Nortek Reznor VRA-4E Series Скачать руководство пользователя страница 9

1712VRA

4EGBEN,

 

pag..

 

9/25

 

                   

INSTALLATION

 

 

 

4.1 Unpacking and preparation 

 

Prior to dispatch, the air heater was operated and 
tested at the factory. If the heater has incurred 
any damage in shipment, file a report claim within 
2 working days from receipt. 
Check the shipping label and data plate to ensure 
the specification of gas and electrical supplies are 
compatible. Read this document and become 
familiar with the installation requirements and the 
appliance before commencing installation. 
 

4.2 Suspending the air heater 

 

Before installing the appliance, check to 
ensure that the supporting structure is 
adequate to carry the weight of the appliance 
and its ancillaries i.e. flue system.  Consult 
table 1 for weight data. 
When the heater is lifted for suspension, 
support the bottom of the heater with plywood 
or other appropriately placed material.  If the 
bottom is not supported, damage could occur. 
The heater is supplied with four point 
suspension. All points must be used. Two 
threaded nut retainers are provided on each 
side of the top of the heater. See dimensions 
in section 2.2 and figure 3. 

Be sure that the 

threaded hanger rods are locked to the heater as 
illustrated.  Recommended maximum hanger rod 
length is 1.8m. 
IMPORTANT : Suspend the heater from the 
threaded nut retainers. Do not suspend from the 
heater cabinet panels. Do not place or add 
additional weight to the suspended air heater. 
See hazard levels, page 2. The heater must be 
installed in a level plane to ensure proper 
operation. 
 

Figure 3 Suspension detail 

 

Add a nut to lock 

the M10x1.5 hanger 

rod to the heater 

 

 

 

 

4.3 Fitting the Combustion air inlet/Flue system 

 

Flue pipe runs may be horizontal or vertical and 
terminate either through the wall or roof. 

See 

table 5 for maximum pipe length for an 
appliance installed as type B or table 6 for 
maximum lengths and approved supplied 
concentric terminals for a heater installed as a 
type C appliance.

 All pipe runs must be 

independently supported so that the heater does 
not carry any of the weight of the flue system. 
 

4.3.1 Fitting the flue pipe (table 5) 

The flue pipe socket is located on the back of the air 
heater. Flue pipes must be sealed. Use seamless, 
aluminium pipe or equivalent. Follow pipe 
manufacturer's instructions (see figures 4 & 5).

 

 

4.3.2 Installing a guard on the combustion air inlet 
pipe for power vent (Type B installations) 

The combustion air inlet socket is located at the 
back of the heater. When installed as a type B 
appliance,  
protect the inlet by fitting an access guard on the 
socket. 

Do not block this socket as it supplies 

combustion air for the burner (see figure 4). 

 

4.3.3 Fitting the combustion air inlet pipe for 
balanced flue (Type C installations) (table 6) 

The combustion air pipe attaches directly to the 
inlet socket at the back of the heater. Air inlet 
pipes must be sealed. Use seamless aluminium 
or equivalent. Follow the pipe manufacturer's 
installation instructions. See typical installations 
in figure 5. 

 

Figure 4 

 

 

 
 
 
 
 
 
 
 
 
 

Figure 5 

 

 

 

Содержание Reznor VRA-4E Series

Страница 1: ...ng Leave it with the user or attached to the appliance or gas service meter after installation WARNING Improper installation adjustment alteration service or maintenance can cause property damage inju...

Страница 2: ...ir Pressure Switch 8 7 Combustion Air Fan 9 0 FAULT FINDING p 17 10 0 PARTS LIST p 20 11 0 GAS CONVERSION p 20 12 0 USERS INSTRUCTIONS p 21 13 0 HEALTH SAFETY STATEMENT p 22 HAZARD INTENSITY LEVELS DA...

Страница 3: ...odels have an axial fan for air delivery These heaters are designed for overhead suspension and are suitable for indoor installation only installed at an operation ambient temperature between 15 C and...

Страница 4: ...pressure G20 natural gas Inlet pressure 20 0 mbar Table 2 Injector size and burner pressure G20 natural gas Inlet pressure 20mbar Table 3 Injector size and burner pressure G30 G31 butane propane Inle...

Страница 5: ...0 151 759 73 808 301 1022 479 477 82 180 608 833 212 212 123 942 550 3 4 G 120 1750 980 846 130 67 1100 164 602 177 1057 348 490 90 175 595 795 160 256 20 1365 770 3 4 G 145 1750 1150 846 130 67 1100...

Страница 6: ...r for the appropriate protection grill IP20 dia130 PN 02 25094 Each heater installed as a type C appliance must be fitted with an individual combustion air flue pipe system Only systems specified by t...

Страница 7: ...outlet socket for flue pipe 2 Combustion air inlet opening Follow any flue pipe manufacturers installation instructions for making joints including connections to the air heater for passing through a...

Страница 8: ...l modify the air throw pattern achieved In building having low heat loss where single heaters are required to cover a large floor area and in buildings with high ceiling heights air re circulation fan...

Страница 9: ...ir heater See hazard levels page 2 The heater must be installed in a level plane to ensure proper operation Figure 3 Suspension detail Add a nut to lock the M10x1 5 hanger rod to the heater 4 3 Fittin...

Страница 10: ...he appliance for long enough to ensure that lock out does not reoccur suggest 5 minutes Fix all electric cables and installer s wiring to the control panel and ensure they do not touch the combustion...

Страница 11: ...ed adjacent to the air heater 6 2 Gas connection ATTENTION NEVER USE A FLAME FOR CHECKING GAS SOUNDNESS Only persons formally qualified to work on gas fired apparatus may carry out commissioning and t...

Страница 12: ...rried out Ascertain from section 1 of this document and the appliance data plate the correct operating gas pressure for the air heater Turn the room thermostat control to its lowest setting Remove the...

Страница 13: ...onds after the burner has lit the time delay relay will activate the thermal fan control which will energize the fan motor Continue to operate the air heater for several minutes to ensure correct oper...

Страница 14: ...soot deposits from the burner with a wire brush Clean the ports with a degreaser or acetone A vacuum cleaner or compressed air may assist in this cleaning operation Wipe the inside of the burner tube...

Страница 15: ...valve 6 At the burner rack assembly remove the nuts that secure the burner manifold to the burner rack Lift the burner rack manifold assembly upward and pull the assembly out of the air heater Instru...

Страница 16: ...ontrol operating valve is the prime safety shut off All gas supply lines must be free of dirt scale etc before connecting to the air heater thus ensuring positive closure of the control valve 8 5 Comb...

Страница 17: ...7 25 FAULT FINDING Fault finding may only be carried out by appropriately qualified persons Air heater does not operate and lock out indicator light is off Air heater does not operate and lock out ind...

Страница 18: ...1712VRA 4EGBEN pag 18 25...

Страница 19: ...1712VRA 4EGBEN pag 19 25...

Страница 20: ...Gas valve modureg 120 145M 03 25144M Burner relay E 03 25321 Ignition electrode ER 03 400US 42 Ignition electrode ER 120 145 05 25186 Flame sensor electrode IS 03 401US 195292 ERP fan 12 01 27003 ERP...

Страница 21: ...lly when the room thermostat calls for heat after about 30 sec 6 If the appliance does not light a check that the burner control does not require resetting An indicator light glows at the inside panel...

Страница 22: ...suffer reddening and itching of the skin Fiber entry into the eyes will cause foreign body irritation Inhalation will cause irritation to the respiratory tract Precautions Wear protective gloves when...

Страница 23: ...tive Complies with the requirements of further directives namely GAD 2009 142 EC EMC 2014 30 EC LVD 2014 35 EC the following harmonized standards have been applied EN 1020 Non domestic gas fired force...

Страница 24: ...mum capacity pl 80 9 77 7 76 2 76 2 77 6 79 0 76 2 77 8 77 7 78 6 79 6 Envelope loss factor Fenv 0 0 0 0 0 0 0 0 0 0 0 Ignition burner power consumption Pign kW 0 02 0 02 0 02 0 02 0 02 0 02 0 02 0 02...

Страница 25: ...A United Kingdom Tel 01384 489 250 Fax 01384 487 707 reznorsales nortek com www reznor co uk Nortek Global HVAC is a registered trademark of the Nortek Global HVAC Limited Because of continuous produc...

Отзывы: