Nortek Q4SE-X24/PPH1SE Скачать руководство пользователя страница 6

6

SAfETY CONSIDERATIONS

It is the responsibility of the installer to ensure 
that the installation is made in accordance with 
all applicable local and national codes.

 WARNINg:

Improper  installation,  ser vice , 
adjustment, or maintenance may cause 
explosion,  fire,  electrical  shock  or 
other hazardous conditions which may 
result  in  personal  injury  or  property 
damage.  Unless  otherwise  noted 
in  these  instructions,  only  factory 
authorized kits or accessories may be 
used with this product. Noncompliance 
may void the unit’s warranty.

labels,  Tags  —  When  working  with  this 
equipment, follow all precautions in the literature, 
on  tags,  and  on  labels  provided  with  the  unit 
and/or  approved  field  installed  kits.  The  type 
of hazard and severity are described on each 
label or tag.

Pressures  Within  The  System  —  This 
equipment  contains  liquid  and  gaseous 
refrigerant  under  high  pressure.  Installation  or 
servicing should only be performed by qualified 
trained  personnel  thoroughly  familiar  with  this 
type equipment.

 CAUTION:

This unit uses refrigerant R-410A. DO 
NOT  under  any  circumstances  use 
any other refrigerant besides R-410A 
in this unit. Use of another refrigerant 
will damage this unit.

INSTAllATION REQUIREMENTS

Equipment  Check  —  Before  beginning  the 
installation, verify that the unit model is correct for 
the job. The unit model number is printed on the 
data label. All units have been securely packaged 
at the point of shipment. After unpacking the unit, 
carefully inspect it for apparent and concealed 
damage. Claims for damage should be filed with 
the carrier by the consignee.

Requirements  and  Codes  —  The  installer 
must comply with all local codes and regulations 
which govern this type equipment. Local codes 
and  regulations  take  precedence  over  any 
recommendations contained in these instructions. 
All electrical wiring must be made in accordance 
with  local  codes  and  regulations  and  with  the 
National  Electric  Code  (ANSI/NFPA  70)  or  in 
Canada the Canadian Electric Code Part 1 CSA 
C.22.1. Air Ducts must be installed in accordance 
with the standards of the National Fire Protection 
Association  “Standards  for  Installation  of  Air 
Conditioning  and  Ventilation  Systems”  (NFPA 
90A),  “Standard  for  Installation  of  Residence 
Type  Warm  Air  Heating  and  Air  Conditioning 
Systems”  (NFPA  90B),  these  instructions  and 
all applicable local codes.

NFPA publications are available by writing:
 
 

National Fire Protection Association

 

1 Batterymarch Park

 

Quincy, Massachusetts 02169-7471

 

www.nfpa.org

Unit location — This heat pump is designed only 
for outdoor installations. Choosing the location of 
the unit should be based on minimizing the length 
of  the  supply  and  return  ducts.  Consideration 
should  also  be  given  to  availability  of  electric 
power,  service  access,  noise,  and  shade. 
Sufficient  clearance  for  unobstructed  airflow 
through the outdoor coil must be maintained in 
order to achieve rated performance See figure 
4
 for minimum clearances to obstructions.

Содержание Q4SE-X24/PPH1SE

Страница 1: ...oning appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable nation...

Страница 2: ...2...

Страница 3: ...fety Considerations 6 Installation Requirements 6 Dimensions 7 Unit Installation 8 Air Ducts 9 Electrical Wiring 10 11 Optional Humidistat 12 Optional Comfort Alert 13 16 Start Up and System Check 17...

Страница 4: ...e supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat Summer Cooling 1 Indoor air enters the return air duct 2 The cold heat transfer section indoor...

Страница 5: ...ts Defrost Duringcoldweatherheatingoperation the outdoor until will develop a coating of snow and ice on the heat transfer coil This is normal and the unit will periodically defrost itself During the...

Страница 6: ...llunitshavebeensecurelypackaged at the point of shipment After unpacking the unit carefully inspect it for apparent and concealed damage Claims for damage should be filed with the carrier by the consi...

Страница 7: ...Entry Capped 22 25 Control Wiring Entry 23 3 5 27 1 5 30 1 4 5 4 13 5 16 0 13 7 13 5 16 0 12 45 11 75 22 75 55 8 C HORIZONTAl SUPPlY DUCT OPENINg HORIZONTAl RETURN DUCT OPENINg 4 0 CONDENSINg COIl 5 0...

Страница 8: ...requirements UNIT INSTALLATION Ground Level When installing the unit at ground level provide a concrete mounting pad separate from the building foundation The pad must be level to insure proper conden...

Страница 9: ...t weights Reinforce the roof if required Air Ducts This unit is designed only for use with a supply and return duct Air ducts should be installed in accordance with the standards of the National Fire...

Страница 10: ...material of the same gage and temperature rating WARNING To avoid the risk of electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance o...

Страница 11: ...r clogging etc The packaged heat pump unit is configured by setting the selector switches and removing jumper connectors as directed below IMPORTANT This packaged heat pump unit has been designed to g...

Страница 12: ...able 3 Delay profile selection controls the start up and shut down characteristics of the packaged heat pump unit By varying the start up and shut down characteristics of the packaged heat pumpunitthe...

Страница 13: ...signal from the thermostat but no current to the compressor is detected by the module The TRIP LED typically indicates the compressor protector is open or may indicate missing supply power to the comp...

Страница 14: ...Alert LED will flash the previous code 8 for 1 minute and then turn off If the yellow LED does not function as described refer to Figure 9a to verify the wiring Troubleshooting The Installation Depen...

Страница 15: ...for excessively low thermostat setting Check evaporator airflow coil blockages or return air filter Check ductwork or registers for blockage 4 Faulty metering device Check TXV bulb installation size l...

Страница 16: ...ring or connections 6 Unusually long compressor protector reset time due to extreme ambient temperature 7 Compressor windings are damaged Check compressor motor winding resistance Yellow ALERT Flash C...

Страница 17: ...sate drainage Verify that there is free airflow to and from the outdoor coil and that all clearance requirements are met Verifythattheductworkissealedtoprevent air leakage Verify that the line voltage...

Страница 18: ...ionandcharging it should only be done by qualified trained personnel thoroughly familiar withthisequipment Somelocalcodes require licensed installation service personnel to service this type of equipm...

Страница 19: ...Y2 E O Y1 AMBIENT SENSOR COIL SENSOR TEST L R C Y O W2 IN W2 OUT COND FAN AMBIENT AMBG COILG COIL DEMAND DEFROST CONTROL BOARD M PRESS SW REV VALVE Demand Defrost Board Terminal Block Optional Outdoor...

Страница 20: ...n concerning accessory Heat Kits and other options DEFROST BOARD OPERATION Heat Pump operates in heating mode until the combination of outdoor ambient and outdoor coil temperatures initiate a defrost...

Страница 21: ...Heat Kits and other options Heat pump operates in heating mode until the combination of outdoor ambient and outdoor coil temperatures initiate a defrost cycle The outdoor coil temperature must be at...

Страница 22: ...ure F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Q4SE X36 Charging Chart Cooling 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540...

Страница 23: ...95 100 105 110 115 120 125 130 135 Liquid Temperature F Liquid Pressure psig Add refrigerant when below curve Remove refrigerant when above curve Q4SE X60 Charging Chart Cooling 240 260 280 300 320 3...

Страница 24: ...s 708626B Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 09 08 708944D INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH...

Отзывы: