameter values are displayed 

consecutively, one after one. 

If AR is permitted, the fault codes and time left till AR are displayed. 
 

2.4.8  Faulty conditions log 

When load relay in case of fault opens, the 

ОМ

-310  device stores the fault code, the parameter value, and time 

of occurrence. 

Note. Time of fault is defined by OM internal clock. As 

ОМ

-310 has no integral power source, the time when the 

device was de-energized, is not accounted.      

Number of synchronously stored fault codes is five. When next following faults occur, the information of this fault 

is recorded over the latest fault. 

To view log press RES/MEM/SEL button. 
 
 

Содержание OM-310

Страница 1: ...NOVATEK ELECTRO LTD Research and Manufacture Company POWER LIMITER OM 310 USERS MANUAL www novatek electro com...

Страница 2: ...ontrol Modes 13 2 2 2 Disabled keypad mode 14 2 2 3 MMSP mode 14 2 2 4 User level 14 2 2 5 Service Engineer Level 14 2 2 6 Restoring factory settings 15 2 3 OM 310 PRE OPERATION PROCEDURE 15 2 4 INTEN...

Страница 3: ...OM 310 is possible via OM 310 Control Panel Software that can be downloaded from the Novatek Electro website http www novatek electro com production_ htm OM 310 Control Panel software is dedicated fo...

Страница 4: ...ccuracy for wattage of rated wattage at most 5 Tripping threshold accuracy for current of rated current at most 2 Tripping threshold accuracy for voltage V at most 3 Phase imbalance detection accuracy...

Страница 5: ...V 100 300 3 V 111 112 113 Power voltage RMS values V 100 450 5 114 115 116 Positive sequence voltage V 100 300 3 B 117 Negative sequence voltage V 3 300 3 B 118 Zero sequence voltage vector sum of thr...

Страница 6: ...aggregate threshold calculation total power for all phases equals Pnn 154 Main threshold 50 150 110 155 Additional threshold 30 100 90 156 Time before load relay de energizing sec main threshold 0 300...

Страница 7: ...3 2 0 1 0 171 Protection function permission 0 2 0 0 protection function prohibited 1 protection function permitted after tripping automatic reset prohibited 2 protection function permitted after trip...

Страница 8: ...from Table 1 5 187 Min number of setting parameters mode ena ble 0 1 1 0 mode disabled 1 mode enabled The mode change is enabled in the service engineer mode only 188 Indication on OM 310 display pan...

Страница 9: ...red LED SETUP glows when the relay is in parameter setup mode 2 green LED LOAD glows when the load relay is closed 3 green LED RELAY glows when the characterizing relay is closed 4 green LED MMSP mod...

Страница 10: ...g it for connection of additional loading After 310 energizing after AR time parameter the load relay will close If during operation the active power consumed by the load crosses the main threshold fo...

Страница 11: ...on which event a or b comes first If during operation the active power consumed by the load crosses the additional threshold line 1 figure 1 3 for a time period that is longer than assigned by parame...

Страница 12: ...It is engaged when at least one of the phase current values reach the tripping threshold The protection has a time delay setting The delay can be independent constant or dependent SIT reverse depende...

Страница 13: ...time assigned by parameter 1 2 6 6 Protection based on phase sequence order trips in case of phase sequence order fault or phase coin cidence it opens the load relay and locks its further operation 1...

Страница 14: ...access mode When switching off the MMSP mode setting parameter 0 LED MMSP goes off In the user mode all parameters list is displayed but to change a parameter parform the following with DOWN and UP b...

Страница 15: ...th 5A rated output current shall be connected in accor dance with Fig 2 1 For correct OM 310 operation the current transformers polarity must be observed 2 3 2 Run all three power phase cables through...

Страница 16: ...h use of external CTs and at 2 characterizing relay operation in the mode of controlling additional load 2 4 INTENDED USE Note In the 310 operation description it is assumed that the protections descr...

Страница 17: ...0 or within 15 sec and then phase A current 1 indication is displayed again 2 4 3 Characterizing relay operation Functions performed by the characterizing relay are defined by parameter When 0 the re...

Страница 18: ...command code and DATA data symbols Data symbols format depends on command codes Command code 0x03 n words read For example read 2 continuous words swapped from 2102H in 310 initial address with 01H co...

Страница 19: ...ode 08h diagnostics 08h function provides a number of tests for checking communication system between PC and OM 310 and for OM 310 integrity control The function uses the sub function field to specify...

Страница 20: ...crc_chk unsigned char data unsigned char length int j unsigned int reg_crc 0xFFFF while length reg_crc data for j 0 j 8 j if reg_crc 0 01 reg_crc reg_crc 1 0xA001 LSB b0 1 else reg_crc reg_crc 1 retur...

Страница 21: ...f the data transferred unsupported function code etc 310 receives the request frame and forms a response with the error indicator and code A high order function field bit inserted in the unit serves a...

Страница 22: ...on in the remote control mode is defined by the parameter When 0 the load energize cutoff by means of remote breaker is prohibited When 1 310 with the open terminal of the S1 remote breaker fig 2 1 fu...

Страница 23: ...olling performed by pressing UP and DOWN buttons To exit log view mode press RECORD RESET SELECT button or the log will close automatically after 30 sec since last button was pressed Fault information...

Страница 24: ...e humidity when there are no fumes in the air that have a damaging effect on package and the equipment material The customer shall provide for the 310 equipment protection against mechanical dam age w...

Страница 25: ...25 NOVATEK ELECTRO 310 APPENDIX 1 Dependent time delay current based protection types...

Страница 26: ...26 310 NOVATEK ELECTRO...

Страница 27: ...27 NOVATEK ELECTRO 310...

Страница 28: ...28 310 NOVATEK ELECTRO...

Страница 29: ...220 240 LYQ20DC12 6031007G 6131406HQ 6 1393099 3 6 1393099 8 6 1393122 4 6 1393123 2 6 1393767 1 6 1393843 7 6 1415012 1 6 1419102 2 6 1423698 4 6 1608051 6 6 1608067 0 6 1616170 6 6 1616248 2 6 16162...

Отзывы: