background image

17

The defrost board is equipped with a 5 minute 
Anti-Short Cycle Delay (ASCD). The compressor 
will not turn on until the minimum 5 minute off 
time is reached.

The control contains a forced - defrost feature, 
which puts the system into defrost mode every 6 
ours and 4 minutes, unless the coil temperature 

is above 40

°

 F.

The system can be manually put into a forced 
defrost mode at any time by shorting the “TEST” 
terminals on the demand defrost board together 
for more than 9 seconds. The coil temperature 
sensor does not need to be cold when the unit 
is forced into defrost. After the “TEST” input is 
removed, the defrost mode will terminate in 13.7 
minutes or when the coil temperature is above 
the terminate set-point or when the “Y” input is 
removed, whichever occurs first.

field Installed Electric Heat — These Single 
Package  Heat  Pumps  are  designed  to  allow 
optional  electric  heat  to  be  field  installed  as 
required by the building’s particular heating load. 
The options available for each unit are shown in 
the heater kit installation instructions. As noted 
in the instructions, a field installed circuit breaker 
kit is available as a means of electrical discon-
nect for the unit. 

Install the heater kits as directed by the installation 
instructions that come as part of the heater kit. 
Follow all cautions and warnings as directed.

Optional Outdoor Thermostat  An outdoor 
thermostat  can  be  installed  in  the  field  with 
2-stage  electric  heat.  To  install  the  outdoor 
thermostat,  remove  the  orange  wire  from  the 
“E” terminal on the terminal block, and connect 
to  the  outdoor  thermostat.  Connect  the  other 
side of the outdoor thermostat to W2 from the 
thermostat.

START UP AND SYSTEM CHECK

Pre-Start Check list

•  Verify that the unit is level to allow proper 

condensate drainage.

•  Verify that there is free airflow to and from 

the  outdoor  coil  and  that  all  clearance 
requirements are met.

•  Verify that the duct work is sealed to prevent 

air leakage. 

•  Verify that the line voltage power leads are 

securely connected and the unit is properly 
grounded.

•   Verify that the low voltage wires are securely 

connected to the correct leads on the low 
voltage terminal strip.

•  Verify that all exterior panels are replaced 

and securely fastened.

•  Verify that the outdoor fan turns freely.

•  Verify that the power supply branch circuit 

overcurrent protection is sized properly.

•  Verify that the thermostat is wired correctly. 

The thermostat function switch should be 
set to “Off’ and the thermostat fan switch 
should be set to “Auto.”

Start-Up Procedure

Close all electrical disconnects to energize the 
system.

Air Circulation — Leave the thermostat system 
switch  set  to  “Off”  and  set  the  thermostat  fan 
switch  to  “On.”  The  blower  motor  should  run 
continuously.  Check  for  air  delivery  at  the 
register(s). Ensure that there are no obstructions 
at the registers or in the duct work. Set thermostat 
fan switch to “Auto.”

Short  Cycle  Protection  —  With  the  system 
operating in cooling mode, note the temperature 
setting of the thermostat and gradually raise the 
set-point temperature until the unit de-energizes. 
Immediately lower the set point temperature of 
the thermostat to its original setting and verify 
that the indoor blower is energized. Verify that 
after approximately 5 minutes the compressor 
and  fan  energize  and  that  the  temperature 
of  the  discharge  air  is  cooler  than  the  room 
temperature. This is available only for the single 
phase models.

System Cooling

1.  Set the thermostat system switch to “Cool” 

and  the  thermostat  fan  switch  to  “Auto”. 
Gradually lower the thermostat temperature 
switch  below  room  temperature  and 
observe that the blower, compressor, and 
fan  energize.  Check  that  air  cooler  than 
room  temperature  is  being  discharged 
at  the  register.  Listen  for  any  unusual 
noises.

Содержание Q4SE-X24/PPH1SE

Страница 1: ...oning appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable nation...

Страница 2: ...2...

Страница 3: ...fety Considerations 6 Installation Requirements 6 Dimensions 7 Unit Installation 8 Air Ducts 9 Electrical Wiring 10 11 Optional Humidistat 12 Optional Comfort Alert 13 16 Start Up and System Check 17...

Страница 4: ...e supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat Summer Cooling 1 Indoor air enters the return air duct 2 The cold heat transfer section indoor...

Страница 5: ...ts Defrost Duringcoldweatherheatingoperation the outdoor until will develop a coating of snow and ice on the heat transfer coil This is normal and the unit will periodically defrost itself During the...

Страница 6: ...llunitshavebeensecurelypackaged at the point of shipment After unpacking the unit carefully inspect it for apparent and concealed damage Claims for damage should be filed with the carrier by the consi...

Страница 7: ...Entry Capped 22 25 Control Wiring Entry 23 3 5 27 1 5 30 1 4 5 4 13 5 16 0 13 7 13 5 16 0 12 45 11 75 22 75 55 8 C HORIZONTAl SUPPlY DUCT OPENINg HORIZONTAl RETURN DUCT OPENINg 4 0 CONDENSINg COIl 5 0...

Страница 8: ...requirements UNIT INSTALLATION Ground Level When installing the unit at ground level provide a concrete mounting pad separate from the building foundation The pad must be level to insure proper conden...

Страница 9: ...t weights Reinforce the roof if required Air Ducts This unit is designed only for use with a supply and return duct Air ducts should be installed in accordance with the standards of the National Fire...

Страница 10: ...material of the same gage and temperature rating WARNING To avoid the risk of electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance o...

Страница 11: ...r clogging etc The packaged heat pump unit is configured by setting the selector switches and removing jumper connectors as directed below IMPORTANT This packaged heat pump unit has been designed to g...

Страница 12: ...able 3 Delay profile selection controls the start up and shut down characteristics of the packaged heat pump unit By varying the start up and shut down characteristics of the packaged heat pumpunitthe...

Страница 13: ...signal from the thermostat but no current to the compressor is detected by the module The TRIP LED typically indicates the compressor protector is open or may indicate missing supply power to the comp...

Страница 14: ...Alert LED will flash the previous code 8 for 1 minute and then turn off If the yellow LED does not function as described refer to Figure 9a to verify the wiring Troubleshooting The Installation Depen...

Страница 15: ...for excessively low thermostat setting Check evaporator airflow coil blockages or return air filter Check ductwork or registers for blockage 4 Faulty metering device Check TXV bulb installation size l...

Страница 16: ...ring or connections 6 Unusually long compressor protector reset time due to extreme ambient temperature 7 Compressor windings are damaged Check compressor motor winding resistance Yellow ALERT Flash C...

Страница 17: ...sate drainage Verify that there is free airflow to and from the outdoor coil and that all clearance requirements are met Verifythattheductworkissealedtoprevent air leakage Verify that the line voltage...

Страница 18: ...ionandcharging it should only be done by qualified trained personnel thoroughly familiar withthisequipment Somelocalcodes require licensed installation service personnel to service this type of equipm...

Страница 19: ...Y2 E O Y1 AMBIENT SENSOR COIL SENSOR TEST L R C Y O W2 IN W2 OUT COND FAN AMBIENT AMBG COILG COIL DEMAND DEFROST CONTROL BOARD M PRESS SW REV VALVE Demand Defrost Board Terminal Block Optional Outdoor...

Страница 20: ...n concerning accessory Heat Kits and other options DEFROST BOARD OPERATION Heat Pump operates in heating mode until the combination of outdoor ambient and outdoor coil temperatures initiate a defrost...

Страница 21: ...Heat Kits and other options Heat pump operates in heating mode until the combination of outdoor ambient and outdoor coil temperatures initiate a defrost cycle The outdoor coil temperature must be at...

Страница 22: ...ure F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Q4SE X36 Charging Chart Cooling 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540...

Страница 23: ...95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Q4SE X60 Charging Chart Cooling 240 260 280 300 320 3...

Страница 24: ...s 708626B Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 09 08 708944D INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH...

Отзывы: