background image

18

2.  After  allowing  the  unit  to  run  for  several 

minutes,  set  the  temperature  selector 
above room temperature.

-  The fan and compressor cycles off with 

the thermostat.

-  The blower should also stop unless fan 

switch is set to “ON” position.

System Heating — If the unit has been equipped 
with optional electric heater kits, set the system 
thermostat switch to HEAT and set the thermostat 
fan switch to AUTO. Verify that the compressor 
and outdoor fan are not energized but that the 
blower and heaters are. Check for warm air at 
the supply registers.

UNIT MAINTENANCE

 WARNINg:

To  avoid  risk  of  electrical  shock, 
personal injury, or death, disconnect 
all electrical power to the unit before 
performing  any  maintenance  or 
service. The unit may have more than 
one electrical supply.

Refrigerant  Charging  —  Packaged  heat 
pumps  are  fully  charged  at  the  factory.  The 
system refrigerant charge can be checked and 
adjusted  through  the  service  ports  provided 
at the front panel. Use only gauge lines which 
have  a  “Schrader”  depression  device  present 
to actuate the valve. Draw a vacuum on gauge 
lines to remove air before attaching them to the 
service ports on the unit. Refrigerant charging 
must be done by qualified personnel familiar with 
safe and environmentally responsible refrigerant 
handling procedures.

 WARNINg:

Single  Packaged  Heat  Pumps  are 
shipped  fully  charged  with  R-410A 
refrigerant and ready for installation. 
When a system is installed according 
to  these  instructions,  no  refrigerant 
charging is required. If repairs make it 
necessary for evacuation and charging, 
it  should  only  be  done  by  qualified, 
trained personnel thoroughly familiar 
with this equipment. Some local codes 
require  licensed  installation/service 
personnel  to  service  this  type  of 

equipment.  Under  no  circumstances 
should  the  owner  attempt  to  install 
and/or service this equipment. failure 
to  comply  with  this  warning  could 
result  in  property  damage,  personal 
injury, or death.

 CAUTION:

Use  care  when  removing  parts  from 
this  unit.  Personal  injury  can  result 
from  sharp  metal  edges  present 
in  all  equipment  of  sheet  metal 
construction.

Routine Maintenance — Proper maintenance is 
important to achieve optimum performance from 
the heat pump. The ability to properly perform 
maintenance on this equipment requires certain 
mechanical skills and tools. If you do not possess 
these skills, contact your dealer for maintenance. 
Consult your local dealer about the availability of 
maintenance contracts. At a minimum, routine 
maintenance should include the following:

1.  Inspect and clean or replace air filters at 

the beginning of each heating and cooling 
season, or more frequently if required.

2.  Inspect the condensate drain and outdoor 

coil at the beginning of each cooling season. 
Remove any debris. Clean the outdoor coil 
and  louvers  as  necessary  using  a  mild 
detergent and water. Rinse thoroughly with 
water.

3.  Inspect  the  electrical  connections  for 

tightness  at  the  beginning  of  each 
heating  and  cooling  season.  Service  as 
necessary.

 CAUTION:

The  unit  should  never  be  operated 
without a filter in the return air system. 
Replace  disposable  filters  with  the 
same type and size.

4.  The  motors  for  the  circulating  air  blower 

and the outdoor fan are pre-lubricated at 
the factory. No further oiling is required for 
the life of this product.

Содержание Q4SE-X24/PPH1SE

Страница 1: ...oning appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable nation...

Страница 2: ...2...

Страница 3: ...fety Considerations 6 Installation Requirements 6 Dimensions 7 Unit Installation 8 Air Ducts 9 Electrical Wiring 10 11 Optional Humidistat 12 Optional Comfort Alert 13 16 Start Up and System Check 17...

Страница 4: ...e supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat Summer Cooling 1 Indoor air enters the return air duct 2 The cold heat transfer section indoor...

Страница 5: ...ts Defrost Duringcoldweatherheatingoperation the outdoor until will develop a coating of snow and ice on the heat transfer coil This is normal and the unit will periodically defrost itself During the...

Страница 6: ...llunitshavebeensecurelypackaged at the point of shipment After unpacking the unit carefully inspect it for apparent and concealed damage Claims for damage should be filed with the carrier by the consi...

Страница 7: ...Entry Capped 22 25 Control Wiring Entry 23 3 5 27 1 5 30 1 4 5 4 13 5 16 0 13 7 13 5 16 0 12 45 11 75 22 75 55 8 C HORIZONTAl SUPPlY DUCT OPENINg HORIZONTAl RETURN DUCT OPENINg 4 0 CONDENSINg COIl 5 0...

Страница 8: ...requirements UNIT INSTALLATION Ground Level When installing the unit at ground level provide a concrete mounting pad separate from the building foundation The pad must be level to insure proper conden...

Страница 9: ...t weights Reinforce the roof if required Air Ducts This unit is designed only for use with a supply and return duct Air ducts should be installed in accordance with the standards of the National Fire...

Страница 10: ...material of the same gage and temperature rating WARNING To avoid the risk of electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance o...

Страница 11: ...r clogging etc The packaged heat pump unit is configured by setting the selector switches and removing jumper connectors as directed below IMPORTANT This packaged heat pump unit has been designed to g...

Страница 12: ...able 3 Delay profile selection controls the start up and shut down characteristics of the packaged heat pump unit By varying the start up and shut down characteristics of the packaged heat pumpunitthe...

Страница 13: ...signal from the thermostat but no current to the compressor is detected by the module The TRIP LED typically indicates the compressor protector is open or may indicate missing supply power to the comp...

Страница 14: ...Alert LED will flash the previous code 8 for 1 minute and then turn off If the yellow LED does not function as described refer to Figure 9a to verify the wiring Troubleshooting The Installation Depen...

Страница 15: ...for excessively low thermostat setting Check evaporator airflow coil blockages or return air filter Check ductwork or registers for blockage 4 Faulty metering device Check TXV bulb installation size l...

Страница 16: ...ring or connections 6 Unusually long compressor protector reset time due to extreme ambient temperature 7 Compressor windings are damaged Check compressor motor winding resistance Yellow ALERT Flash C...

Страница 17: ...sate drainage Verify that there is free airflow to and from the outdoor coil and that all clearance requirements are met Verifythattheductworkissealedtoprevent air leakage Verify that the line voltage...

Страница 18: ...ionandcharging it should only be done by qualified trained personnel thoroughly familiar withthisequipment Somelocalcodes require licensed installation service personnel to service this type of equipm...

Страница 19: ...Y2 E O Y1 AMBIENT SENSOR COIL SENSOR TEST L R C Y O W2 IN W2 OUT COND FAN AMBIENT AMBG COILG COIL DEMAND DEFROST CONTROL BOARD M PRESS SW REV VALVE Demand Defrost Board Terminal Block Optional Outdoor...

Страница 20: ...n concerning accessory Heat Kits and other options DEFROST BOARD OPERATION Heat Pump operates in heating mode until the combination of outdoor ambient and outdoor coil temperatures initiate a defrost...

Страница 21: ...Heat Kits and other options Heat pump operates in heating mode until the combination of outdoor ambient and outdoor coil temperatures initiate a defrost cycle The outdoor coil temperature must be at...

Страница 22: ...ure F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Q4SE X36 Charging Chart Cooling 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540...

Страница 23: ...95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Q4SE X60 Charging Chart Cooling 240 260 280 300 320 3...

Страница 24: ...s 708626B Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 09 08 708944D INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH...

Отзывы: