HLS PS25 & HLS PS50 User Manual
MN-DT-1305I_B
14
3.
Specification
Dimensions:
377 mm (w) x 408 mm (h) x 92 mm (d).
Power Supply Wattage:
130 W (HLSPS50) y 65 W (HLSPS25).
The HLSPS50 power supply has a total of 5Amp and 300mA
to 600mA of them are dedicated to charge batteries.
Input Voltage:
115 - 230 Vac; 50/60 Hz
Output voltage:
28 VDC +/-2% VDC (overload and short circuit protection).
Power Supply Outputs:
2
Terminals:
Removable terminals for 2.5 mm cable.
Optional conversion 2 outputs to 1 output: Yes, using DIP SW1.
Maximum current per output*:
1.10 Amp (HLSPS25); 2.20 Amp (HLSPS50).
Maximum current using only one output
2.20 Amp (HLSPS25); 4.40 Amp (HLSPS50).
Alarm input:
By linking both terminals with a jumper (or short-circuit), this
input allows the battery charger momentary disablement in
order to provide extra 300/600 mA to the outputs.
Battery load current:
300 mA (7 Amp/hour) / 600 mA (17 Amp/hour).
80% of the Battery Capacity is charged in less than 24 h and
the 100% in less than 48 h.
Fault relay:
C, NC, NO contacts. 1 Amp/24Vdc maximum.
Energized in normal state.
State Indicators:
10 external leds (5 mm) + 7 internal (SMD).
Battery room:
For 2 x 22 Amp/hour
Conduit knockouts:
Ø 21 mm
6 at the top of the back box
6 at the rear top of the back box
Earth Fault Supervision:
Configurable (ON/OFF)
Standards:
Design according to EN54-4; UL1950; TUV EN60950 and
EMC standards, EN55022, IEC1000-4-2,3,4,5 IEC1000-3-2.
Vibration test:
10-500 Hz 2G 10 min/1 cycle during 60 min. on each axle.
NOTE: Shield cables are required for power supply units’ connection.
Содержание HLSPS25-XP
Страница 2: ...HLS PS25 HLS PS50 User Manual MN DT 1305I_B 2...
Страница 15: ...HLS PS25 HLS PS50 User Manual MN DT 1305I_B 15...