background image

2

Important Safety Information ....................................3

General Information ...................................................4

Before You Install this Unit .........................................4
Locating the Air Conditioner  .....................................4
Minimum Clearance Requirements  ..........................4

Service Access Clearances  ..................................4
Clearances to Combustible Materials  ...................4

Air Duct System ........................................................4

Air Conditioner Installation .......................................5

Unpacking the Unit  ...................................................5
Installing Return & Supply Collars .............................5

Supply Duct  ...........................................................5
Return Duct  ...........................................................6

Locating & Installing the Return Air Assembly

 ..........

6

Connecting the Return & Supply Air Flexible
Ducts .........................................................................6
Locating & Installing the Supply Dampers.................6
Condensate Drainage  ..............................................7

Electrical Connections ...............................................7

Pre - Electrical Checklist ...........................................7
Line Voltage ...............................................................7
Grounding..................................................................8
Overcurrent Protection ..............................................8
Thermostat / Low Voltage Connections .....................8

Cooling Thermostat ................................................8
Heat / Cool Thermostat ..........................................8

Blower Speed - ECM Motor .....................................10

Startup & Adjustments ............................................10

Pre - Start Checklist ................................................10
Start - Up Procedure ...............................................10

System Cooling ....................................................10
System Heating ....................................................10

Charging the Unit in AC Mode w/ Outdoor
Temperatures above 55° F ......................................10
Safety Switches .......................................................11

Air Conditioner Maintenance ...................................11
Figures & Tables .......................................................12

Figure 9 - Phys. Data & Unit Dimensions .............12

Wiring Diagrams ......................................................13

Figure 10 - W.D. for 2 & 2.5 Ton Units ..................13
Figure 11 - W.D. for 3 Ton Units ............................14
Figure 12 - W.D. for 3.5, 4, & 5 Ton Units .............15

Refrigerant Charging Tables ....................................16

Table 4 - Charging Table for 2 Ton Units ...............16
Table 5 - Charging Table for 2.5 Ton Units ............16
Table 6 - Charging Table for 3 Ton Units ...............17
Table 7 - Charging Table for 3.5 Ton Units ............17
Table 8 - Charging Table for 4 Ton Units ...............17
Table 9 - Charging Table for 5 Ton Units ...............18

Replacement Parts ...................................................20
Installation / Performance Checklist .......................20

TAbLE OF CONTENTS

Содержание P7RD-A Series

Страница 1: ...d using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follo...

Страница 2: ...ons 8 Cooling Thermostat 8 Heat Cool Thermostat 8 Blower Speed ECM Motor 10 Startup Adjustments 10 Pre Start Checklist 10 Start Up Procedure 10 System Cooling 10 System Heating 10 Charging the Unit in...

Страница 3: ...nt will damage the unit WARNING The information listed below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these i...

Страница 4: ...practical place the air conditioner and its ducts in an area where they will be shaded from the afternoon sun when the heat load is greatest The length of the supply and return ducts should be kept to...

Страница 5: ...st fit Supply Duct 1 Position the supply duct collar so the edge of the unit opening fits between the flange and the bead 2 Overlap the collar ends keeping the small screw holes underneath 3 Align the...

Страница 6: ...o cut a hole for the collar on the return air box or for the insulated duct 3 Set the box into the opening and fasten with screws or nails 4 Install the filter and return air grille in the air box Con...

Страница 7: ...to the unit An electrical disconnect must be located within sight of and readily accessible to the unit This switch shall be capable of electrically de energizing the unit Line voltage to the unit sho...

Страница 8: ...e unit Thermostat Low Voltage Connections The unit is designed to operate from a 24 VAC Class II control circuit The control circuit wiring must comply with the current provisions of the NEC ANSI NFPA...

Страница 9: ...1160 27 1125 28 1090 29 036KA Tap T1 905 35 865 37 810 39 755 42 695 45 645 49 590 54 555 57 Tap T2 1130 28 1090 29 1050 30 1000 32 950 33 895 35 835 38 790 40 Tap T3 1265 25 1225 26 1190 27 1145 28 1...

Страница 10: ...Fandthetemperaturemode to its highest setting 2 Turn power on at the disconnect switch 3 Set the system mode to ON or COOL 4 Set the temperature mode below room temperature Verify that the indoor blow...

Страница 11: ...dditionaloiltomotorsunequipped with oil tubes The compressor is hermetically sealed at the factory and does not require lubrication If the pressure measured in step 1 is greater than the required liqu...

Страница 12: ...49 35 30 2 35 02 2 48 14 12 060KA 49 35 34 2 35 02 2 48 14 12 L W Top View 18 01 1 75 Electric Heater Power Supply 1 13 Power Supply 88 Low Voltage Supply Control Access Panel Blower Access Panel H 17...

Страница 13: ...r le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRIN...

Страница 14: ...de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged...

Страница 15: ...ien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner...

Страница 16: ...4 342 146 138 285 143 304 146 323 149 344 150 365 152 140 307 150 327 152 346 154 367 156 387 158 142 330 156 349 158 369 160 389 162 410 164 144 334 160 353 162 372 164 391 166 412 168 146 356 166 37...

Страница 17: ...s Temp Liq Press Dis Temp 123 257 140 125 259 145 282 142 127 261 151 284 147 307 145 129 267 148 286 152 309 150 332 147 131 271 151 292 152 311 154 334 152 357 150 133 295 155 316 156 336 157 359 15...

Страница 18: ...4 140 128 273 146 296 146 320 145 130 277 148 299 151 322 150 346 150 132 281 151 302 153 324 155 348 154 371 155 134 306 156 328 158 350 159 373 159 397 159 136 331 161 353 163 375 163 399 164 422 16...

Страница 19: ...19...

Страница 20: ...TRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity correct YES NO Rated Voltage VOLTS L1 L2 Volts VOLTS Hasthethermostatbeencalibrated YES NO Is the thermostat level YES NO Istheh...

Отзывы: