background image

4

gEnERAl InFoRMAtIon

Single packaged heat pumps are ready for easy and 

immediate installation and can be readily connected 

into the high static duct system of a home. This unit is 

completely assembled, wired, and run tested at the factory. 

this heat pump is designed for outdoor installation 

only. 

The only connections needed for installation are the 

supply and return ducts, the line voltage, and thermostat 

wiring. Use of components other than those specified may 

invalidate AHRI Certification, Code Agency Listing, and 

limited warranty on the air conditioner.

before You Install this unit

 The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. 

It is recommended that the area to be conditioned be 

completely insulated and vapor sealed.

  Check the electrical supply and verify the power supply 

is adequate for unit operation. If there is any question 

concerning the power supply, contact the local power 

company.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage 

prior to installing the equipment at the job site. Verify 

coil fins are straight. If necessary, comb fins to remove 

flattened or bent fins. Claims for damage should be filed 

immediately with the carrier.

  Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read 
all instructions before installing the unit.

locating the Heat Pump

•  Survey the job site to determine the best location for 

mounting the outdoor unit. Select a solid, level position, 

preferably on a concrete slab, slightly above the grade 

level, and parallel to the home. If possible, select a site 

for the unit that is as close as possible to the proposed 

return grille location. 

Do not PlAcE unIt unDER 

tHE HoME.

•  The  unit  should  be  located  with  consideration  of 

minimizing the length of the supply and return ducts 

with no sharp radius bends. If practical, place the heat 

pump and its ducts in an area where they will be shaded 

from the afternoon sun, when the heat load is greatest.

•  Consideration  should  also  be  given  to  availability  of 

electric power, service access, noise, and shade.

•  Overhead  obstructions,  poorly  ventilated  areas,  and 

areas subject to accumulation of debris should be 

avoided. The hot condenser air must be discharged up 

and away from the home, and if possible, in a direction 

with the prevailing wind. Do not place the unit in a confined 
space. See 

Figure 8 (page 13)

 for unit dimensions.

•  Sufficient clearance for unobstructed airflow through the 

outdoor coil must be maintained in order to achieve rated 

performance. For minimum clearances to obstructions, 
see 

Figure 1

.

REQuIREMEntS & coDES

•  All electrical wiring must be completed in accordance 

with local, state & national codes and regulations and 

with the National Electric Code (ANSI/NFPA 70) or in 

Canada the Canadian Electric Code Part 1 CSA C.22.1.

•  The  installer  must  comply  with  all  local  codes  and 

regulations which govern the installation of this type 

of equipment. Local codes and regulations take 

precedence over any recommendations contained in 

these instructions. Consult local building codes and the 

National Electrical Code (ANSI CI) for special installation 

requirements.

•  Air  Ducts  must  be  installed  in  accordance  with  the 

standards of the National Fire Protection Association 

“Standards for Installation of Air Conditioning and 

Ventilation Systems” (NFPA 90A), “Standard for 

Installation of Residence Type Warm Air Heating and Air 

Conditioning Systems” (NFPA 90B), these instructions, 

and all applicable local codes.

•  Consult 

Table 2 (page 10)

, and the rating plate for 

the proper circulating air flow and temperature rise. It is 

important that the duct system be designed to provide 

the correct flow rates and external pressure rise. An 

improperly designed duct system can result in nuisance 

shutdowns, and comfort or noise issues.

•  This unit is designed for outdoor installations only and 

should be positioned as described in Locating the Heat 

Pump.

12"

12"

24"

TOP OF UNIT

TO

 BE

UNOBSTR

UCTED

0"

Figure 1. Minimum unit clearances

Содержание PPH3RE Series

Страница 1: ...lays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings coul...

Страница 2: ...ing 11 Short Cycle Protection 11 Emergency Heat 11 Anti Short Cycle Timer Test 11 Heating Mode 11 Cooling Mode 11 Unit MAINTENANCE 11 Adjustment of Refrigerant Charge 12 Charging the Unit in AC Mode 1...

Страница 3: ...ancer Disturbing the insulation of this product during installation maintenance or repair will expose you to fiberglass wool Breathing this material may cause respiratory irritations or may cause lung...

Страница 4: ...practical place the heat pump and its ducts in an area where they will be shaded from the afternoon sun when the heat load is greatest Consideration should also be given to availability of electric po...

Страница 5: ...tandards of the National Fire Protection Association StandardforInstallationofAirConditioningandVentilation Systems NFPA 90A Standard for Installation of Residence Type Warm Air Heating and Air Condit...

Страница 6: ...re tight Homes with multiple supply ducts or special applications a Y fitting is available for dividing the supplyairtodifferentareasofthehomeformoreefficient cooling NOTE Formaximumperformance insula...

Страница 7: ...ocation 2 Cut a hole approximately 3 4 larger than the damper opening in the fiberboard 3 Cut a 9 1 8 x 13 1 8 hole in the duct and bend over all tabs flat on the inside of the heat duct 4 Insert the...

Страница 8: ...nside the control compartment Extend leads through power wiring hole See Figure 7 Connect L1 L2 directly to the contactor Use only copper wire for the line voltage power supply to this unit as listed...

Страница 9: ...tinuously even through loss of power for 7 days Electric Heat Package optional This heat pump is shipped without an auxiliary electric heat kit installed If electric heat is desired an accessory heate...

Страница 10: ...1630 1589 1545 048K T1 1418 1385 1351 1316 1279 1242 1203 1163 T2 1530 1500 1467 1433 1396 1358 1318 1275 T3 1679 1645 1611 1576 1541 1505 1469 1432 T4 1787 1757 1726 1693 1658 1621 1582 1542 T5 2006...

Страница 11: ...for the discharge of warm air at the supply registers System Cooling Set the thermostat s system mode to COOL and the fan mode to AUTO Change the thermostat temperature selector below the existing roo...

Страница 12: ...ernal to the unit The switch is designed to de energize the system when very high pressures occur during abnormal conditions Under normal conditions the switch is closed If the discharge pressure rise...

Страница 13: ...63 35 38 2 35 02 2 48 Figure 8 Physical Data Unit Dimensions A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View L W TopView 18 01...

Страница 14: ...75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 133 249 131 135 250 134...

Страница 15: ...R TEMPERATURE F 70 75 80 85 90 95 100 105 Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp Liq Press Dis Temp 135 26...

Страница 16: ...e suction pressure will vary from design value if outdoor air flow entering dry bulb or entering wet bulb temperatures vary NOTES 1 All pressures are listed psig and all temperatures in F 2 Discharge...

Страница 17: ...63 124 69 283 130 84 307 145 105 352 166 126 396 188 43 231 109 52 249 116 61 268 122 70 287 128 85 314 142 106 359 162 127 403 182 44 238 107 53 255 114 62 273 120 71 290 126 86 321 139 107 366 157 1...

Страница 18: ...115 47 242 123 58 268 132 69 294 141 84 324 158 104 374 183 124 424 208 38 223 113 48 248 121 59 273 130 70 298 139 85 331 155 105 381 178 125 431 201 39 230 111 49 254 119 60 278 128 71 301 137 86 3...

Страница 19: ...N BLACK RED BLUE BLACK BLACK BLACK ORANGE RED YELLOW WHITE YELLOW GREEN WITH YELLOW STRIPE VIOLET WHITE 208 230 VOLT Z H 0 6 E S A H P E L G N I S P M U P T A E H D E G A K C A P L L A M S WIRING DIAG...

Страница 20: ...LUE RED RED WHITE BLACK GREEN GREY ORANGE WHITE YELLOW BLACK BLACK BLACK BROWN BLACK RED BLUE BLACK YELLOW BLACK ORANGE RED YELLOW WHITE WHITE 208 230 VOLT SMALL PACKAGED HEAT PUMP SINGLE PHASE 60HZ W...

Страница 21: ...N BLUE RED RED WHITE BLACK GREEN GREY ORANGE WHITE YELLOW BLACK BLACK BLACK BROWN BLACK RED BLUE YELLOW ORANGE WITH YELLOW STRIPE 208 230 VOLT SMALL PACKAGED HEAT PUMP SINGLE PHASE 60HZ WIRING DIAGRAM...

Страница 22: ...ostat is used W2 OUT W2 IN Optional 2nd Stage Outdoor Thermostat Field Supplied 6 7 8 9 2 3 4 5 1 C G O W2 Y1 Y2 E R INDOOR TERMINAL THERMOSTAT White wire not present when optional thermostat is used...

Страница 23: ...23...

Страница 24: ...TY________________________ STATE_________________ Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO VENTING SYSTEM Is the ven...

Отзывы: