15
6.3 Pipe length and the elevation
Model
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas
Liquid
MSC-30HRDN1-MP0W+MOG-30HDN1-MP0W
5
/8’’
(
Ф15.9)
3/8’’
(
Ф9.52)
5
10
20
40
MSC-28CRDN1-MN15W+MOG-28CDN1-MN15W
5
10
20
40
MSC-36HRDN1-MN5W+MOJ-36HDN1-MN5W
5
10
25
40
MSC-36CRDN1-MN5W+MOJ-36CDN1-MN5W
5
10
25
40
Caution:
The capacity test is based on standard length and the maximum permissive length is based on the
system reliability.
Oil trap should be installed per 5-7 meters.