HLS PS25 & HLS PS50 User Manual 

 

MN-DT-1305I_B                                                          

                                          9 

 

 

2.2 Battery 

 

DIP SW2 allows selecting the maximum current of battery load, 
depending on the batteries inside the power supply unit box.  
With DIP SW2 in ON position (up), 7Amp/h batteries can be charged 
at 300mA. When DIP SW2 is in OFF position (down), 20Amp/h 
batteries can be charged at 600mA. 

 

In this example, 

DIP

 

SW2

 is in OFF position 

(down) and the load current will be limited to 
600mA. 

 
 

 

DIP SW3

. This DIP switch is in ON position (up). 

For future use. 

 
 

DIP SW4

. For future use. 

 
 

2.3 Fault relay 

 

The Power Supply has a fault relay to report any anomaly to a remote 
control unit.  
Any fault has a delay of 30 seconds from the fault signal to fault relay 
confirmation, except when there is a mains AC loss, which will be 
indicated after an 8-minute delay to avoid faults from intermittent 
power cuts.  
In stand-by, the fault relay is energized indicating its normal operation. 
In case of any fault, the relay deactivates after the confirmation time.

 

 

 

Fault relay operation

 

 

FAULT

 switch with three terminals 

Terminal 1 (left) C common 
Terminal 2 (centre) NC or Normally Closed 
Terminal 3 (right) NO or Normally Open  

 

Fault relay operates as follows: 

 

 

No supervision (without power) or in fault condition 

 

 

Between C and NC —> continuity 
Between C and NO —> open circuit 

 

 

Operating with supervision without faults, i.e. in NORMAL STATE 

 

 

Between C and NC —> open circuit 
Between C and NO —> continuity 

 

 

 

 
 

Содержание HLSPS25-XP

Страница 1: ...Power Supply Unit HLS PS Series HLSPS25 XP and HLSPS50 XP User manual Information in this document is subject to change without notice 8 APRIL 2010 MN DT 1305I_B...

Страница 2: ...HLS PS25 HLS PS50 User Manual MN DT 1305I_B 2...

Страница 3: ...HLS PS for damage 4 1 2 Pre installation check list 5 1 3 Transient protection 5 1 4 Cleaning 5 1 5 Back Box HLS PS fixing 6 2 Functions and indicators 7 2 1 HLS PS25 and HLS PS50 characteristics 8 2...

Страница 4: ...lity of any supplied order items follow the procedure bellow 1 If after removing the HLS PS Series a visual inspection reveals that it has been damaged you MUST NOT continue with the installation but...

Страница 5: ...may operate erratically or can be damaged if subjected to lightning induced transients This equipment contains transient protection devices Although no system is immune from lightning transients and i...

Страница 6: ...y in the required position against the wall and mark the position of the fixing holes while ensuring the panel is level The drawing below shows the position of the fixing holes at the back box Do NOT...

Страница 7: ...ions and indicators FRONT PANEL 1 2 FUS BAT FAULT LOW BAT NO BAT BAT TEST BAT CH BAT DIS IN ALARM 321087 CPU MAX LEGEND ON FAULT MAIN SUPPLY FAULT BATTERY FAULT BATTERY CHARGER FAULT OUTPUT 1 FAULT OU...

Страница 8: ...tandard module control which supervises the entire power supply HLS PS25 and HLS PS50 power supplies provide 2 5 Amp and 5 Amp respectively and 300mA to 600mA of them are dedicated to charge batteries...

Страница 9: ...control unit Any fault has a delay of 30 seconds from the fault signal to fault relay confirmation except when there is a mains AC loss which will be indicated after an 8 minute delay to avoid faults...

Страница 10: ...arm input to disable momentarily the battery charger and be able to supply 300 600mA from battery load to the outputs For this it is necessary to link both IN ALARM terminals by means of a jumper or s...

Страница 11: ...n case batteries fail a Battery fault will be reported The HLS PS Series will supervise automatically the battery each 3 hours If the battery load is in normal condition the fault signal will disappea...

Страница 12: ...e fault relay signal and the FAULT led do not activate until the power supply fault remains for more than 8 minutes BATTERY FAULT Led Battery is not detected by the Control Unit or the battery voltage...

Страница 13: ...will not be earth fault supervision Earth fault solution Make sure that there are no links between Earth and Output 1 and 2 y OVERLOAD Led Indicates that the equipment exceeds the maximum current 5 A...

Страница 14: ...g both terminals with a jumper or short circuit this input allows the battery charger momentary disablement in order to provide extra 300 600 mA to the outputs Battery load current 300 mA 7 Amp hour 6...

Страница 15: ...HLS PS25 HLS PS50 User Manual MN DT 1305I_B 15...

Страница 16: ...www honeywelllifesafety es Honeywell Life Safety Charles Avenue Burgess Hill RH15 9UF West Sussex Tel 44 0 1444 230 300 England Avenue de L Expansion 16 D B 4432 Alleur Tel 32 0 4 247 03 00 Belgium w...

Отзывы: