background image

8

power wiring hole (Figure 7, page 7). Connect L1 & L2 
directly to the contactor.

•  The unit requires both power and control circuit electrical 

connections. Refer to the wiring diagram / schematic 
(Figures 10 - 12, pages 13 - 15) for identification and 
location of unit field wiring interfaces. Make all electrical 
connections in accordance with all applicable codes 
and ordinances.

•  Overcurrent protection must be provided at the branch 

circuit distribution panel and sized as shown on the unit 
rating label and according to applicable local codes. 
See the unit rating plate for minimum circuit ampacity 
and maximum overcurrent protection limits.

•  Use only copper wire for the line voltage power supply 

to this unit as listed in Table 1. Use proper code agency 
listed conduit and a conduit connector for connecting 
the supply wires to the unit. Use of rain tight conduit is 
recommended.

•  208/230 Volt units are shipped from the factory wired 

for 230 volt operation. For 208V operation, remove the 
lead from the transformer terminal marked 240V and 
connect it to the terminal marked 208V.

•  Optional equipment requiring connection to the power 

or control circuits must be wired in strict accordance of 
the NEC (ANSI/NFPA 70), applicable local codes, and 
the instructions provided with the equipment.

Grounding

 WARNING:

The unit cabinet must have an uninterrupted or 
unbroken electrical ground to minimize personal 
injury if an electrical fault should occur. Do not 
use gas piping as an electrical ground!

This unit must be electrically grounded in accordance 
with local codes or, in the absence of local codes, with the 

National Electrical Code (ANSI/NFPA 70) or CSA C22.1 
Electrical Code. Ground the air conditioning unit using 
the green grounding screw provided in the control panel.

Overcurrent Protection

Generally, the best fuse or breaker for any air conditioner 
is the smallest size that will permit the equipment to run 
under normal usage and provide maximum equipment 
protection. Properly sized fuses and breakers also prevent 
nuisance trips during unit startup. 

If a fuse blows or a 

breaker trips, always determine the reason. Do not 
arbitrarily install a larger fuse or breaker and do not, 
in any case, exceed the maximum size listed on the 
data label of the unit.

Thermostat / Low Voltage Connections

•  The unit is designed to operate from a 24 VAC Class 

II control circuit. The control circuit wiring must comply 
with the current provisions of the NEC (ANSI/NFPA 
70) and with applicable local codes having jurisdiction. 
Thermostat connections should be made in accordance 
with the instructions supplied with the thermostat and 
the indoor equipment.

•  The low voltage wires must be properly connected. Route 

24V control wires through the sealing grommet (Figure 
7, page 7) near the power entrance. Recommended 
wire gauge and wire lengths for typical thermostat 
connections are listed in Table 2 (page 9).

•  Single  stage  or  two-stage  heating  thermostats  can 

be used with this equipment depending on optional 
accessories installed with the unit. Select a thermostat 
that operates in conjunction with the installed 
accessories.

•  The thermostat should be mounted about 5 feet above 

the floor on an inside wall. DO NOT install the thermostat 
on an outside wall or any other location where its 
operation may be adversely affected by radiant heat 
from fireplaces, sunlight, lighting fixtures or convective 
heat from warm air registers or electrical appliances. 
Refer to the thermostat manufacturer’s instruction sheet 
for detailed mounting information.

Cooling Only Thermostat
Connect the 

red

 & 

yellow

 wires from the unit to the 

R

 

Y

 terminals on the thermostat subbase. Connect the 

green

 wire to the 

yellow

 wire at the unit. See Figure 8.

Heat / Cool Thermostat
For the highest efficiency, the use of a 2-stage Heating/
Cooling thermostat is recommended. The heat/cool 
thermostat prevents simultaneous operation of the heating 
and cooling units and is equipped with an ON-AUTO fan 
mode that allows the home owner to operate the indoor 
blower when only air circulation is desired.
Connect the red, yellow, green and brown/orange low 
voltage wires to the 

R

 or 

RC

Y

G,

 

or 

W2 

(if applicable) 

terminals on the thermostat base. The black wire is the 24 
volt common required on some thermostats. See Figure 8.

Figure 8. Low Voltage Connections

RED

R

YELLOW

Y

GREEN

G

BROWN

*

W1

ORANGE

RED

R

YELLOW

Y

GREEN

G

BROWN

*

W

ORANGE

4 WIRE HEAT/COOL THERMOSTAT

Two Stage Heating T-Stat

Single Stage Electric Heat

RED

R

YELLOW

Y

GREEN

2 WIRE COOLING

(ONLY) THERMOSTAT

CONTROL WIRE LEGEND:

GREEN - Blower Relay
RED - Transformer (24V)
YELLOW - Cooling 1st Stage
BROWN - Heating 1st Stage
ORANGE - Heating 2nd Stage

*

W2

*Connected when Optional Electric Heating Kit is Installed.

Содержание P7RD-A Series

Страница 1: ...d using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follo...

Страница 2: ...ons 8 Cooling Thermostat 8 Heat Cool Thermostat 8 Blower Speed ECM Motor 10 Startup Adjustments 10 Pre Start Checklist 10 Start Up Procedure 10 System Cooling 10 System Heating 10 Charging the Unit in...

Страница 3: ...nt will damage the unit WARNING The information listed below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these i...

Страница 4: ...practical place the air conditioner and its ducts in an area where they will be shaded from the afternoon sun when the heat load is greatest The length of the supply and return ducts should be kept to...

Страница 5: ...st fit Supply Duct 1 Position the supply duct collar so the edge of the unit opening fits between the flange and the bead 2 Overlap the collar ends keeping the small screw holes underneath 3 Align the...

Страница 6: ...o cut a hole for the collar on the return air box or for the insulated duct 3 Set the box into the opening and fasten with screws or nails 4 Install the filter and return air grille in the air box Con...

Страница 7: ...to the unit An electrical disconnect must be located within sight of and readily accessible to the unit This switch shall be capable of electrically de energizing the unit Line voltage to the unit sho...

Страница 8: ...e unit Thermostat Low Voltage Connections The unit is designed to operate from a 24 VAC Class II control circuit The control circuit wiring must comply with the current provisions of the NEC ANSI NFPA...

Страница 9: ...1160 27 1125 28 1090 29 036KA Tap T1 905 35 865 37 810 39 755 42 695 45 645 49 590 54 555 57 Tap T2 1130 28 1090 29 1050 30 1000 32 950 33 895 35 835 38 790 40 Tap T3 1265 25 1225 26 1190 27 1145 28 1...

Страница 10: ...Fandthetemperaturemode to its highest setting 2 Turn power on at the disconnect switch 3 Set the system mode to ON or COOL 4 Set the temperature mode below room temperature Verify that the indoor blow...

Страница 11: ...dditionaloiltomotorsunequipped with oil tubes The compressor is hermetically sealed at the factory and does not require lubrication If the pressure measured in step 1 is greater than the required liqu...

Страница 12: ...49 35 30 2 35 02 2 48 14 12 060KA 49 35 34 2 35 02 2 48 14 12 L W Top View 18 01 1 75 Electric Heater Power Supply 1 13 Power Supply 88 Low Voltage Supply Control Access Panel Blower Access Panel H 17...

Страница 13: ...r le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRIN...

Страница 14: ...de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged...

Страница 15: ...ien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM Packaged Air Conditioner...

Страница 16: ...4 342 146 138 285 143 304 146 323 149 344 150 365 152 140 307 150 327 152 346 154 367 156 387 158 142 330 156 349 158 369 160 389 162 410 164 144 334 160 353 162 372 164 391 166 412 168 146 356 166 37...

Страница 17: ...s Temp Liq Press Dis Temp 123 257 140 125 259 145 282 142 127 261 151 284 147 307 145 129 267 148 286 152 309 150 332 147 131 271 151 292 152 311 154 334 152 357 150 133 295 155 316 156 336 157 359 15...

Страница 18: ...4 140 128 273 146 296 146 320 145 130 277 148 299 151 322 150 346 150 132 281 151 302 153 324 155 348 154 371 155 134 306 156 328 158 350 159 373 159 397 159 136 331 161 353 163 375 163 399 164 422 16...

Страница 19: ...19...

Страница 20: ...TRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity correct YES NO Rated Voltage VOLTS L1 L2 Volts VOLTS Hasthethermostatbeencalibrated YES NO Is the thermostat level YES NO Istheh...

Отзывы: