Nortek PPG3HE Series Скачать руководство пользователя страница 22

22

not close within 12 seconds, the control will display a 

Pressure Switch Open with Inducer On Fault.  If the hall 

effect sensor switch does not close before 60 seconds 

expires, the control will de-energize the inducer for 5 

minutes and continue to display a Pressure Switch Open 

with Inducer On Fault during the 5 minute inducer off 

period. After the inducer has been off for 5 minutes, the 

control energizes the inducer motor and restarts the 60 

second pressure switch proving period.

5. Pre-Purge - If the hall effect sensor switch closes the 

control runs the inducer on high speed for a 30 second 

pre-purge time while monitoring the thermostat call for 

heat, limit switch circuit, vent pressure switch, and flame 

sense.

6. Igniter Warm Up - When the 30 second pre-purge time 

has elapsed, the control begins the Hot Surface Ignition 

(HSI) warm-up as follows:

 

Initial Power up:

 After 30 seconds of igniter warm-up, the 

gas valve will open. The igniter circuit will stay energized 

for 3 seconds after the gas valve opens.

 

After Initial Power up:

 The control has a programmed 

adaptive ignition feature which varies the warm-up 

period as follows: If ignition is successful the warm-up 

is reduced by 3 seconds on each subsequent call for 

heat until ignition failure occurs. Upon ignition failure, 

the warm -up is increased by 3 seconds on the next try. 

If successful, the timing remains fixed at this level. In 

general, whenever ignition failure occurs the warm-up 

interval is increased by 3 seconds on the next try.

  If successful, it remains there. Minimum and maximum 

warm-up time limits are set at 9 and 54 seconds.

7. Flame Proving / Ignition / Low Heat Operation - The 

furnace control must prove flame via the flame sensor 

5 seconds after the high main gas valve is energized. 

• If flame is sensed, burners are on and the igniter cools 

off. The Yellow LED will be lit.

• If no flame is sensed, the gas valve closes immediately 

and the inducer continues to run on high. A second 

trial for ignition (step 6) begins. If no flame is sensed 

on the fifth try for ignition, the furnace control is locked 

and the control will display 1 Hour Lockout Fault. The 

thermostat must be opened for at least 10 seconds to 

reset the furnace control after a lock out. Otherwise, 

the furnace will attempt another ignition sequence 

in 1 hour.

 

Low Fire Heat (Stage 1):

 If flame is present at the end 

of the trial for ignition time, the control leaves High main 

gas valve energized and inducer motor on High speed 

for the first 15 seconds, and begins the heat blower 

22 second on delay. Control inputs are continuously 

monitored while the call for heat remains. The control 

will always energize the gas valve on High fire with the 

inducer on High speed for the first 15 seconds of any 

heating cycle. After this 15 second period, the control 

switches the gas valve to Low fire and inducer to Low 

speed if no second stage (

W2

) demand is present.

8. Blower Start-Up - After flame is proven, the furnace 

control energizes the circulating air blower after 22 

seconds. The blower will then ramp up to the airflow 

selected for heating.

9. High Heat Staging (with 2 Stage Heat Thermostat) - Unit 

will always start in High heat operation. See step 7 for 

start up sequence. After the initial 15 second start up 

sequence is satisfied, the control will move to Low heat 

and wait for a 

W2

 call from a 2-stage thermostat. After a 

second stage heat demand is present (

W2

 energized), 

the gas valve will open to High heat mode increasing 

the flow of gas to the burners while the inducer and 

blower motor ramp to high speed.

  Single Stage Heat Thermostat with Automatic Heat 

Staging - Automatic heat staging allows the unit to 

operate as a two stage gas furnace with the use of a 

single stage heating thermostat. With the ignition control 

AUTO HEAT STAGE jumper repositioned from the OFF 
position to the ON position, see 

Figure 12 (page 36)

the gas furnace will automatically switch to High heat 

mode of operation after a 10 minute delay. The induced 

draft motor and blower motor will both ramp to high 

speed.

10. When the thermostat has been satisfied, gas valve is 

de-energized.

11.  The inducer motor is de-energized after a 30 second 

post purge.

12. The circulating air blower will remain energized for 

approximately 120 seconds (factory setting) after the 

demand for heat is no longer present.

13. Abnormal Conditions - If a limit switch opens during 

heating operation the gas valve is de-energized 

immediately. The control de-energizes the induced draft 

motor and runs the indoor blower motor continuously 

while the limit switch is open.

  NOTE:  This  unit  has  two  special  features 

programmed  into  the  furnace  control  board  for 

safety and proper unit operation.

Thaw Cycle Start Up / Shutdown

The vent pressure switch is constantly monitored 

throughout the ignition cycle. If after 1 minute of burner 

ignition the vent pressure switch remains open, the 

control will de-energize the gas valve, energize the main 

blower, and begin another ignition sequence after a 30 

second inter-purge. If after 5 cycles the pressure switch 

fails to close the unit will lockout for a period of one hour.

 

The blower stays energized for the selected blower off 

delay period. This feature only activates if the unit is off 

for extended periods of time between heating cycles in 

extremely cold weather which could  lead to ice formation 

over the vent pressure tap or the switch itself is faulty.  

Any ice formation will clear after one or two trials.  One 

hour lockout period can be terminated by shutting off the 

thermostat for 5-10 seconds or main power to unit for 

1-2 seconds.

Содержание PPG3HE Series

Страница 1: ...RISQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de s curit pourrait entra ner des blessures graves la mort ou des dommages mat riels L installation et l entretien doivent tre effec...

Страница 2: ...Stage Operation 23 De Humidification Control 23 Fan Mode 23 COMPONENT FUNCTIONS 23 equipment MAINTENANCE 24 Heat Exchanger Burner Maintenance 24 Cleaning of Burners 25 REPLACEMENT PARTS 25 Troublesho...

Страница 3: ...ion maintenance or repair may expose you to fiberglass insulation Breathing this material may cause respiratory irritations Fiberglass insulation may also cause eye irritation skin sensitization or ot...

Страница 4: ...e 28 Table 10 page 29 Table 11 page 30 Table 12 page 31 Table 13 page 32 and the rating plate for the proper circulating air flow and temperature rise It is important that the duct system be designed...

Страница 5: ...reas and areas subject to accumulation of debris should be avoided Do not place the unit in a confined space or recessed area where discharge air from the unit to re circulate into the condenser air i...

Страница 6: ...outdoors No additional venting shall be used Do not vent the unit through a conventional venting system The vent and drain assembly must be installed to assure proper operation of the unit Figure 2 sh...

Страница 7: ...the unit for ventilation or to improve indoor air quality the system must be designed so that the return air to the unit is not less than 50 F 10 C during heating operation If a combination of indoor...

Страница 8: ...ved duct sealing methods to ensure an air and watertight seal is achieved Rooftop Rooftop installations must be located according to local building codes or ordinances and these requirements The roof...

Страница 9: ...filter sizes refer to Table 1 page 10 Allreturnairmustpassthroughthefiltersbeforeentering the evaporator coil It is important that all filters be kept cleanandreplacedfrequentlytoensureproperoperatio...

Страница 10: ...imate Filter Area Sq In 30 20 2 14 x25 700 1300 700 24 1 12 x20 and 1 16 x25 640 34 20 2 16 x25 900 1400 800 24 1 12 x20 and 2 10 x25 740 38 20 2 18 x25 1100 1600 900 24 1 12 x20 and 2 12 x25 840 42 2...

Страница 11: ...g requirements Verify factory wiring is in accordance with the unit wiring diagram Figure 13 page 37 Figure 14 page 38 Figure 15 page 39 Make sure the connections didn t loosen during shipping or inst...

Страница 12: ...cal thermostat connection The control circuit wiring must comply with the current provisions of the NEC ANSI NFPA 70 and with applicable local codes having jurisdiction Thermostat connections should b...

Страница 13: ...icing continues raise the selected airflow to the next higher tap For maximum dehumidification and energy efficiency select an airflow near the middle or bottom of the CFM range for that nominal capa...

Страница 14: ...all for dehumidification If a humidistat is not available it is an acceptable option to directly jumper the R DEHUM on the blower control board NOTE This option will always operate the blower at 75 th...

Страница 15: ...ground joint union external to the unit The shut off valve should be readily accessible for service and or emergency use Consult the local utility or gas supplier for additional requirements regarding...

Страница 16: ...theinputrate must be reduced 4 per 1 000 feet of altitude Example 12 at 3 000 feet 16 at 4 000 feet etc Deration is necessary to compensate for low atmospheric pressure at high altitudes LP Propane Ga...

Страница 17: ...Gas Orifice Size Rise Range oF Max Outlet Air Temp Maximum External Static Pressure E S P in WC Net Cooling Capacity BTUH Blower Size Motor HP X24K060 X XA 10 0 4 5 3 5 60 000 57 000 39 000 37 050 45...

Страница 18: ...han 12 hrs Failure to comply may result in damage or cause premature failure of the system Air Circulation Leave the thermostat system mode on OFF and set the fan mode to ON Blower should run continuo...

Страница 19: ...ide must be shielded against direct radiation from the heat exchanger to avoid false readings 2 Adjust all registers and duct dampers to the desired position Run the unit for 10 to 15 minutes before t...

Страница 20: ...manifold pressure Compare the measured value with the value shown in Table 3 page 17 for Natural Gas and Table 4 page 17 for LP Propane gas Ifthemanifold pressureisnotsettotheappropriate pressure the...

Страница 21: ...de to AUTO Gradually lower the thermostat temperaturesetpointbelowroomtemperatureandverify the compressor fan and indoor blower energize 2 Feel the air being circulated by the indoor blower and verify...

Страница 22: ...on High speed for the first 15 seconds of any heating cycle After this 15 second period the control switches the gas valve to Low fire and inducer to Low speed if no second stage W2 demand is present...

Страница 23: ...e low voltage field connection board and connect the other side to the DEHUM terminal on the blower control board Wire the humidistat to close on rise in humidity For dehumidification the DEHUM input...

Страница 24: ...potentially hazardousconditionsincludingcarbonmonoxide poisoning that could result in personal injury or death Maintain heat exchanger and burners The furnace should operate for many years without exc...

Страница 25: ...ower Assembly Fan Grille Burner Manifold Filter Driers Burners Orifices Gaskets Cabinet Panels Heat Exchanger Expansion Valves Table 5 Furnace Control Board Fault Conditions Diagnostic Description Gre...

Страница 26: ...DUCT OPENING HORIZONTAL RETURN DUCT OPENING 4 0 1 75 9 75 24 75 CONDENSING COIL C 30 89 13 5 16 0 13 5 16 0 4 0 4 0 13 5 16 0 13 5 55 8 12 45 9 75 24 75 1 75 8 75 12 45 17 50 C 16 0 HORIZONTAL SUPPLY...

Страница 27: ...34 26 0 27 0 35 31 3 55 8 47 5 R8HE X48C096X 455 482 27 5 26 5 43 39 3 55 8 47 5 R8HE X48D096X 472 499 27 0 27 0 43 39 3 55 8 47 5 R8HE X60C096X 485 510 28 0 26 5 47 43 3 55 8 47 5 R8HE X60D096X 502 5...

Страница 28: ...Rise CFM Rise 1 2 3 4 CFM Rise CFM Rise 0 0 0 0 600 57 800 66 0 0 0 0 885 55 1180 64 1 0 0 0 656 52 875 60 1 0 0 0 938 52 1250 61 0 1 0 0 694 49 925 57 0 1 0 0 990 49 1320 58 1 1 0 0 750 46 1000 53 1...

Страница 29: ...0 60 0 70 0 80 0 90 1 00 1 2 3 4 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise 0 0 0 0 783 67 740 71 696 76 645 82 594 89 554 95 514 103 472 112 429 123 1 0 0 0 851...

Страница 30: ...0 1 00 1 2 3 4 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise 0 0 0 0 1218 58 1175 60 1132 62 1097 64 1062 66 1024 69 986 71 950 74 914 77 1 0 0 0 1270 55 1230 57 119...

Страница 31: ...0 30 0 40 0 50 0 60 0 70 0 80 0 90 1 00 1 2 3 4 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise 0 0 0 0 1308 55 1252 57 1196 60 1139 63 1082 66 1025 70 967 74 915 78...

Страница 32: ...80 0 90 1 00 1 2 3 4 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise 0 0 0 0 1308 67 1252 70 1196 74 1139 77 1082 81 1025 86 967 91 915 96 863 102 1 0 0 0 1363 65 1309...

Страница 33: ...IC FEET PER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692...

Страница 34: ...ir la compagnie du gaz en utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Ne jamais uti...

Страница 35: ...mum Circuit Ampacity Maximum Over current Protection RLA Min Max RLA LRA R8HE X36C080X High 80 000 0 30 208 230 3 60 187 253 11 6 73 1 5 7 0 23 0 30 Low 52 000 R8HE X36D080X High 80 000 0 30 460 3 60...

Страница 36: ...WER OFF DELAY THERMOSTAT CONNECTIONS NEUTRALS FLAME 3 AMP FUSE INPUTS ON Figure 12 Ignition Control Board 624817 Figure 10 Two Stage Heating Single Stage Cooling Configuration TERMINAL STRIP THERMOSTA...

Страница 37: ...Fault On Flash Communications Fault Flash Flash Blower Control Diagnostic Description Green LED Red LED 711318C Replaces 711318B 11 14 Y2 E O Y1 2 W 1 W 1 A C G R COM 230 24V 208 IGNITOR FLAME SENSOR...

Страница 38: ...n remove wire from 230V tap and place on 208V tap SEE NOTE 6 711383A Replaces 7113830 11 14 Y2 E O Y1 G C A1 W1 W2 R COM 230 24V 208 IGNITOR FLAME SENSOR 2 STAGE GAS VALVE HIGH TEMP LIMIT FLAME ROLL O...

Страница 39: ...7113840 11 14 460V 230V COM FUSE Y2 E O Y1 2 W 1 W 1 A C G R COM 230 24V 208 IGNITOR FLAME SENSOR 2 STAGE GAS VALVE HIGH TEMP LIMIT FLAME ROLL OUT LIMIT INDUCER LIMIT HIGH PRESSURE SWITCH 11 4 1 8 7...

Страница 40: ...move refrigerant when above curve Add refrigerant when below curve Figure 16 Charging Chart for 2 Ton Units 260 280 300 320 340 360 380 400 420 440 460 480 500 80 85 90 95 100 105 110 115 120 Liquid T...

Страница 41: ...ant when below curve Remove refrigerant when above curve 220 240 Figure 18 Charging Chart for 3 Ton Units 280 300 320 340 360 380 400 420 440 460 480 500 80 85 90 95 100 105 110 115 120 Liquid Tempera...

Страница 42: ...t when above curve Add refrigerant when below curve Figure 20 Charging Chart for 4 Ton Units 260 280 300 320 340 360 380 400 420 440 460 480 500 90 95 100 105 110 115 120 125 130 Liquid Temperature F...

Страница 43: ...43 1 Inch Filter Installations 2 Inch Filter Installations Figure 22 Filter Comversion Internal Filter Conversion...

Страница 44: ...t on standard 2 concrete pad NOTE For a trench style drain installation page 3 you will also need 4 x36 min corrugated flexible pipe w drain holes a 2 x4 PVC reducer 4 corrugated piping connection 2 x...

Страница 45: ...f the limestone rock chat or lime pellets if required by code with the initial rock base 2 Measure the distance between the top of the rock base and bottom of drain fitting 3 Cut the field supplied 2...

Страница 46: ...onnection at bottom of 2 PVC Tee and secure with spring hose clamp 8 Install flexible insulation over the entire length of drain tube and cut away any excess then secure at the top with wire tie provi...

Страница 47: ...E VENT AND DRAIN SYSTEM Figure 23 Condensate Disposal Using A Vertical Drainage Pit 30 36 OR GREATER 3 3 2 4 4 PIPE DRAIN BACK FILL ROCK ROCK BASE SEE NOTE GRADE LEVEL 2 PAD GRADE LEVEL NOTE SLOPE 1 1...

Страница 48: ...of curb and 1 2 in from the long side of curb See Figure 25 If drilling a hole is not an option routing the condensate drainhoseovertotheductpassageopeningwithenough slope is acceptable as long as dra...

Страница 49: ...position of the condensate drain valve be changed from the horizontal H to downflow D position The condensate drain valve is located in the bottom left corner of the heat exchanger collector box to t...

Страница 50: ...Degree Elbow 1 4 Mesh Screen 1 2 ID x 84 Drain Hose Flexible Insulation Optional Condensate Drain Valve D Position for Downflow Applications Only To building drain per State and Local Codes J Trap Hei...

Страница 51: ...51...

Страница 52: ...VOLTS 3 Phase Units Rated Voltage VOLTS L1 L2 Volts VOLTS L1 L3 Volts VOLTS L2 L3 Volts VOLTS Avg Volts VOLTS Max deviation of voltage from avg volts VOLTS Volt Imbalance VOLTS VENTING SYSTEM Is the h...

Отзывы: