NovaLynx Corporation________________________________________________________________________________
210-421x-A
Page 8
March 2021
4.4
Program Alarm Delays
To begin, navigate to the Alarm Delays menu:
1.
Press GO until the display shows the operating mode screen (see GO Button, above).
2.
Press MENU to bring up one of the three sub-menu displays.
3.
Press UP to reach the Alarm Delays sub-menu.
(Do NOT use the DOWN button to change
menus.)
Alarm Delays (s)
ON: 5 OFF: 5
Alarm Delays (s)
ON: 5 OFF: 5
MENU
MENU
MENU
(END)
ON Delay
OFF Delay
4.
Press MENU again. A blinking block cursor will appear at the ON Delay.
Note:
The range is 0 to 99 seconds.
a.
Press UP or DOWN to change the ON Delay.
b.
Press MENU to advance to the OFF Delay.
c.
Press UP or DOWN to change the OFF Delay.
d.
Press MENU to complete programming the Alarm Delays.
e.
Press GO to return to the operating mode screen.
4.5
DIP Switch Settings
The DIP switches are pre-set at the factory and should not need to be adjusted. However,
sometimes during installation they get changed accidentally.
1.
The Dual Set Point controller is designed to operate as either a wind alarm or temperature
alarm. The DIP switch marked "Wt" determines which mode is selected. Set this switch to
ON for temperature alarms.
2.
The "Wu" switch sets the wind speed units. This is not relevant to the temperature alarms,
so it doesn't matter how this switch is set.
3.
The "Tu" switch sets the temperature units. Set the "Tu" switch to OFF to display
temperature in degrees Fahrenheit (°F). Set the switch ON for degrees Celsius (°C).
4.
The "Si" (silent) switch determines whether the internal buzzer operates. The normal
setting is OFF which allows the buzzer to operate. The ON setting silences the buzzer.
The controller checks the positions of the DIP switches when the unit initializes during power-up.
Disconnect the AC Adapter for a few seconds and then re-connect power to change modes after
changing any switches.