Norton 6900 PowerMatic Скачать руководство пользователя страница 5

80-9369-0120-020 (09-08)

Activation Mode – (Push and Go)

Functions – Power Operator / Power Assist:

• Rotate the “SC” Valve Counter-Clockwise to adjus opening speed

(POR) or opening force (PAS).

• Rotate the “PA”Valve Clockwise if needed to adj st pressure.

(See illustrations on page 2 for Dip Switch and Valve location.

t

u

Adjust the “SC” valve so the the door does

not open when activated, but opening force is reduced below A.D.A
requirements. The “PA” valve is factory set and should not need
adjustment. Adjust if needed to obtain proper opening forces.

Power Assisted Opening:

Obstruction During Opening:

Obstruction During Closing:

Obstruction Sensitivity

The door will stop and close under spring force.

The door will stop and the unit will reopen the door.

If the

Obstruction During Closing is detected a second time, the door will
not attempt to reopen and will attempt to close under spring force.

The time delay of the obstruction feature can be adjusted in the field
as required.

The unit has been factory-configured to respond

immediately to an obstruction.

In certain applications where

excessive wind or excessive stack pressure is present, a delay of 1,
3, or 5 seconds can be selected by toggling dip switches T1 and T2
on the ELS board.

Obstruction Operation:

TEACHING CLOSED AND OPEN DOOR POSITIONS:

5

The following adjustments mechanical, hydraulic and electrical are
listed in a suggested sequence.

Make sure that power to unit is

.

• Set Closing Power. Use 11/16" wrench or socket. Turn Power

Adjustment Nut clockwise to increase door closing power. Door
control is shipped set at midpoint of power setting. Maximum
closing power can be achieved with 5 (360°) turns of the power
adjustment nut for a regular PowerMatic, 7 turns if unit is  a
Barrier Free (BF) unit.

– Use 1/8" hex wrench

• Closing Cycle – Make adjustments, as necessary, to the Sweep

Speed "S" valve and Latch Speed "L" valve. See illustration on
Page 2. Turn valves clockwise to reduce speed, counter
clockwise to increase speed.

NOTE:

MECHANICAL ADJUSTMENT

HYDRAULIC ADJUSTMENT

OFF

Adjustments for the PowerMatic Product

– Adjust "CL/AS DLY" Rotary Switch/Timer Pot on the printed

circuit board as necessary using a standard screwdriver with a
1/8" wide blade. Adjustable for 0 to 30 seconds (see chart
below).

– Power Assist Function Only:

Adjusts the length of time the motor will assist with opening

from the time the motor is activated.

– Power Operator Function Only:

Adjusts the length of time the door remains at the fully open
position after the operator function shuts off.

• Opening Cycle – Adjust Backcheck, "B" valve, as necessary, for

hydraulic resistance to door opening in the backcheck range. See
illustration on Page 2.

1/8"

Hex

Key

Slower
Closing

Faster
Closing

Closing Cycle

Closed

10°

L

a

tc

h

R

a

n

g

e

S

w

ee

p R

ang

e

1/8"

Hex

Key

Increase
Cushion

Decrease
Cushion

Opening Cycle

Backche

ck

O

p

e

ni

ng

Length of Time

(Seconds)

Setting

0

2

5

10

15

20

25

30

0

1

2

3

4

5

6

7

• If desired, install No. 668 Security Plate over notch in cover to

conceal the Selector Mode Switch when cover is installed.

• Install cover with mounting screws removed at beginning of

installation.

1

0 9

8

7

6

2

3

4

5

CL/AS DLY

S2

Illustration for CL/AS DLY

Rotary Switch/Timer Pot

From Printed Circuit Board

NOTE:

oo much Backcheck, "B" valve, can affect

he

operation of the units pump, preventing units rom fully
opening the door. This valve may requir fine tuning after all
other adjustments have bee made.

T

t

f

e

n

• Backcheck Position "P" valve is closed. Open by turning counter

clockwise, only if backcheck cushioning is required to begin at a
greater degree of door opening than the approximately 75° it is
set for.

ELECTRICAL:
Turn power input to unit on.
Selector Mode Switch – Set to the “ON” Position for normal use.

Time

B

ELS Dip Switch T1

B

ELS Dip Switch T2

1 Sec.

5 Sec.

Immediate

3 Sec.

A

A

B

B

A
A

Push And Go

A

ENABLED

DISABLED

B

ELS Dip #3 DN

Selectively Activated

Automatically Activated

Mode

Function

Power Operator

Power Assist

A

B

ELS Dip #4 PAS

Main Board Dip #1 P/A

OFF

ON

OBSTRUCTION DIP SWITCH SETTINGS:

!

Before operating, the PowerMatic 6900 must be “taught” the
fully closed and fully open door positions.

l

- Turn Power Input to Unit “ON”.
- With the door fully closed, press and release the BLACK

pushbutton on the ELS board. The ELS system will store this
position as closed and begin the 10 second “Teaching Mode”.

- Within the 10 second time frame, manually open the door to the

desired fully open position. While holding the door open in this
position, press and release the WHITE pushbutton on the ELS
board. The ELS system will store this position as open.

- Let the door return to the closed position.

This will end the

“Teaching Mode” regardless if the 10 second time frame has
elapsed.

- Set the Selector Mode Switch to the “ON” position for normal

operation or “H\O” for i

hold open.

-

If unit does not respond to teaching or if the ELS LED

began flashing when power input was first turned on and
continues to flash , see ELS Reset Instructions on page 8.

WARNING:

A

NOTE:

Verify that dip switch #3 on the ELS board is

in the “ ” position to disable the Push and Go Feature. Verify
the Selector Mode Switch is in the“OFF”position (Page 2)

• ELS board comes from factory with potentiometer timed” and
ready for unit to be taught open and c osed door positions.

ndefinite

Содержание 6900 PowerMatic

Страница 1: ...ceed all of the requirements for the Power Assist Door POR Function is designed to meet or exceed all of the requirements for the Low Energy Power Operated Door C US UL 6900 PowerMatic Low Energy Power Operator Installation Instructions Activation Modes Modes are configured during installation Selectively Activated Mode Automatically Activated Mode Functions Functions are configured during install...

Страница 2: ...ng on butt hinges 5 127mm max width or 3 4 19mm offset pivots A separate door and frame preparation template will be supplied for other conditions Door thickness must be 1 3 4 44mm minimum 2 1 4 57mm maximum Door must swing freely through the entire opening and closing cycle before beginning the installation Use of a supplemental door stop is always recommended Requirements 2 SC SC XX XXXX PAS DN ...

Страница 3: ...ameter x 1 3 4 45mm long sex nut WARNING Make sure that 120V 60Hz input power is turned off before proceeding with installation 1 2 13 5 16 8 7 1 4 184 1 11 16 43 1 7 16 37 5 8 16 3 8 10 4 0 102 A 11 1 2 292 17 5 16 440 23 7 8 606 26 0 660 3 8 10 1 1 4 32 Notes Do not scale drawing Left hand door shown All dimensions are given in inches mm Thickness recommended for reinforcements in hollow metal d...

Страница 4: ...ven 7 two 2 ConcealedWired Units Only Surface Wired Units Only NOTE before Installation Sequence Fasten arm slide and shoe assembly to the door with the long end of arm shoe away from the hinge Slide the main arm onto the pinion shaft of the door control unit at a 90 angle to the door control unit and frame Align arm mark S with the flat corner of the pinion shaft square see illustration above rig...

Страница 5: ...Backcheck B valve as necessary for hydraulic resistance to door opening in the backcheck range See illustration on Page 2 1 8 Hex Key Slower Closing Faster Closing Closing Cycle Closed 10 L a t c h R a n g e S weep Range 1 8 Hex Key Increase Cushion Decrease Cushion Opening Cycle Backcheck O p e n i n g Length of Time Seconds Setting 0 2 5 10 15 20 25 30 0 1 2 3 4 5 6 7 If desired install No 668 S...

Страница 6: ... power cycle starts 3 Read the EXSOL DLY rotary switch timer pot to determine how long solenoid should be energized or de energized depending upon function required 4 Read th SW1 2 A D dip switch to determine how long solenoid should be energized 5 Read the M DLY rotary switch timer pot to determine how long before the pump motor and solenoid valve tu n on 6 When ELS board reaches upper taught lim...

Страница 7: ...AD STEPS COMPLETELY BEFORE PROCEEDING The ELS board is calibrated Timed to appropriate starting zone at the factory During a normal installation this procedure is not required If for any reason the ELS Board was removed or the ELS Board Pulley is turned without the pinion turning it is likely the ELS board will need to be re calibrated timed The ELS board may be timed while unit is mounted to the ...

Страница 8: ...eck SC Speed Control Valve setting Door may be opening too slowly Turn SC valve clockwise to increase speed 4 There may be wind or some other positive pressure present Adjust Obstruction Sensitivity to a longer time setting See page 7 PowerMatic Motor turns on and re activates door before it reaches jam or closed position a This could be caused by the unit sensing an obstruction on Closing 1 Check...

Отзывы: