Section 6: Wiring Requirements
Section 6: Wiring Requirements
Section 6: Wiring Requirements
Section 6: Wiring Requirements
Section 6: Wiring Requirements
Figure 6-1.
Card Reader Connections to TB5.
N-1000-III Terminal Block 5 supports
interface for two Wiegand output card readers and provides an alarm point common. Each card
reader port includes terminals for LED control, Data 1 signal, Data Ø signal, +5 VDC output and
Ground. +12 VDC power is available on Terminal Block 9 position 7. Card reader/keypad
communication shields should be connected to TB5 position 12. The shield at the card reader/
keypad end should not be grounded unless the device is electrically floating (not touching metal).
Brown LED
White Data 1
Green Data Ø
Red +5 VDC
Black Ground
Blue Not used
(Aux. Output 11)
Panel must be
earth grounded.
S-4 SUPPRESSION
REQUIRED ACROSS
EVERY ACTIVE RELAY
AND ELECTRICAL
DEVICE (CONNECT
WITHIN 18 INCHES).
Lock Solenoid
1
3
4
5
6
7
8
9
10
2
11
12
Shield
Shield
no connection
Shield
Shield
no connection
Card Reader 1
Card Reader 2
Blue Not used
Red +5 VDC
Black Ground
Green Data Ø
White Data 1
Brown LED
(Aux. Output 12)