background image

NovaLynx Corporation________________________________________________________________________________ 

 

 

 
210-421x-A 

Page 12 

March 2021 

 

7.3

 

Relay Connections 

There are two internal relays for alarms or operating pumps, etc. Please refer to the specifications to 
ensure the internal relays are rated for the load you intend to control. If the contact rating is less than 
required an external relay will be needed (not supplied). Refer the installation to a qualified electrical 
contractor. 

WARNING: Turn off all power sources before connecting to the relays.

 Identify which relay(s) you will 

be using and which function is required. When there is no alarm, the N.O. contacts are OPEN. This 
contact is used to turn something ON when there is an alarm. The N.C. contact does the opposite, i.e. 
turns something OFF when there is an alarm. 

The relay contacts are "dry". Connect the Hot lead to C1 for relay #1 or to C2 for relay #2. Connect the 
corresponding N.O. or N.C. output to the load. The return side of the load must be connected to 
Neutral to complete the circuit. Connect the grounding wire to the Earth Ground lug. 

WARNING: The unused spade lug (N.O. or N.C.) will be electrically HOT under some circumstances.

 

Place a spare connector or insulating tape over the unused lug to prevent anyone from touching it 
accidentally. 

Be sure you have programmed the temperature alarm to the settings you desire and the temperature 
alarm system is operating properly before you connect power to your external devices. 

8

 

ALARM FUNCTIONS 

 

The temperature alarm must be in Operating Mode in order for the alarms to 
activate. Alarms are disabled while programming and when the unit is in 
Paused Mode. Be sure to return the unit to Operating Mode when the alarm 
function is required.

 (See GO button instructions). 

Operating Mode Screen

 

Alarm Channel #1: 

The audible alarm will beep at 400 millisecond intervals (if enabled) and the relay will energize when 
the threshold and Delay-Before-ON timeout has occurred. A red LED on the circuit board will also flash. 

 

Alarm Channel #2: 

The audible alarm will beep at 200 millisecond intervals (if enabled) and the relay will energize when 
the threshold and Delay-Before-ON timeout has occurred. A red LED on the circuit board will also flash.  
When both alarms occur together, the beeping will be at 200 millisecond intervals. 

 

Paused Mode 

Press the GO button to place the controller in Paused Mode to turn off the alarms and relays. The 
controller will remain in this mode indefinitely unless the power to the controller is interrupted. Press 
GO again to return to operating mode.  

 

CLEAR Button 

(temporarily clears the alarm) 

The CLEAR button will stop the alarms by clearing the Delay Before ON timeout. If the temperature 
is beyond the programmed threshold the alarm will activate again when the timeout occurs. 

Temp: 71.4 (°F)
1:< 32    2:< 28

Содержание 210-421W-A

Страница 1: ...x A User Manual Dual Set Point Temperature Alarm 210 421 A Air Temperature 210 421W A Water Soil Temperature Air Temperature Sensor Water and Soil Temperature Sensor Phone 530 823 7185 Email nova nova...

Страница 2: ...ns in the case of delicate or sensitive items If packing facilities are not available take the equipment to the nearest Post Office UPS or other freight service and obtain assistance with the packagin...

Страница 3: ...P Button 6 4 2 3 DOWN Button 7 4 2 4 CLEAR Button 7 4 2 5 GO Button 7 4 3 Program Alarm Thresholds 7 4 4 Program Alarm Delays 8 4 5 DIP Switch Settings 8 5 TEMPERATURE SENSOR INSTALLATION 9 5 1 Air Te...

Страница 4: ...the unit is programmed by push button controls without the need to connect a computer All set points and the minimum and maximum temperatures are stored in non volatile memory DIP switch settings sele...

Страница 5: ...connectors supplied Relay specifications Form C SPDT N O and N C Contact rating 3A 24Vdc 115 VAC Alarm ON OFF delay range 0 to 99 seconds Timing accuracy 2 Measurement range 40 to 160 F 40 to 60 C In...

Страница 6: ...tion 4 2 Menu Navigation The programming buttons are below the display 4 2 1 MENU Button Press the MENU button One of three sub menus will be displayed depending on which was viewed last Additional us...

Страница 7: ...te to the Temp Alarms menu 1 Press GO until the display shows the operating mode screen see GO Button above 2 Press MENU to bring up one of the three sub menu displays 3 Press UP to reach the Temp Ala...

Страница 8: ...creen 4 5 DIP Switch Settings The DIP switches are pre set at the factory and should not need to be adjusted However sometimes during installation they get changed accidentally 1 The Dual Set Point co...

Страница 9: ...t is on the underside of the bracket The clamp will provide strain relief for the cable and ensure the sensor will not fall out For Pipe Mounting 1 Remove the U bolt from the mounting bracket 2 Secure...

Страница 10: ...AC receptacle for power If the controller is inside a building the sensor cable may need to be routed outside so that the sensor can be exposed ambient air conditions 6 2 Controller Mounting There are...

Страница 11: ...of this wire to a good earth ground an electrical box with an earth connection or a metal cold water pipe that actually enters the ground Failure to provide a ground may cause erratic operation and ma...

Страница 12: ...u have programmed the temperature alarm to the settings you desire and the temperature alarm system is operating properly before you connect power to your external devices 8 ALARM FUNCTIONS The temper...

Страница 13: ...Go PROGRAMMING BUTTONS MODE WIND UNITS TEMP UNITS BUZZER WIND MPH DEG F BUZZ TEMP KPH DEG C SILENT ON OFF Wt Wu Tu Si DIP SETTINGS DUAL SET POINT TEMPERATURE ALARM 210 421 A and 210 421W A Alarms OFF...

Отзывы: