2.1  HLS PS25 / HLS PS50 characteristics

 

 

 

These Power Supplies Units are designed to comply with the 
requirements of EN54-4 in order to provide fire control systems with 
backup supply. 
 
The HLS PS Series operates at 115/230 Vac and 50/60 Hz. 
 
Both Power Supply Units, HLS PS25 and HLS PS50, are very similar: 
they consist of a 2x65W, which means 130W in HLS PS50 and 1x65W 
in HLS PS25 and a standard module control which supervises the entire 
power supply. 
 
HLS PS25 and HLS PS50 power supplies provide 2.5 Amp and 5 Amp 
respectively and 300mA to 600mA of them are dedicated to charge 
batteries.  These power supplies are able to supply either up to 1.10 
and 2.20 Amp current at each PSO1 and PSO2 outputs. This is the 
default set up (DIP SW1 ON, 

up

 position). However, power supplies can 

also supply all the current in only one output by placing the DIP SW1 in 
the down position, OFF. This way, all the current (2.20Amp or 4.40Amp 
respectively) will be supplied through PSO1 output. 

 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
                                                       

 

HLS PS25

HLS PS50

SW1 up

SW1 up

SW1 down

SW1 down

Содержание HLSPS25-XP

Страница 1: ...Power Supply Unit HLS PS Series HLSPS25 XP and HLSPS50 XP User manual Information in this document is subject to change without notice 8 APRIL 2010 MN DT 1305I_B...

Страница 2: ...HLS PS25 HLS PS50 User Manual MN DT 1305I_B 2...

Страница 3: ...HLS PS for damage 4 1 2 Pre installation check list 5 1 3 Transient protection 5 1 4 Cleaning 5 1 5 Back Box HLS PS fixing 6 2 Functions and indicators 7 2 1 HLS PS25 and HLS PS50 characteristics 8 2...

Страница 4: ...lity of any supplied order items follow the procedure bellow 1 If after removing the HLS PS Series a visual inspection reveals that it has been damaged you MUST NOT continue with the installation but...

Страница 5: ...may operate erratically or can be damaged if subjected to lightning induced transients This equipment contains transient protection devices Although no system is immune from lightning transients and i...

Страница 6: ...y in the required position against the wall and mark the position of the fixing holes while ensuring the panel is level The drawing below shows the position of the fixing holes at the back box Do NOT...

Страница 7: ...ions and indicators FRONT PANEL 1 2 FUS BAT FAULT LOW BAT NO BAT BAT TEST BAT CH BAT DIS IN ALARM 321087 CPU MAX LEGEND ON FAULT MAIN SUPPLY FAULT BATTERY FAULT BATTERY CHARGER FAULT OUTPUT 1 FAULT OU...

Страница 8: ...tandard module control which supervises the entire power supply HLS PS25 and HLS PS50 power supplies provide 2 5 Amp and 5 Amp respectively and 300mA to 600mA of them are dedicated to charge batteries...

Страница 9: ...control unit Any fault has a delay of 30 seconds from the fault signal to fault relay confirmation except when there is a mains AC loss which will be indicated after an 8 minute delay to avoid faults...

Страница 10: ...arm input to disable momentarily the battery charger and be able to supply 300 600mA from battery load to the outputs For this it is necessary to link both IN ALARM terminals by means of a jumper or s...

Страница 11: ...n case batteries fail a Battery fault will be reported The HLS PS Series will supervise automatically the battery each 3 hours If the battery load is in normal condition the fault signal will disappea...

Страница 12: ...e fault relay signal and the FAULT led do not activate until the power supply fault remains for more than 8 minutes BATTERY FAULT Led Battery is not detected by the Control Unit or the battery voltage...

Страница 13: ...will not be earth fault supervision Earth fault solution Make sure that there are no links between Earth and Output 1 and 2 y OVERLOAD Led Indicates that the equipment exceeds the maximum current 5 A...

Страница 14: ...g both terminals with a jumper or short circuit this input allows the battery charger momentary disablement in order to provide extra 300 600 mA to the outputs Battery load current 300 mA 7 Amp hour 6...

Страница 15: ...HLS PS25 HLS PS50 User Manual MN DT 1305I_B 15...

Страница 16: ...www honeywelllifesafety es Honeywell Life Safety Charles Avenue Burgess Hill RH15 9UF West Sussex Tel 44 0 1444 230 300 England Avenue de L Expansion 16 D B 4432 Alleur Tel 32 0 4 247 03 00 Belgium w...

Отзывы: