Norton 6900 PowerMatic Скачать руководство пользователя страница 6

80-9369-0120-020 (09-08)

General Product Information

(See illustrations on page 2 for location of switch and valves.)

Function and Operation Sequence

• Selector Mode Switch

• "SC" Speed Control Valve

• "PA" pressure Adjustment Valve

– This is a three (3) position switch that

has positions marked "OFF” “ON” “H/O".

–  "ON" position – Unit is in standby, capable of function

activation either by a remote switch or scanner; or by the unit's
integral switch depending upon the Activation Mode.

– "H/O" position – Indefinite hold open. Door will hold open until

power is interrupted.

Power Assist Function Only (PAS).
These units must be manually pushed to the full open position

for this indefinite Hold Open function to operate.

– "OFF" position – All signal inputs are disabled, rendering all

power functions inoperative. The unit functions as a standard
hydraulic door closer.

–  Power Assist Function Only.

Adjusts the force required to open the door.

– Power Operator Funtion Only (POR).

Adjusts the opening speed of the door.

Important:

From closed position to 80 degrees must be 3

seconds or longer and 4 seconds or longer to the
fully open osition.

Factory set adjustment for opening force. Will not generally

require adjustment:

Important:

Power Operator Function Only (POR): The force

required to prevent a door from opening or closing
must not exceed a 15 lbf. (67N) applied 1" (25mm)
from the latch edge of the door at any point in the
opening or closing cycle.

p

VESTIBULE OPERATION

POWER OPERATOR FUNCTION – “POR”

In either Power Operator or Power Assist Function, initiation

of a power cycle may be performed on a delayed basis. This
feature, referred to as Vestibule Operation, allows placement
of the initiating switch at a remote location from the Door
Operator. The adjustable VEST DLY rotary switch/timer pot is
provided for selection a leng h of delay, appropriate for the
particular installation. The basic sequence is shown below:

• Initiate vestibule delay cycle JP1-INV from JP1-OUTV of

another unit or from a switch.

• Set VEST DLY rotary switch/timer pot to delay initiation of

pump motor.

• Upon initiation of pump motor, Power Operator or Power

Assist Function will start.

In the power operator function, initiation of the unit causes

the operator to fully open the door under its own power,
sustain the opened position for a set duration, and then
release and close.

The basic sequence is:
1. Initiate power cycle through any of the following JP1

terminal functions: AUX1, AUX2, RFT, JP1-INV, the L1
limit switch input, the H/O of slide switch or the JP1-O/O
terminal.

2. If JP1-INV is the power cycle initiating signal, read the

VEST DLY rotary switch/timer pot to determine how long
to wait before the power cycle starts.

3. Read the EXSOL DLY rotary switch/timer pot to determine

how long solenoid should be energized or de-energized,
depending upon function required.

4. Read th SW1-2 (A/D) dip switch to determine how long

solenoid should be energized.

5. Read the M DLY rotary switch/timer pot to determine how

long before the pump motor and solenoid valve tu n on.

6. When ELS board reaches upper taught limit, door is fully

open.

7. Pump motor turns off.
8. Read the CL/AS DLY rotary switch/timer pot to determine

the length of temporary hold open.

9. Solenoid valve turns off, releasing door from temporary

hold open.

10. Door closes and operator waits for next power cycle

in tiation.

Additional door open signals received during Step 8 of the Power
Operator function will cause the cl sing de ay timer to be reset to
the beginning.

t

e

r

i

o

l

Exceptions to the Power Operator Function

POWER ASSIST FUNCTION – "PAS”

Following is an explanation of the inputs that can modify the

basic flow of the Power Operator function described above.

1. If terminal JP1-PDET is signaled the door will not open if it

is closed or the door will not close if it is open. This signal
is normally used to connect to a presence detector which
will prevent the door from opening or closing when
someone is in the area of detection. Note that JP1-0/0 will
override the PDET signal.

2. If JP1-0/0 is signaled the door will open independently of

the state of JP1-PDET or JP2-E signals.

3. If the H/0 slide switch is set, the door will open and remain

open. JP1-PDET, JP1-0/0 or JP2-E will override the H/0
signal.

4. If JP2-E is signaled, the power cycle will terminate and the

door will close. JP1-0/0 will override the JP2-E signal.

5. The door must reach its fully open position within 7

seconds after it has started opening or the pump motor
and solenoid valve will be turned off allo ing the door to
close.

6. If the door is in the closed position, and not in the Manual

or Emergency mode, signaling RFT will initiate a door
power cycle. The door will remain open until PH1-RFT is
again signaled or until JP2-E is signaled. If the door is in
the open position, the RFT signal will close the door,
therefore, the door can be "toggled" between an open and
closed position.

In the Power Assist function, initiation of a power cycle

causes the pump motor and solenoid valve to engage,
requiring minimal force to open or close the door. The ease
of operation is sustained for an adjustable duration, after
which the motor and solenoid are turned off, causing the
door to close. If the door is fully opened during the power
cycle, the motor will disengage for the remainder of the
cycle. The solenoid will remain engaged for the duration of
the cycle. The basic flow for the Power Assist mode is the
same as the Power Operator mode except that the 7 second
time-out function is not in effect.

w

6

Содержание 6900 PowerMatic

Страница 1: ...ceed all of the requirements for the Power Assist Door POR Function is designed to meet or exceed all of the requirements for the Low Energy Power Operated Door C US UL 6900 PowerMatic Low Energy Power Operator Installation Instructions Activation Modes Modes are configured during installation Selectively Activated Mode Automatically Activated Mode Functions Functions are configured during install...

Страница 2: ...ng on butt hinges 5 127mm max width or 3 4 19mm offset pivots A separate door and frame preparation template will be supplied for other conditions Door thickness must be 1 3 4 44mm minimum 2 1 4 57mm maximum Door must swing freely through the entire opening and closing cycle before beginning the installation Use of a supplemental door stop is always recommended Requirements 2 SC SC XX XXXX PAS DN ...

Страница 3: ...ameter x 1 3 4 45mm long sex nut WARNING Make sure that 120V 60Hz input power is turned off before proceeding with installation 1 2 13 5 16 8 7 1 4 184 1 11 16 43 1 7 16 37 5 8 16 3 8 10 4 0 102 A 11 1 2 292 17 5 16 440 23 7 8 606 26 0 660 3 8 10 1 1 4 32 Notes Do not scale drawing Left hand door shown All dimensions are given in inches mm Thickness recommended for reinforcements in hollow metal d...

Страница 4: ...ven 7 two 2 ConcealedWired Units Only Surface Wired Units Only NOTE before Installation Sequence Fasten arm slide and shoe assembly to the door with the long end of arm shoe away from the hinge Slide the main arm onto the pinion shaft of the door control unit at a 90 angle to the door control unit and frame Align arm mark S with the flat corner of the pinion shaft square see illustration above rig...

Страница 5: ...Backcheck B valve as necessary for hydraulic resistance to door opening in the backcheck range See illustration on Page 2 1 8 Hex Key Slower Closing Faster Closing Closing Cycle Closed 10 L a t c h R a n g e S weep Range 1 8 Hex Key Increase Cushion Decrease Cushion Opening Cycle Backcheck O p e n i n g Length of Time Seconds Setting 0 2 5 10 15 20 25 30 0 1 2 3 4 5 6 7 If desired install No 668 S...

Страница 6: ... power cycle starts 3 Read the EXSOL DLY rotary switch timer pot to determine how long solenoid should be energized or de energized depending upon function required 4 Read th SW1 2 A D dip switch to determine how long solenoid should be energized 5 Read the M DLY rotary switch timer pot to determine how long before the pump motor and solenoid valve tu n on 6 When ELS board reaches upper taught lim...

Страница 7: ...AD STEPS COMPLETELY BEFORE PROCEEDING The ELS board is calibrated Timed to appropriate starting zone at the factory During a normal installation this procedure is not required If for any reason the ELS Board was removed or the ELS Board Pulley is turned without the pinion turning it is likely the ELS board will need to be re calibrated timed The ELS board may be timed while unit is mounted to the ...

Страница 8: ...eck SC Speed Control Valve setting Door may be opening too slowly Turn SC valve clockwise to increase speed 4 There may be wind or some other positive pressure present Adjust Obstruction Sensitivity to a longer time setting See page 7 PowerMatic Motor turns on and re activates door before it reaches jam or closed position a This could be caused by the unit sensing an obstruction on Closing 1 Check...

Отзывы: