Nortek PPG3HE Series Скачать руководство пользователя страница 5

5

gEnERAl inFoRMAtion

This Single Package Gas Heating / Electric Cooling 

Unit is designed for outdoor rooftop or ground level 

slab installations and can be readily connected to the 

duct system of a home or building. This unit has been 

tested for capacity and efficiency in accordance with 

AHRI standards and will provide many years of safe and 

dependable comfort, providing it is properly installed 

and maintained. With regular maintenance, this unit will 

operate satisfactorily year after year. Abuse, improper 

use, and/or improper maintenance can shorten the life 

of the appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment 

failure, it is recommended that periodic maintenance be 

performed on this unit. The ability to properly perform 

maintenance on this equipment requires certain tools 

and mechanical skills.

before you install this unit

 The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. 

It is recommended that the area to be conditioned be 

completely insulated and vapor sealed.

  Check the electrical supply and verify the power supply 

is adequate for unit operation. Consideration should be 

given to availability of electric power, service access, 

noise, and shade. If there is any question concerning 

the power supply, contact the local power company.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage 

prior to installing the equipment at the job site. Verify 

coil fins are straight. If necessary, comb fins to remove 

flattened or bent fins. Claims for damage (apparent or 

concealed) should be filed immediately with the carrier.

 Survey the job site to determine the best location for 

setting the unit. Choose an appropriate location that 

minimizes the length of the supply and return air ducts.

  Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read 
all instructions before installing the unit.

Locating the Equipment

•  Select a solid, level position, preferably on a concrete 

slab, slightly above the grade level, and parallel to the 

home. 

DO NOT PLACE UNIT UNDER ThE hOME.

•  Overhead  obstructions,  poorly  ventilated  areas,  and 

areas subject to accumulation of debris should be 

avoided. Do not place the unit in a confined space or 

recessed area where discharge air from the unit to re-

circulate into the condenser air inlet, through the coil.

•  Sufficient clearance for unobstructed airflow through the 

louvered control access panel and outdoor coil must 

be maintained in order to achieve rated performance. 
See 

Figure 1

 for minimum clearances to obstructions.

•  A  clearance  of  at  least  36  inches  from  the  blower 

access panel and from the louvered control access 

panel is recommended for servicing and maintenance. 

Where  accessibility  clearances  are  greater  than 

minimum clearances to combustibles, accessibility 

clearances must take preference.

•  The hot condenser air must be discharged up and away 

from the home, and if possible, in a direction with the 

prevailing wind.

•  If practical, place the air conditioner and its ducts in an 

area where they will be shaded from the afternoon sun, 

when the heat load is greatest.

heating Load

This unit should be sized to provide the design heating 

load requirement. Heating load estimates can be made 

using approved methods available from Air Conditioning 

Contractors of America (Manual J); American Society of 

Heating, Refrigerating, and Air Conditioning Engineers; 

or other approved engineering methods. For installations 

above 2,000 ft., the unit should have a sea level input 

rating large enough that it will meet the heating load after 

deration for altitude.

COMbUSTION AIR & vENTINg 

REQUiREMEntS

 WARning:

Installation methods other than those described 

in the following sections must comply with the 

National Fuel gas Code and all applicable local 

codes  for  providing  sufficient  combustion  air 

to the unit.

•  Provisions  must  be  made  during  the  installation  of 

this unit that provide an adequate supply of air for 

combustion.

•  Instructions  for  determining  the  adequacy  of  an 

installation can be found in the current revision of the 

NFGC (ANSI Z223.1 / NFPA54). 

Consult local codes 

for special requirements

. These requirements are for 

US installations as found in the NFGC.

•  The requirements in Canada (B149.1) are structured 

differently. Consult with B149.1 and local code officials 

for Canadian installations.

Minimum Required 

Clearances to Combustibles

36"

36"

36"

See Note 1

See Note 2

NOTE 1:

 6” When coil is present on duct side.

NOTE 2:

 1” When no coil is present on duct side.

Figure 1. Clearance Requirements

Содержание PPG3HE Series

Страница 1: ...RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit pourrait entra ner des blessures graves la mort ou des dommages mat riels L installation et l entretien doivent tre effec...

Страница 2: ...Stage Operation 23 De Humidification Control 23 Fan Mode 23 COMPONENT FUNCTIONS 23 equipment MAINTENANCE 24 Heat Exchanger Burner Maintenance 24 Cleaning of Burners 25 REPLACEMENT PARTS 25 Troublesho...

Страница 3: ...ion maintenance or repair may expose you to fiberglass insulation Breathing this material may cause respiratory irritations Fiberglass insulation may also cause eye irritation skin sensitization or ot...

Страница 4: ...e 28 Table 10 page 29 Table 11 page 30 Table 12 page 31 Table 13 page 32 and the rating plate for the proper circulating air flow and temperature rise It is important that the duct system be designed...

Страница 5: ...reas and areas subject to accumulation of debris should be avoided Do not place the unit in a confined space or recessed area where discharge air from the unit to re circulate into the condenser air i...

Страница 6: ...outdoors No additional venting shall be used Do not vent the unit through a conventional venting system The vent and drain assembly must be installed to assure proper operation of the unit Figure 2 sh...

Страница 7: ...the unit for ventilation or to improve indoor air quality the system must be designed so that the return air to the unit is not less than 50 F 10 C during heating operation If a combination of indoor...

Страница 8: ...ved duct sealing methods to ensure an air and watertight seal is achieved Rooftop Rooftop installations must be located according to local building codes or ordinances and these requirements The roof...

Страница 9: ...filter sizes refer to Table 1 page 10 Allreturnairmustpassthroughthefiltersbeforeentering the evaporator coil It is important that all filters be kept cleanandreplacedfrequentlytoensureproperoperatio...

Страница 10: ...imate Filter Area Sq In 30 20 2 14 x25 700 1300 700 24 1 12 x20 and 1 16 x25 640 34 20 2 16 x25 900 1400 800 24 1 12 x20 and 2 10 x25 740 38 20 2 18 x25 1100 1600 900 24 1 12 x20 and 2 12 x25 840 42 2...

Страница 11: ...g requirements Verify factory wiring is in accordance with the unit wiring diagram Figure 13 page 37 Figure 14 page 38 Figure 15 page 39 Make sure the connections didn t loosen during shipping or inst...

Страница 12: ...cal thermostat connection The control circuit wiring must comply with the current provisions of the NEC ANSI NFPA 70 and with applicable local codes having jurisdiction Thermostat connections should b...

Страница 13: ...icing continues raise the selected airflow to the next higher tap For maximum dehumidification and energy efficiency select an airflow near the middle or bottom of the CFM range for that nominal capa...

Страница 14: ...all for dehumidification If a humidistat is not available it is an acceptable option to directly jumper the R DEHUM on the blower control board NOTE This option will always operate the blower at 75 th...

Страница 15: ...ground joint union external to the unit The shut off valve should be readily accessible for service and or emergency use Consult the local utility or gas supplier for additional requirements regarding...

Страница 16: ...theinputrate must be reduced 4 per 1 000 feet of altitude Example 12 at 3 000 feet 16 at 4 000 feet etc Deration is necessary to compensate for low atmospheric pressure at high altitudes LP Propane Ga...

Страница 17: ...Gas Orifice Size Rise Range oF Max Outlet Air Temp Maximum External Static Pressure E S P in WC Net Cooling Capacity BTUH Blower Size Motor HP X24K060 X XA 10 0 4 5 3 5 60 000 57 000 39 000 37 050 45...

Страница 18: ...han 12 hrs Failure to comply may result in damage or cause premature failure of the system Air Circulation Leave the thermostat system mode on OFF and set the fan mode to ON Blower should run continuo...

Страница 19: ...ide must be shielded against direct radiation from the heat exchanger to avoid false readings 2 Adjust all registers and duct dampers to the desired position Run the unit for 10 to 15 minutes before t...

Страница 20: ...manifold pressure Compare the measured value with the value shown in Table 3 page 17 for Natural Gas and Table 4 page 17 for LP Propane gas Ifthemanifold pressureisnotsettotheappropriate pressure the...

Страница 21: ...de to AUTO Gradually lower the thermostat temperaturesetpointbelowroomtemperatureandverify the compressor fan and indoor blower energize 2 Feel the air being circulated by the indoor blower and verify...

Страница 22: ...on High speed for the first 15 seconds of any heating cycle After this 15 second period the control switches the gas valve to Low fire and inducer to Low speed if no second stage W2 demand is present...

Страница 23: ...e low voltage field connection board and connect the other side to the DEHUM terminal on the blower control board Wire the humidistat to close on rise in humidity For dehumidification the DEHUM input...

Страница 24: ...potentially hazardousconditionsincludingcarbonmonoxide poisoning that could result in personal injury or death Maintain heat exchanger and burners The furnace should operate for many years without exc...

Страница 25: ...ower Assembly Fan Grille Burner Manifold Filter Driers Burners Orifices Gaskets Cabinet Panels Heat Exchanger Expansion Valves Table 5 Furnace Control Board Fault Conditions Diagnostic Description Gre...

Страница 26: ...DUCT OPENING HORIZONTAL RETURN DUCT OPENING 4 0 1 75 9 75 24 75 CONDENSING COIL C 30 89 13 5 16 0 13 5 16 0 4 0 4 0 13 5 16 0 13 5 55 8 12 45 9 75 24 75 1 75 8 75 12 45 17 50 C 16 0 HORIZONTAL SUPPLY...

Страница 27: ...34 26 0 27 0 35 31 3 55 8 47 5 R8HE X48C096X 455 482 27 5 26 5 43 39 3 55 8 47 5 R8HE X48D096X 472 499 27 0 27 0 43 39 3 55 8 47 5 R8HE X60C096X 485 510 28 0 26 5 47 43 3 55 8 47 5 R8HE X60D096X 502 5...

Страница 28: ...Rise CFM Rise 1 2 3 4 CFM Rise CFM Rise 0 0 0 0 600 57 800 66 0 0 0 0 885 55 1180 64 1 0 0 0 656 52 875 60 1 0 0 0 938 52 1250 61 0 1 0 0 694 49 925 57 0 1 0 0 990 49 1320 58 1 1 0 0 750 46 1000 53 1...

Страница 29: ...0 60 0 70 0 80 0 90 1 00 1 2 3 4 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise 0 0 0 0 783 67 740 71 696 76 645 82 594 89 554 95 514 103 472 112 429 123 1 0 0 0 851...

Страница 30: ...0 1 00 1 2 3 4 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise 0 0 0 0 1218 58 1175 60 1132 62 1097 64 1062 66 1024 69 986 71 950 74 914 77 1 0 0 0 1270 55 1230 57 119...

Страница 31: ...0 30 0 40 0 50 0 60 0 70 0 80 0 90 1 00 1 2 3 4 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise 0 0 0 0 1308 55 1252 57 1196 60 1139 63 1082 66 1025 70 967 74 915 78...

Страница 32: ...80 0 90 1 00 1 2 3 4 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise 0 0 0 0 1308 67 1252 70 1196 74 1139 77 1082 81 1025 86 967 91 915 96 863 102 1 0 0 0 1363 65 1309...

Страница 33: ...IC FEET PER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692...

Страница 34: ...ir la compagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais uti...

Страница 35: ...mum Circuit Ampacity Maximum Over current Protection RLA Min Max RLA LRA R8HE X36C080X High 80 000 0 30 208 230 3 60 187 253 11 6 73 1 5 7 0 23 0 30 Low 52 000 R8HE X36D080X High 80 000 0 30 460 3 60...

Страница 36: ...WER OFF DELAY THERMOSTAT CONNECTIONS NEUTRALS FLAME 3 AMP FUSE INPUTS ON Figure 12 Ignition Control Board 624817 Figure 10 Two Stage Heating Single Stage Cooling Configuration TERMINAL STRIP THERMOSTA...

Страница 37: ...Fault On Flash Communications Fault Flash Flash Blower Control Diagnostic Description Green LED Red LED 711318C Replaces 711318B 11 14 Y2 E O Y1 2 W 1 W 1 A C G R COM 230 24V 208 IGNITOR FLAME SENSOR...

Страница 38: ...n remove wire from 230V tap and place on 208V tap SEE NOTE 6 711383A Replaces 7113830 11 14 Y2 E O Y1 G C A1 W1 W2 R COM 230 24V 208 IGNITOR FLAME SENSOR 2 STAGE GAS VALVE HIGH TEMP LIMIT FLAME ROLL O...

Страница 39: ...7113840 11 14 460V 230V COM FUSE Y2 E O Y1 2 W 1 W 1 A C G R COM 230 24V 208 IGNITOR FLAME SENSOR 2 STAGE GAS VALVE HIGH TEMP LIMIT FLAME ROLL OUT LIMIT INDUCER LIMIT HIGH PRESSURE SWITCH 11 4 1 8 7...

Страница 40: ...move refrigerant when above curve Add refrigerant when below curve Figure 16 Charging Chart for 2 Ton Units 260 280 300 320 340 360 380 400 420 440 460 480 500 80 85 90 95 100 105 110 115 120 Liquid T...

Страница 41: ...ant when below curve Remove refrigerant when above curve 220 240 Figure 18 Charging Chart for 3 Ton Units 280 300 320 340 360 380 400 420 440 460 480 500 80 85 90 95 100 105 110 115 120 Liquid Tempera...

Страница 42: ...t when above curve Add refrigerant when below curve Figure 20 Charging Chart for 4 Ton Units 260 280 300 320 340 360 380 400 420 440 460 480 500 90 95 100 105 110 115 120 125 130 Liquid Temperature F...

Страница 43: ...43 1 Inch Filter Installations 2 Inch Filter Installations Figure 22 Filter Comversion Internal Filter Conversion...

Страница 44: ...t on standard 2 concrete pad NOTE For a trench style drain installation page 3 you will also need 4 x36 min corrugated flexible pipe w drain holes a 2 x4 PVC reducer 4 corrugated piping connection 2 x...

Страница 45: ...f the limestone rock chat or lime pellets if required by code with the initial rock base 2 Measure the distance between the top of the rock base and bottom of drain fitting 3 Cut the field supplied 2...

Страница 46: ...onnection at bottom of 2 PVC Tee and secure with spring hose clamp 8 Install flexible insulation over the entire length of drain tube and cut away any excess then secure at the top with wire tie provi...

Страница 47: ...E VENT AND DRAIN SYSTEM Figure 23 Condensate Disposal Using A Vertical Drainage Pit 30 36 OR GREATER 3 3 2 4 4 PIPE DRAIN BACK FILL ROCK ROCK BASE SEE NOTE GRADE LEVEL 2 PAD GRADE LEVEL NOTE SLOPE 1 1...

Страница 48: ...of curb and 1 2 in from the long side of curb See Figure 25 If drilling a hole is not an option routing the condensate drainhoseovertotheductpassageopeningwithenough slope is acceptable as long as dra...

Страница 49: ...position of the condensate drain valve be changed from the horizontal H to downflow D position The condensate drain valve is located in the bottom left corner of the heat exchanger collector box to t...

Страница 50: ...Degree Elbow 1 4 Mesh Screen 1 2 ID x 84 Drain Hose Flexible Insulation Optional Condensate Drain Valve D Position for Downflow Applications Only To building drain per State and Local Codes J Trap Hei...

Страница 51: ...51...

Страница 52: ...VOLTS 3 Phase Units Rated Voltage VOLTS L1 L2 Volts VOLTS L1 L3 Volts VOLTS L2 L3 Volts VOLTS Avg Volts VOLTS Max deviation of voltage from avg volts VOLTS Volt Imbalance VOLTS VENTING SYSTEM Is the h...

Отзывы: