33
Decrease: Running frequency decrease to lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
Note:
When AC is in “hold” zone for 3 minutes, the compressor frequency will rise to the higher
level.(frequency increases twice at most)
8.4.3.2 Outdoor fan running rules:
17
15
Low
High
8.4.3.3 Indoor fan running rules:
If the compressor stops caused by room temperature rising, indoor fan will be forced to run 127
seconds with breeze. During this period, anti-cold-wind is disabled. After this, anti-cold
–wind function
is available.
If the machine runs in rating capacity test mode, indoor fan runs with rating speed, and anti-cold-wind
is disabled.
Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is
preferential.
Содержание MSC-28CRDN1-MN15W
Страница 10: ...8 For MSC 28CRDN1 MN15W and MSC 36CRDN1 MN5W models ...
Страница 14: ...12 5 Wiring Diagram 5 1 Indoor Unit MSC 28CRDN1 MN15W MSC 30HRDN1 MP0W MSC 36CRDN1 MN5W MSC 36HRDN1 MN5W ...
Страница 15: ...13 5 2 Outdoor Unit MOG 28CDN1 MN15W MOG 30HDN1 MP0W MOJ 36CDN1 MN5W MOJ 36HDN1 MN5W ...
Страница 26: ...24 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage ...