SERVICING INSTRUCTIONS

 

 

IMPORTANT: Only appropriately qualified persons 
may carry out servicing and fault finding on this gas 
fired equipment. Before commencing service ensure 
that both the gas and the electricity are turned and 
switched "OFF" and that the air heater has cooled 
down.  Inadvertent substitution or replacement of 
components similar to those specified or replacement 
in a manner contrary to the method herein described 
could constitute a hazard and lead to prosecution. 

VRA-4E air heaters will operate with a minimum 
of maintenance. To ensure long life and 
satisfactory and safe performance, an air heater 
that is operated under normal conditions should 
be inspected and cleaned at the start of each 
heating season. If the air heater is operated in an 
area where unusual amounts of dust, etc are 
present in the air, more frequent servicing is 
recommended. 
 

 

 

When any service is completed, be sure that 
components are reassembled correctly to ensure 
that no unsafe condition exists. 
Upon completion of the service carry out the 
commissioning instructions outlined in section 6 
of this document. 
 
 

WARNING: Excessive dirt build-up on the inside of 
the burner ports could cause unburnt gas to spill out 
of the back of the burner tube causing a fire or 
explosion. To prevent this occurring,

 

clean all of the 

burner ports at least annually. 
 
CAUTION : When cleaning air heaters, wearing of eye 
protection and a dust face mask is recommended.

 

 

 

Service procedure 

 
The following procedures should be carried out at 
least annually: 
 

1.  Remove the burner assembly as in section 

8.1. Clean thoroughly, (cleaning the burners 
requires an emery cloth, wire brush and a 
cleaning cloth -stubborn deposits on burners 
are best cleaned using 

"acetone"

 as a 

solvent). 

* Check the condition of the ignitor and clean 

to remove all deposits. Check the spark gap 
(3,0 mm). 

 * Check the sensor - clean as necessary. 
* Remove any soot deposits from the burner 

with a wire brush. Clean the ports with a 
degreaser or acetone. A vacuum cleaner or 
compressed air may assist in this cleaning 
operation. Wipe the inside of the burner tube 
clean (cleaning thoroughly with a degreaser 
as recommended will retard future build-up of 
dirt).  Inspect the burner for any damage or 
deterioration. If the burner is damaged or 
corroded, replace it. 

 

2. The heat exchanger should remain clean 

unless a problem has developed due to poor 
combustion. Examine the heat exchanger 
tubes internally and externally for any sign of 
deterioration. The outside of the tubular heat 
exchanger can be cleaned from the front of 
the heater with an air jet and/or a flexible 
brush. Remove any dust and grease deposits. 

 

The inner surfaces of the heat exchanger can 
be reached for cleaning with the burner and 
combustion air fan (venter) assemblies 
removed. Clean with a flue brush or a heavy 
wire to which wire wool has been attached.  

  Brush inside each heat exchanger tube until 

all foreign material has been removed. The 
use of a flashlight is necessary to carry out 

this operation. 

 
 
 
3.  Clean the axial fan blades, fan guard, and fan 

motor to remove all external dirt. Check the 
security of the fan on the motor.  

Note

: Fan motors are lubricated for life and do 

not require lubricating. 

 

4.  Remove any dirt and/or grease that may have 

accumulated on the venter fan motor and its 
housing. 

Note:

 The combustion air fan motors 

are lubricated for life and do not require oiling 
or greasing. 

 
5.  The gas multi-functional control valve requires 

no field maintenance except cleaning of its 
exterior and checking the condition of the wire 
connections. Instructions for testing pressure 
are given in section 6.6. 

 
6. Check the flue/combustion air system for 

soundness. Reseal/replace any parts that are 
not sound. 

 
7.  Check all wiring connections. Check wiring for 

any signs of damage. Replace any suspect 
wiring with an equivalent specification. 
 

8. Check operation of thermal fan control and 

control relay. 

 
9. When service is complete carry out full 

commissioning procedure as per section 6 of 
this document. 

Содержание Reznor VRA-4E Series

Страница 1: ...ng Leave it with the user or attached to the appliance or gas service meter after installation WARNING Improper installation adjustment alteration service or maintenance can cause property damage inju...

Страница 2: ...ir Pressure Switch 8 7 Combustion Air Fan 9 0 FAULT FINDING p 17 10 0 PARTS LIST p 20 11 0 GAS CONVERSION p 20 12 0 USERS INSTRUCTIONS p 21 13 0 HEALTH SAFETY STATEMENT p 22 HAZARD INTENSITY LEVELS DA...

Страница 3: ...odels have an axial fan for air delivery These heaters are designed for overhead suspension and are suitable for indoor installation only installed at an operation ambient temperature between 15 C and...

Страница 4: ...pressure G20 natural gas Inlet pressure 20 0 mbar Table 2 Injector size and burner pressure G20 natural gas Inlet pressure 20mbar Table 3 Injector size and burner pressure G30 G31 butane propane Inle...

Страница 5: ...0 151 759 73 808 301 1022 479 477 82 180 608 833 212 212 123 942 550 3 4 G 120 1750 980 846 130 67 1100 164 602 177 1057 348 490 90 175 595 795 160 256 20 1365 770 3 4 G 145 1750 1150 846 130 67 1100...

Страница 6: ...r for the appropriate protection grill IP20 dia130 PN 02 25094 Each heater installed as a type C appliance must be fitted with an individual combustion air flue pipe system Only systems specified by t...

Страница 7: ...outlet socket for flue pipe 2 Combustion air inlet opening Follow any flue pipe manufacturers installation instructions for making joints including connections to the air heater for passing through a...

Страница 8: ...l modify the air throw pattern achieved In building having low heat loss where single heaters are required to cover a large floor area and in buildings with high ceiling heights air re circulation fan...

Страница 9: ...ir heater See hazard levels page 2 The heater must be installed in a level plane to ensure proper operation Figure 3 Suspension detail Add a nut to lock the M10x1 5 hanger rod to the heater 4 3 Fittin...

Страница 10: ...he appliance for long enough to ensure that lock out does not reoccur suggest 5 minutes Fix all electric cables and installer s wiring to the control panel and ensure they do not touch the combustion...

Страница 11: ...ed adjacent to the air heater 6 2 Gas connection ATTENTION NEVER USE A FLAME FOR CHECKING GAS SOUNDNESS Only persons formally qualified to work on gas fired apparatus may carry out commissioning and t...

Страница 12: ...rried out Ascertain from section 1 of this document and the appliance data plate the correct operating gas pressure for the air heater Turn the room thermostat control to its lowest setting Remove the...

Страница 13: ...onds after the burner has lit the time delay relay will activate the thermal fan control which will energize the fan motor Continue to operate the air heater for several minutes to ensure correct oper...

Страница 14: ...soot deposits from the burner with a wire brush Clean the ports with a degreaser or acetone A vacuum cleaner or compressed air may assist in this cleaning operation Wipe the inside of the burner tube...

Страница 15: ...valve 6 At the burner rack assembly remove the nuts that secure the burner manifold to the burner rack Lift the burner rack manifold assembly upward and pull the assembly out of the air heater Instru...

Страница 16: ...ontrol operating valve is the prime safety shut off All gas supply lines must be free of dirt scale etc before connecting to the air heater thus ensuring positive closure of the control valve 8 5 Comb...

Страница 17: ...7 25 FAULT FINDING Fault finding may only be carried out by appropriately qualified persons Air heater does not operate and lock out indicator light is off Air heater does not operate and lock out ind...

Страница 18: ...1712VRA 4EGBEN pag 18 25...

Страница 19: ...1712VRA 4EGBEN pag 19 25...

Страница 20: ...Gas valve modureg 120 145M 03 25144M Burner relay E 03 25321 Ignition electrode ER 03 400US 42 Ignition electrode ER 120 145 05 25186 Flame sensor electrode IS 03 401US 195292 ERP fan 12 01 27003 ERP...

Страница 21: ...lly when the room thermostat calls for heat after about 30 sec 6 If the appliance does not light a check that the burner control does not require resetting An indicator light glows at the inside panel...

Страница 22: ...suffer reddening and itching of the skin Fiber entry into the eyes will cause foreign body irritation Inhalation will cause irritation to the respiratory tract Precautions Wear protective gloves when...

Страница 23: ...tive Complies with the requirements of further directives namely GAD 2009 142 EC EMC 2014 30 EC LVD 2014 35 EC the following harmonized standards have been applied EN 1020 Non domestic gas fired force...

Страница 24: ...mum capacity pl 80 9 77 7 76 2 76 2 77 6 79 0 76 2 77 8 77 7 78 6 79 6 Envelope loss factor Fenv 0 0 0 0 0 0 0 0 0 0 0 Ignition burner power consumption Pign kW 0 02 0 02 0 02 0 02 0 02 0 02 0 02 0 02...

Страница 25: ...A United Kingdom Tel 01384 489 250 Fax 01384 487 707 reznorsales nortek com www reznor co uk Nortek Global HVAC is a registered trademark of the Nortek Global HVAC Limited Because of continuous produc...

Отзывы: