49
Main parts check
1. Temperature sensor checking
Disconnect the temperature sensor from PCB, measure the resistance value with a tester.
Temperature Sensors.
Room temp.(T1) sensor,
Indoor coil temp.(T2) sensor,
Outdoor coil temp.(T3) sensor,
Outdoor ambient temp.(T4) sensor,
Compressor discharge temp.(T5) sensor.
Measure the resistance value of each winding by using the multi-meter.
Table 1:Some frequently-used R-T data for T1,T2,T3 and T4 sensor:
Temperature (
℃
)
5
10
15
20
25
30
40
50
60
Resistance Value (KΩ)
26.9 20.7 16.1 12.6 10
8
5.2
3.5
2.4
Table 2:Some frequently-used R-T data for T5 sensor:
Temperature (
℃
)
5
15
25
35
60
70
80
90
100
Resistance Value (KΩ)
141.6 88
56.1 36.6 13.8 9.7
6.9
5
3.7
Resistance value (KΩ)
Temperature (
℃
)
T5
T1,T2,T3,T4
Содержание MSC-28CRDN1-MN15W
Страница 10: ...8 For MSC 28CRDN1 MN15W and MSC 36CRDN1 MN5W models ...
Страница 14: ...12 5 Wiring Diagram 5 1 Indoor Unit MSC 28CRDN1 MN15W MSC 30HRDN1 MP0W MSC 36CRDN1 MN5W MSC 36HRDN1 MN5W ...
Страница 15: ...13 5 2 Outdoor Unit MOG 28CDN1 MN15W MOG 30HDN1 MP0W MOJ 36CDN1 MN5W MOJ 36HDN1 MN5W ...
Страница 26: ...24 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage ...