background image

5

HEAt PuMP InStAllAtIon

unpacking the unit

It is recommended that the unit be unpacked at the 

installation site to minimize damage due to handling.

 cAutIon:

Do not tip the unit on its side. oil may enter the 

compressor cylinders and cause starting trouble. 

If unit has been set on its side, restore to upright 

position and do not run for several hours. then 

run unit for a few seconds. Do this three or four 

times with five minutes between runs.

1. Remove the bands from around the unit.

2. Unfold the top and bottom cap flanges.

3. Carefully remove the top cap and tube.

Installing Return & Supply Air collars

If the supply and return collars are supplied with the unit, 

they will be located in the supply duct. They can be easily 

positioned over the unit openings and secured with sheet 
metal screws. See 

Figure 2

.

•  The  diameter  of  the  return  duct  collar  is  14”. 

 

notE:

 2 ton units are designed with 12” returns.

•  The diameter of the supply duct collar is 12”.

•  Before  permanently  installing  the  collars,  it  is 

recommended you pre-fit them over the openings first 

to determine best fit and alignment.

Minimum clearances

Minimum clearances MUST be maintained from adjacent 

structures to provide room for proper servicing and air 

circulation. DO NOT install unit in a confined or recessed 

area that will allow discharge air from the unit to re-circulate 
into the condenser air inlet, through the coil. See 

Figure 1

.

Service Access Clearance:

Blower access panel side .......................................... 24”
Electrical compartment access panel side ............... 12”

Clearance between overhang and top
of unit  .................................................................. 72”
Clearance around condenser coil area to
wall or shrubs (excludes duct panel side) .................. 12”

Clearances to Combustibles:

Combustible base - wood or Class A, B, or C
roof covering material ................................................. 0”
Supply & return air ducts ............................................ 0”
Duct connection side .................................................. 0”

Air Duct System

Air ducts should be installed in accordance with the 

standards of the National Fire Protection Association 

“Standard for Installation of Air Conditioning and Ventilation 

Systems” (NFPA 90A), “Standard for Installation of 

Residence Type Warm Air Heating and Air Conditioning 

Systems” (NFPA 90B), these instructions, and all applicable 

codes. NFPA publications are available by writing to: 

National Fire Protection Association, Batterymarch Park, 

Quincy, ME 02269 or visit www.NFPA.org on the web.

•  Design the duct work according to methods described 

by the Air Conditioning Contractors of America (ACCA).

•  The supply duct system, including the number and type of 

registers, will have much more effect on the performance 

of the system than any other factor. The duct must be 

sufficiently large to conduct an adequate amount of air 
to each register. See 

Figure 3 (page 6)

.

•  Duct work should be attached directly to the unit flanges 

for horizontal applications.

•  For highly resistive duct systems it may be necessary 

to add an additional return air duct and or supply to 

achieve maximum performance and prevent coil icing 

and refrigerant flood back.

• 

the heat pump system will not cool or heat the home 

if air is lost to the outside through leaks in the duct 

system. Ducts that are collapsed or restricted by 

foreign objects will also prevent adequate air flow.

• 

All duct work passing through unconditioned space 
must be properly insulated to minimize duct losses 
and prevent condensation. Use insulation with an outer 
vapor barrier. Refer to local codes for insulation material 
requirements.

Unconditioned Spaces

All duct work passing through unconditioned space must 

be properly insulated to minimize duct losses and prevent 

condensation. Use insulation with an outer vapor barrier. 

Refer to local codes for insulation material requirements.

Figure 2. Return & Supply Air collars

Transition

Duct Screws

Supply Air

Return Air

Duct

Dimples

the heat pump system will not cool or heat the home 

if air is lost to the outside through leaks in the duct 

system. Ducts that are collapsed or restricted by 

foreign objects will also prevent adequate air flow.

Содержание PPH3RE Series

Страница 1: ...lays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings coul...

Страница 2: ...ing 11 Short Cycle Protection 11 Emergency Heat 11 Anti Short Cycle Timer Test 11 Heating Mode 11 Cooling Mode 11 Unit MAINTENANCE 11 Adjustment of Refrigerant Charge 12 Charging the Unit in AC Mode 1...

Страница 3: ...ancer Disturbing the insulation of this product during installation maintenance or repair will expose you to fiberglass wool Breathing this material may cause respiratory irritations or may cause lung...

Страница 4: ...practical place the heat pump and its ducts in an area where they will be shaded from the afternoon sun when the heat load is greatest Consideration should also be given to availability of electric po...

Страница 5: ...tandards of the National Fire Protection Association StandardforInstallationofAirConditioningandVentilation Systems NFPA 90A Standard for Installation of Residence Type Warm Air Heating and Air Condit...

Страница 6: ...re tight Homes with multiple supply ducts or special applications a Y fitting is available for dividing the supplyairtodifferentareasofthehomeformoreefficient cooling NOTE Formaximumperformance insula...

Страница 7: ...ocation 2 Cut a hole approximately 3 4 larger than the damper opening in the fiberboard 3 Cut a 9 1 8 x 13 1 8 hole in the duct and bend over all tabs flat on the inside of the heat duct 4 Insert the...

Страница 8: ...nside the control compartment Extend leads through power wiring hole See Figure 7 Connect L1 L2 directly to the contactor Use only copper wire for the line voltage power supply to this unit as listed...

Страница 9: ...tinuously even through loss of power for 7 days Electric Heat Package optional This heat pump is shipped without an auxiliary electric heat kit installed If electric heat is desired an accessory heate...

Страница 10: ...1630 1589 1545 048K T1 1418 1385 1351 1316 1279 1242 1203 1163 T2 1530 1500 1467 1433 1396 1358 1318 1275 T3 1679 1645 1611 1576 1541 1505 1469 1432 T4 1787 1757 1726 1693 1658 1621 1582 1542 T5 2006...

Страница 11: ...for the discharge of warm air at the supply registers System Cooling Set the thermostat s system mode to COOL and the fan mode to AUTO Change the thermostat temperature selector below the existing roo...

Страница 12: ...ernal to the unit The switch is designed to de energize the system when very high pressures occur during abnormal conditions Under normal conditions the switch is closed If the discharge pressure rise...

Страница 13: ...63 35 38 2 35 02 2 48 Figure 8 Physical Data Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View L W TopView 18 01...

Страница 14: ...75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 133 249 131 135 250 134...

Страница 15: ...R TEMPERATURE F 70 75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 135 26...

Страница 16: ...e suction pressure will vary from design value if outdoor air flow entering dry bulb or entering wet bulb temperatures vary NOTES 1 All pressures are listed psig and all temperatures in F 2 Discharge...

Страница 17: ...63 124 69 283 130 84 307 145 105 352 166 126 396 188 43 231 109 52 249 116 61 268 122 70 287 128 85 314 142 106 359 162 127 403 182 44 238 107 53 255 114 62 273 120 71 290 126 86 321 139 107 366 157 1...

Страница 18: ...115 47 242 123 58 268 132 69 294 141 84 324 158 104 374 183 124 424 208 38 223 113 48 248 121 59 273 130 70 298 139 85 331 155 105 381 178 125 431 201 39 230 111 49 254 119 60 278 128 71 301 137 86 3...

Страница 19: ...N BLACK RED BLUE BLACK BLACK BLACK ORANGE RED YELLOW WHITE YELLOW GREEN WITH YELLOW STRIPE VIOLET WHITE 208 230 VOLT Z H 0 6 E S A H P E L G N I S P M U P T A E H D E G A K C A P L L A M S WIRING DIAG...

Страница 20: ...LUE RED RED WHITE BLACK GREEN GREY ORANGE WHITE YELLOW BLACK BLACK BLACK BROWN BLACK RED BLUE BLACK YELLOW BLACK ORANGE RED YELLOW WHITE WHITE 208 230 VOLT SMALL PACKAGED HEAT PUMP SINGLE PHASE 60HZ W...

Страница 21: ...N BLUE RED RED WHITE BLACK GREEN GREY ORANGE WHITE YELLOW BLACK BLACK BLACK BROWN BLACK RED BLUE YELLOW ORANGE WITH YELLOW STRIPE 208 230 VOLT SMALL PACKAGED HEAT PUMP SINGLE PHASE 60HZ WIRING DIAGRAM...

Страница 22: ...ostat is used W2 OUT W2 IN Optional 2nd Stage Outdoor Thermostat Field Supplied 6 7 8 9 2 3 4 5 1 C G O W2 Y1 Y2 E R INDOOR TERMINAL THERMOSTAT White wire not present when optional thermostat is used...

Страница 23: ...23...

Страница 24: ...TY________________________ STATE_________________ Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO VENTING SYSTEM Is the ven...

Отзывы: