NOTE

: Air gate setting may vary for sidewall vented units where air gate must be adjusted to achieve 

zero smoke.

 
A.1 OIL BURNER AIR ADJUSTMENT 

For complete details, consult the oil burner instruction 
manual provided in the furnace documents envelope. 

Beckett AF Burner 

Adjust the air shutter by loosening the locking screws 
and moving the air shutter, and if necessary, the bulk 
air band. 

Beckett AFII Burner

 

Adjust the burner air supply by first loosening the 
locking screw located on the black dial to the right of 
the burner.  Turn the black dial clockwise to increase 
the combustion air and counter-clockwise to decrease 
the combustion air.  Re-tighten the locking screw after 
obtaining the proper setting. 

 

A.2 BURNER ELECTRODES 

Adjustment of the electrode tips with respect to each 
other, the nozzle, and to the rest of the burner is very 
important to ensure smooth start-ups and to permit 
efficient combustion. 

Beckett AF Burner

 

Electrode gap: 5/32 inch. 

Distance above horizontal centerline: 5/16 inch. Older 
instruction sheets specify 7/16 inch. The current 
specification is 5/16 inch. 

Distance ahead of nozzle: 1/16 inch. 

“Z” dimension, the distance from the front of the end 
cone (head) to the face of the nozzle should be 1-1/8 
inches. If a ceramic head is used, the distance from 
the end cone to the nozzle face is increased to 1-3/8 
inches. 

 
 
 
 
 
 
 
 
 

 
A.3 START UP 

The furnace should be operated for a minimum of 10 
minutes to reach steady state conditions before fine 
tuning combustion. The warm up time is ideal for 
testing the oil pump pressure. 

Drill a 1/4-inch test port in the venting between the 
furnace flue outlet and draft regulator (barometric 
damper). Insert a stack thermometer and note the flue 
gas temperature. The flue gases should be within a 
range of 350°F to 450°F. If the flue gases are below 
the range, it may be necessary to slow down the 
blower fan. If the flue gases are above the range, the 
blower fan may require speeding up. Stack 
temperature varies directly with the system 
temperature rise. System temperature rise is the 
difference between the furnace outlet temperature and 
furnace inlet temperature as measured in the vicinity of 
the connection between the plenum take-offs and the 
trunk ducts.  Temperature rise value is listed on the 
system rating plate. 

Perform a smoke spot test. The smoke spot should not 
exceed No. 1 on the Bacharach Scale. 

After the air adjustments have been completed, re-
check the draft pressure at the test port on the burner 
mounting plate as shown in Figure 2. The draft should 
be adjusted to -0.02 inches w.c. 

In the United States, the Beckett AF Burner may be 
equipped with Beckett's "

Inlet Air Shut-Off

" to increase 

efficiency. (Beckett Part No. AF/A 5861).

  

NOTE:  USE  OF THE INLET AIR SHUT-OFF 

COULD CAUSE POST COMBUSTION  NOZZLE 

DRIP. 

 

 

 
 
 

 

12

Содержание O4HD-091A-12-FB

Страница 1: ...not store or use gasoline or other flammable liquids or vapors in the vicinity of this or any other appliance ALL INSTALLATIONS MUST MEET ALL LOCAL PROVINCIAL STATE AND FEDERAL CODES WHICH MAY DIFFER...

Страница 2: ...ER PRIMARY SAFETY CONTROL 7 18 COMBUSTION CHAMBER 7 19a 19b CIRCULATING AIR BLOWER 7 20 MAINTENANCE AND SERVICE 8 21 OPERATING INSTRUCTIONS 9 22 ECM BLOWER MOTOR OPERATION 9 APPENDIX A O4HD 091A 12 FB...

Страница 3: ...red The furnace should be carefully inspected for damage when being unpacked 2 HEAT LOSS The maximum hourly heat loss for each heated space shall be calculated in accordance with the procedures descri...

Страница 4: ...is installed in a full basement infiltration is normally adequate to provide air for combustion and draft operation Furnace rooms under 65m 700 ft should automatically be treated as confined space 6 C...

Страница 5: ...at the end of a call for heat Blower shutdown is delayed to remove any residual heat from the heat exchanger and improve the annual efficiency of the furnace The electronic fan timer board works in co...

Страница 6: ...rmers 12 PIPING INSTALLATION The entire fuel system should be installed in accordance with the requirement of CAN CSA B 139 and local regulations Use only an approved fuel oil tanks piping fittings an...

Страница 7: ...ER UNLESS THE BLOWER ACCESS DOOR IS SECURED IN PLACE 19a CIRCULATING AIR BLOWER O4HD 091A 12 FB The O4HD 091A 12 FB O4HD 091A 14 FA DV and O4HD 091A V FA furnace models are equipped with direct drive...

Страница 8: ...s of the same size and type See Appendix A Table A 8 During the routine service inspect the general condition of the furnace watching for signs of oil leaks in the vicinity of the oil burner soot form...

Страница 9: ...ive blower motor Restore the electrical power to the furnace and set the thermostat above room temperature After three or four minutes of burner operation the limit control should turn the burner off...

Страница 10: ...TTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN THE FURNACE IS FULL OF VAPOUR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT NEVER BURN GARBAGE OR PAPER IN THE FURNACE AND NEVER LEAVE PAPE...

Страница 11: ...80 A 100 psig 0 50 usgph F3 3 in O4HD 091A 12 FB O4HD 091A 12 FB 76 000 AF76BNHS 0 65 80 A 100 psig 0 65 usgph F3 3 in O4HD 105A 12 FB O4HD 105A 12 FB 86 000 AF76BNHS 0 75 80 A 100 psig 0 75 usgph F3...

Страница 12: ...cone to the nozzle face is increased to 1 3 8 inches A 3 START UP The furnace should be operated for a minimum of 10 minutes to reach steady state conditions before fine tuning combustion The warm up...

Страница 13: ...10T DD Med Low 1 2 HP Med High 1 2 HP 3 1 2 HP 690 1500 O4HD 105A 12 FB O4HD 105A 14 FA DV 100 10T DD Med High 1 2 HP High 1 2 HP 3 1 2 HP 690 1500 Table A 7 Direct Drive Blower Characteristics PSC M...

Страница 14: ...istics ECM Motor CFM RANGE Continuous Heating Cooling Furnace Model Blower Motor HP Motor FLA T Fan 0 28 0 48 inches w c 0 5 inches w c O4HD 070A V FA O4HD 091A V FA O4HD 105A V FA 100 10 DD 1 2 HP EC...

Страница 15: ...inet Plenum Openings Filter Shipping Weight Return LB Furnace Model Width Depth Height Supply Side Bottom Flue Diameter Type Size O4HD A 12 FB O4HD A 14 FA DV 070 105 22 30 3 4 49 5 8 20 x 20 14 x 22...

Страница 16: ...SW3 ADJUST Heating Mode Increase OR decrease temperature rise respectively Cooling Mode Increase OR decrease CFM respectively INPUT DIP Switch Position AC Size 1 2 POS USGPH 1 2 POS TON OFF OFF A 0 65...

Страница 17: ...L F interupteur a basse vitesse si quipp e AL limite auxiliaire si quipp e REQUIRED FOR CANADIAN INSTALLATIONS BLOCKED VENT SAFETY L BVS RIELLO 40F BURNER br leur BECKETT AF BURNER br leur 4 1 2 3 OR...

Страница 18: ...TE blanc GND GROUND Terre VI VIOLET violet MOTOR 3 UNUSED BURNER 1 2 YL F IGNITER I soupappe VALVE V L1 FUSED DISCONNECT ON HOT LEG POWER SUPPLY 120 VAC 60 HZ alimentation 120 VAC 60Hz transformateur...

Страница 19: ...fan adjustments can be made by moving the dipswitch settings on the timer control board for fan off delay To check the operation of the limit switch shut off power to the furnace Temporarily remove t...

Страница 20: ...spark for 10 sec a Provides continuous spark after flame is sensed to assure that burner remains lit b Turns on LED diagnostic light c Starts carryover timer i Flame and call for heat are monitored I...

Страница 21: ...FIGURE 4 UNITED TECHNOLOGIES 1158 120 FAN TIMER BOARD O4HD 091A 12 FB and O4HD 091A 14 FA DV FIGURE 5 UNITED TECHNOLOGIES 1168 1 ECM TAP BOARD O4HD 091A V FA 21...

Страница 22: ...S TO IDLE STATE FLAME FLAME FLAME FLAME NO FLAME NO FLAME FLAME LOST FLAME LOST REMAINS IN IDLE STATE OIL PRIMARY CONTROL SEQUENCE of OPERATION LOCKOUT STATE OIL PRIMARY CONTROL Shuts off burner motor...

Страница 23: ...ol shuts off burner Circulator fan is energized immediately at heat speed EFT opens the oil primary control T T connections Circulating fan runs as long as limit string stays open If there is a call f...

Страница 24: ...sing the reset button The LED diagnostic light will flash the following code Table C 2 Cad Cell Resistance Flashes Resistance in Ohms 1 Less than 400 2 Between 400 800 3 Between 800 1600 4 Between 160...

Страница 25: ...ad cell with new cad cell and recheck If indicator light does not turn off remove yellow lead wires from oil primary control and recheck If indicator light is still on replace the oil primary control...

Страница 26: ...Step 7 6 Reset oil primary control by pushing in and releasing red reset button Indicator light continues to flash at 1 Hz rate Verify that the control is not in restricted mode See notes at end of th...

Страница 27: ...ero each time a call for heat is successfully completed To reset from RESTRICTED MODE press and hold the reset button for 30 seconds When the LED flashes twice the device has reset NOTE Disable functi...

Страница 28: ...aximum of 1500 in the presence of light Ensure that room light is not leaking into the cad cell compartment See diagnostic light section No fuel oil Check fuel oil supply Check that all hand operated...

Страница 29: ...radiator Poor alignment between oil burner blast tube and fire pot Check alignment Blast tube should be centered with fire pot burner opening Oil burner head should be inch back from the inside surfac...

Страница 30: ...oints and seams Insulate ductwork if necessary IMPORTANT FINAL CHECK OUT ENSURE THAT ALL SAFETY DEVICES AND ELECTRICAL COMPONENTS HAVE BEEN SET FOR NORMAL OPERATION ENSURE THAT ALL ELECTRICAL CONNECTI...

Страница 31: ...al No Date Installed Contractor Contact Address Postal Code Telephone No After Hours No FUEL SUPPLIER Fuel Oil Supplier Contact Telephone No After Hours No IF DIFFERENT FROM INSTALLATION CONTRACTOR Se...

Страница 32: ...240006333 29161 29163 19 Filter Frame 16 X 25 18020 20 Filter Frame End Support 5592B2 21 Filter 16 X 25 X 1 Permanent 2180023 24 Control Box 29362 25 Upper Door Panel 30164L Logo Bezel 28479 Logo La...

Страница 33: ...DV Ref No Description Part No All parts are the same as listed on the previous pages for Models O4HD 091A 12 FB and O4HD 091A V FA except where noted below 12 Oil Burner Mounting Plate Assembly 29872...

Страница 34: ...34...

Страница 35: ...NOTES Nortek Global HVAC 8000 Phoenix Parkway O Fallon Missouri 63368 151B 0810 Replaces 151B 0909 Nortek Global HVAC LLC 2015 All Rights Reserved 35...

Отзывы: