background image

10

blower Speed - ECM Motor

 WARNING:

To prevent electric shock, personal injury, 
or death, turn off the electric power at the 
disconnect or the main service panel before 
making any electrical connections.

For optimum system performance and comfort, it may be 
necessary to change the factory speed setting.

1. Disconnect all electrical power to the unit and remove 

the service panel.

2. Locate the orange and red wires terminated to the blower 

motor. 

NOTE: 

The orange wire controls cooling operation 

and the red wire controls the heating operation.

3. Verify the required speed from the airflow data found 

in Table 3 (page 9). Place appropriate wire on the 
appropriate motor speed tap for the required airflow.

4. Check all factory wiring as shown in the wiring diagram 

and inspect the connections to make sure none of them 
loosened during shipping or installation.

START UP & ADJUSTMENTS

Pre-Start Checklist

The following check list should be observed prior to 
starting the unit.

  Verify the unit is level and allows proper condensate 

drainage.

  Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/
control panels are in place. Unit must be installed with 
the proper clearances shown in Figure 1 (page 4).

  Verify that the duct work is sealed to prevent air leakage.

  Verify that the line voltage power leads are securely 

connected and the unit is properly grounded. Check 
the condenser fan to make sure it turns freely.

  Verify the thermostat is wired correctly and installed 

in a proper location. Make sure the low voltage wires 
are securely connected to the correct leads on the low 
voltage terminal strip.

  Verify that the power supply branch circuit overcurrent 

protection is sized properly.

  To achieve rated capacity and efficiency the compressor 

must be exposed to refrigerant for at least 24 hours 
prior to running. After unit startup, the compressor must 
run for a minimum of 12 hours.

Start-Up Procedure
NOTE:

 The control circuit thermostat may consist of an 

anti-short cycle timer that will not let the compressor re-
start before 3 - 5 minutes have elapsed.
1. Set the system mode to OFF and the temperature mode 

to its highest setting.

2. Turn power on at the disconnect switch.
3. Set the system mode to ON or COOL.

4. Set the temperature mode below room temperature. 

Verify that the indoor blower, outdoor fan, and 
compressor energize and the cooling function starts.

5. Verify the discharge air grilles are adjusted and the 

system air is balanced.

6. Verify the duct work has no air leaks.
7. Verify the condensate drain is installed correctly and 

functions properly.

8. Set the temperature mode above room temperature. 

The unit should stop.

9. Instruct the homeowner on unit and thermostat operation 

and filter servicing.

System Cooling
Set the thermostat’s system mode to COOL and the fan 
mode to AUTO. Lower the thermostat temperature selector 
below the existing room temperature. Allow the cooling 
system to operate for several minutes and check for the 
discharge of cool air at the supply registers.

System Heating
(Available only when Electric heat is supplied) Set the 
thermostat’s system mode to HEAT and the fan mode to 
either AUTO (intermittent air) or to ON (continuous air). 
Raise the thermostat’s temperature selector above the 
existing room temperature and check the following:
1. The compressor and outdoor fan should not run.
2. The blower will run according to the thermostat’s fan 

mode setting.

Charging the Unit in AC Mode with Outdoor 
Temperatures Above 55° F

 CAUTION:

This air conditioner contains liquid and gaseous 
refrigerant under pressure. Adjustment of 
refrigerant charge should only be attempted 
by qualified, trained personnel thoroughly 
familiar with the equipment and safe responsible 
refrigerant handling procedures. Under no 
circumstances should the homeowner attempt 
to install and/or service this equipment. Failure 
to comply with this warning could result in 
equipment damage, personal injury, or death.

NOTE:

 The refrigerant charge can be checked and adjusted 

through the service ports provided external to the unit. Use 
only gage line sets which have a “Schrader” depression 
device present to actuate the valve.
1.  With the system operating at steady-state, measure the 

liquid refrigerant pressure in psig at the service valve.

2. Measure the liquid refrigerant temperature (° F) at the 

service valve.

3. For the temperature measured, determine the required 

liquid refrigerant pressure from Tables 4 - 9 (pages 16 
- 18).

Содержание P7RD-A Series

Страница 1: ...d using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follo...

Страница 2: ...ons 8 Cooling Thermostat 8 Heat Cool Thermostat 8 Blower Speed ECM Motor 10 Startup Adjustments 10 Pre Start Checklist 10 Start Up Procedure 10 System Cooling 10 System Heating 10 Charging the Unit in...

Страница 3: ...nt will damage the unit WARNING The information listed below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these i...

Страница 4: ...practical place the air conditioner and its ducts in an area where they will be shaded from the afternoon sun when the heat load is greatest The length of the supply and return ducts should be kept to...

Страница 5: ...st fit Supply Duct 1 Position the supply duct collar so the edge of the unit opening fits between the flange and the bead 2 Overlap the collar ends keeping the small screw holes underneath 3 Align the...

Страница 6: ...o cut a hole for the collar on the return air box or for the insulated duct 3 Set the box into the opening and fasten with screws or nails 4 Install the filter and return air grille in the air box Con...

Страница 7: ...to the unit An electrical disconnect must be located within sight of and readily accessible to the unit This switch shall be capable of electrically de energizing the unit Line voltage to the unit sho...

Страница 8: ...e unit Thermostat Low Voltage Connections The unit is designed to operate from a 24 VAC Class II control circuit The control circuit wiring must comply with the current provisions of the NEC ANSI NFPA...

Страница 9: ...1160 27 1125 28 1090 29 036KA Tap T1 905 35 865 37 810 39 755 42 695 45 645 49 590 54 555 57 Tap T2 1130 28 1090 29 1050 30 1000 32 950 33 895 35 835 38 790 40 Tap T3 1265 25 1225 26 1190 27 1145 28 1...

Страница 10: ...Fandthetemperaturemode to its highest setting 2 Turn power on at the disconnect switch 3 Set the system mode to ON or COOL 4 Set the temperature mode below room temperature Verify that the indoor blow...

Страница 11: ...dditionaloiltomotorsunequipped with oil tubes The compressor is hermetically sealed at the factory and does not require lubrication If the pressure measured in step 1 is greater than the required liqu...

Страница 12: ...49 35 30 2 35 02 2 48 14 12 060KA 49 35 34 2 35 02 2 48 14 12 L W Top View 18 01 1 75 Electric Heater Power Supply 1 13 Power Supply 88 Low Voltage Supply Control Access Panel Blower Access Panel H 17...

Страница 13: ...r le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRIN...

Страница 14: ...de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged...

Страница 15: ...ien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner...

Страница 16: ...4 342 146 138 285 143 304 146 323 149 344 150 365 152 140 307 150 327 152 346 154 367 156 387 158 142 330 156 349 158 369 160 389 162 410 164 144 334 160 353 162 372 164 391 166 412 168 146 356 166 37...

Страница 17: ...s Temp Liq Press Dis Temp 123 257 140 125 259 145 282 142 127 261 151 284 147 307 145 129 267 148 286 152 309 150 332 147 131 271 151 292 152 311 154 334 152 357 150 133 295 155 316 156 336 157 359 15...

Страница 18: ...4 140 128 273 146 296 146 320 145 130 277 148 299 151 322 150 346 150 132 281 151 302 153 324 155 348 154 371 155 134 306 156 328 158 350 159 373 159 397 159 136 331 161 353 163 375 163 399 164 422 16...

Страница 19: ...19...

Страница 20: ...TRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity correct YES NO Rated Voltage VOLTS L1 L2 Volts VOLTS Hasthethermostatbeencalibrated YES NO Is the thermostat level YES NO Istheh...

Отзывы: