PARTS LISTING
VRA-4 E
Part number
Delta P switch S3: 12
30 606177 200
238Pa out
250Pa in
Delta P switch S3: 20
30 60617 185
175Pa out
203Pa in
Delta P switch S3: 30/35/45/50/60/75
30 60621 175
162
7Pa out
176
7Pa in
Delta P switch S3: 120/145
30 60617 185
185Pa out
203Pa in
Delta P switch S3 : 100
30 60621 130
135
±
5Pa out
147
±
5Pa in
Overheat control device LC1 (not 120/145)
03 24959 04
90°C out
85° C in
Overheat control device LC3 (all, exc 100, 120 & 145)
03 24959 03
110° C out
reset
Overheat control device LC3 (100)
03 24959
96° C out
reset
Overheat control device LC3 (120/145)
03 24959 03
110° C out
reset
Overheat control device LC3 (120/145)
03 24958
86° C out
reset
Venter motor (all exc 120/145)
11 43426 04
Venter motor 120/145
20 25749
Gas valve modureg 35/45/60/75/100
03 25136M
Gas valve modureg 12/20/30
03 25141M
Gas valve modureg 120/145M
03 25144M
Burner relay E
03 25321
Ignition electrode ER
03 400US 42
Ignition electrode ER (120/145)
05 25186
Flame sensor electrode IS
03 401US 195292
ERP fan 12
01 27003
ERP fan 20
01 27006
ERP fan 30
01 27021
ERP fan 35/45
01 27010 01
ERP fan 50
01 27011 01
ERP fan 60/75
01 26063
ERP fan 100
01 27014 02
ERP fan 120/145 (2x)
01 26063
Settings
GAS CONVERSION
VRA-4E air heaters are designed to operate
on natural or propane gas and will be
supplied fitted for the gas type ordered. In
the event of site conversion to a different gas
type it is necessary to convert the gas burner
and burner controls.
Affix new data plate and gas type over-
sticker.
Upon completion of conversion re-commission
the air heater in accordance with section 6 of
this document.
Changes to carry out:
- Natural gas: use Honeywell VR4601AB (PN 03
25136) - set pressure regulator as per Table 2A
- Propane: use Honeywell VR4601B (PN 03
25136B) or VR blocking plate
To adapt gas injectors and gas inlet pressures,
we refer to table 2A/2B
.