Page 68 of 120
Configuring ISDN BRI hardware
553-3001-218 Standard 2.00 September 2004
Procedure 19
Connecting system cables to the cross-connect terminal
Each card slot equipped with a SILC or UILC requires one NE-A25B 25-pair
connector cable.
1
Remove the connector retaining bar from the connector panel in the lower
part of each cabinet. See Figures 17 and 18 on
, and Figure 19
2
Connect an NE-A25B cable to each connector associated with a card slot
containing a SILC or UILC circuit card. See Figures 17 and 18 on
and Figures 19 and 20 on
.
Tag both ends of each cable with the cabinet or MG 1000S connector
numbers.
3
Connect the cables to the connectors at the bottom of the cabinet or at the
rear of the MG 1000S.
4
Replace the retaining bar when you connect all the cables to the system.
5
Terminate the 25-pair cables at the cross-connect terminal.
6
Label the cross-connect terminal for each connector (UILC or SILC).
Figures 21 and 22 on page 71 show the label used with the BIX cross-
connecting system.
Note:
Use of the BIX cross-connect system is not mandatory. The
system supports other cross-connect equipment. Refer to the
documentation provided with your cross-connect system for further
information.
End of Procedure
Содержание Communication Server 1000M
Страница 2: ......
Страница 4: ...Page 4 of 120 Revision history 553 3001 218 Standard 2 00 September 2004...
Страница 12: ...Page 12 of 120 About this document 553 3001 218 Standard 2 00 September 2004...
Страница 16: ...Page 16 of 120 Preparing for installation 553 3001 218 Standard 2 00 September 2004...
Страница 52: ...Page 52 of 120 Installing ISDN BRI hardware 553 3001 218 Standard 2 00 September 2004...
Страница 90: ...Page 90 of 120 Configuring ISDN BRI hardware 553 3001 218 Standard 2 00 September 2004...
Страница 98: ...Page 98 of 120 Preparing the system 553 3001 218 Standard 2 00 September 2004...
Страница 120: ...Page 120 of 120 Generating traffic reports 553 3001 218 Standard 2 00 September 2004...
Страница 121: ......