SFP-400B    15124:G1   06/24/97

4

I

NFPA Standards

This control panel complies with the following NFPA standards:
NFPA 72-1993 Central Station Signaling Systems (Automatic, Manual, and Waterflow). Protected
Premises Unit (Requires NOTI-FIRE 911A/911AC DACT or MS5012 Slave Communicator).
NFPA 72-1993 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Protective Signaling
Systems.
NFPA 72-1993 Auxiliary (Automatic, Manual, and Waterflow) Protective Signaling Systems. (Requires
4XTM.)
NFPA 72-1993 Remote Station (Automatic, Manual, and Waterflow) Protective Signaling Systems.
(Requires 4XTM or NOTI•FIRE 911A/911AC DACT.)
NFPA 72-1993 Proprietary (Automatic, Manual, and Waterflow) Protective Signaling Systems. (Requires
Potter EFT-C McCulloh Transmitter.)

II

Additional Information

Note:  Before proceeding, the installer should be familiar with the following documents and standards:

NFPA 72 National Fire Alarm Code

Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for the Hearing Impaired
CAN/ULC-S524-M91 Standard for Installation of Fire Alarm Systems
CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm Systems

Other:
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
Notifier Device Compatibility Document,15378.
ADA Americans with Disabilities Act

Содержание SFP-400B

Страница 1: ...O N T R O L P A N E L Doc 15124 G1 ECN 97 192 ZONE 1 ZONE 2 ZONE 3 ZONE 4 AC POWER SYSTEM ALARM ALARM TEST SUPERVISORY SYSTEM TROUBLE TONE SILENCE ALARM SILENCE ALARM ACTIVATE RESET CIRCUIT TROUBLE P...

Страница 2: ...yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the uni...

Страница 3: ...LEDs 11 2 2 Control Switches 12 2 3 Zone Status LEDs 12 2 4 Supervisory 13 2 5 Zone Disable 13 2 6 Last Event Recall 13 3 0 Installation Procedure 14 3 1 General 14 3 2 Initiating Device Circuits 15 3...

Страница 4: ...Code Underwriters Laboratories Documents UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors Single and Multiple Station UL 228 Door Closers Holders for Fire Protective Signaling Systems UL...

Страница 5: ...o Optional supervised remote annunciator RZA 4X Requires LED Interface Module 4XLM o Optional digital communicator NOTI FIRE 911A 911AC Complies with NFPA 72 1993 Central Station and Remote Station P...

Страница 6: ...SFP 400B 15124 G1 06 24 97 6 Figure 1 0 1 SFP 400B Installation Diagram...

Страница 7: ...panel and trip coil 3 ohms Municipal Box wiring can leave the building For Remote Station service NFPA 72 1993 Remote Station Fire Alarm System Maximum load for each circuit 10 mA Reverse polarity out...

Страница 8: ...provide for off premises monitoring of a fire alarm control panel The 911AC is triggered by the alarm trouble and orsupervisorycontactsreceived fromthecontrolpanelandconvertstheminto digitaltransmiss...

Страница 9: ...stor Notification Appliance Circuits Power limited circuitry Maximum allowable voltage drop due to wiring 2 VDC Normal Operating Voltage 24 VDC Total current available to all external devices 2 25 amp...

Страница 10: ...SFP 400B 15124 G1 06 24 97 10 Cabinet 3 047 Backbox 3 0 Door 14 218 Backbox 14 Door 14 718 Backbox 14 5 Trim Ring TR 2 R Figure 1 5 1 Cabinet Dimensions...

Страница 11: ...LED that flashes for any trouble condi tion including those associated with option boards CIRCUIT TROUBLE Yellow LED that flashes for trouble conditions on output circuits notification ALARM SILENCED...

Страница 12: ...until 60 seconds after the initiation of the alarm Alarm Activate The ALARM ACTIVATE switch may be used to activate Notification Appliance Circuits ALARM ACTIVATE also activates the System Alarm relay...

Страница 13: ...status will be lost The Zone Disable routine makes use of the four panel switches as follows 1 Press and hold in the TONE SILENCE switch 2 With the TONE SILENCE switch held in press in sequence the A...

Страница 14: ...be in accordance with the National and or Local codes for fire alarm systems UL Power Limited Wiring Requirements Power limited and non power limited circuit wiring must remain separated in the cabine...

Страница 15: ...when connecting polarized devices 2 All circuits are supervised and power limited 3 Leave Dummy Load provided on all unused circuits TB4 4 7K 1 2 Watt part 71252 4 7K 1 2 Watt part 71252 4 7K 1 2 Wat...

Страница 16: ...detector current in alarm IR is the end of line relay current 24 VDC Common IDC IDC Red Black 24 VDC Common IDC IDC UL listed 24 VDC Four Wire Smoke Detectors UL Listed 4 7K 1 2 Watt ELR TB2 3 4 TB4 7...

Страница 17: ...ate only one Notification Appliance Circuit Circuit 2 cut jumper SUPV 1 To disable both NotificationApplianceCircuits cutjumper SUPV2forsupervisoryconditions Seefigurebelowforjumper location If a 4XZM...

Страница 18: ...50 60 Hz 1 2 amps and primary power required for the SFP 400BE panel is 220 240 VAC 50 Hz 0 6 amps Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code...

Страница 19: ...7 and J8 only 4XTM and 4XZM modules can be installed in either location Battery Power Observe polarity when connecting battery Connect battery cable to J9 on the main board using the plug in connector...

Страница 20: ...main board Carefully align the pins on the main board with J1 and or J2 on the option board Press firmly on the option board until it locks in place on the standoffs Affix the terminal identification...

Страница 21: ...h the disconnect switch down to prevent unwanted activation of the Municipal Box during testing of the control panel The Disconnect LED will remain illuminated while the Municipal Box is disconnected...

Страница 22: ...ower limited and power limited wiring must have a minimum distance of 0 25 wire to wire If this module is used to drive non power limited and power limited circuits please follow the instructions belo...

Страница 23: ...m Trouble Sound Resound 1 2 3 4 5 6 7 8 The wiring of this module must follow the requirements as specified in the General Section UL Power Limited Wiring Requirements LED Interface Module 4XLM Remote...

Страница 24: ...ing Circuit under test will sound piezo and light Zone Trouble LED Switch 1 Alarm Verification If selected alarm signals that occur on any zone will be subjected to a two minute verification period t...

Страница 25: ...ith AC power off System Trouble LED and audible trouble sounder on If using a 4XZM Zone Relay Module X 8 mA If using a 4XTM Transmitter Module add 11 mA If using the Reverse Polarity Alarm output add...

Страница 26: ...s within 48 hours 7 amp hour minium Batteries larger than 12 amp hour will require a UL listed battery cabinet e g Notifier BB 17 Table A 2 Ampere Hour AH Calculations amps X hours Enter 0 20 for 5 mi...

Страница 27: ...Transmitter Module for connection to a compatible listed Local Energy Municipal Box This unit must be installed as outlined in Figure B 1 NFPA 72 1993 Remote Station Protective Signaling System 4XTM T...

Страница 28: ...snotsuitableforseparatetransmission of sprinkler supervisory or trouble conditions Note Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms 4XTM Transmitter Module...

Страница 29: ...aving compatible ratings All connections are power limited and supervised with the exception of the reverse polarity loop Supervision of the loop is the responsibility of the receiver Fire Lite RS82 9...

Страница 30: ...by load shall be 125 mA The Standby by Battery Requirement 24VDC 7AH Max To Central Station Common Trouble Supervisory Alarm Red Black STD DACT NOTE on STD DACT Place jumper over pins 2 3 marked DACT...

Страница 31: ...and 911AC must be in conduit less than 20 in length in the same room NOTE on STD DACT Place jumper over pins 2 3 marked DACT when employ ing a DACT This directs the control panel to transmit all troub...

Страница 32: ...12VDC Battery 2 7AH Red Black 120 VAC HOT Neutral Ground Black White Green yellow yellow 1 2 TB2 TB3 RESET SILENCE MODE ALARM AC POWER TROUBLE SUPERVISORY Primary Active Secondary Active Kissoff J2 J...

Страница 33: ...ormer model ULT STK NO 1000391 listed Class 2 12 V 10 VA See Potter Electric Signal Company Bulletin 748 3 This control panel transmitter arrangement can be employed for NFPA 72 1993 Proprietary Prote...

Страница 34: ...e v o m e R y m m u d l l a t s n I d e l l a t s n i f i s e l u d o m l a n o i t p o V 2 1 r o f K 2 2 V 4 2 r o f K 7 4 R L E 2 s d a e l y r e t t a b h t o b e v o m e R 3 e m i t e h t t a t i...

Страница 35: ...SFP 400B 15124 G1 06 24 97 35 NOTES...

Страница 36: ...ng constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all...

Отзывы: