DC Inverter U-match Series Floor Ceiling Type Unit
24
ķ
. The power cord and the wire of the fresh air valve are high-voltage, while the communication
cord and connection wire of the wired controller are low-voltage. They should run separately to
protect against electromagnetic interference.
ĸ
. The high-voltage and low-voltage lines should pass through the rubber rings at different electric
box covers.
Ĺ
. Do not bundle the connection wire of the wired controller and the communication cord together,
or arrange them in parallel, otherwise improper operation would occur.
ĺ
. The high-voltage and low-voltage lines should be fixed separately and securely, with internal big
clamps for the former and small clamps for the latter.
Ļ
. Tighten the indoor/outdoor connection cord and power cord respectively on the terminal boards
with screws. Faulty connection may cause a fire.
ļ
. If the indoor unit connection cord (to the outdoor unit) and power supply are wired incorrectly,
the air conditioner may be damaged.
Ľ
. Connect the indoor unit connection cord properly based on the corresponding marks as shown
in Fig. 4.29.
ľ
. Ground both the indoor and outdoor units by attaching a ground wire.
Ŀ
. Unit shall be grounded in compliance with the applicable local and national codes.
(6). Electric wiring of outdoor unit side
NOTICE!
When connecting the power supply cord, make sure that the phase
of the power supply matches with the exact terminal board. If not, the
compressor will rotate backward and be damaged.
Remove the big handle (18k~30k) /front board (36k~48k) of the outdoor unit and
insert the end of the communication cord and the power cable into the terminal
board.
Single phase:
Fig. 4.31