DC Inverter U-match Series Floor Ceiling Type Unit
14
Fig. 4.11
Fig. 4.12
Table 4.3 Flare nut tightening torque
Pipe Diameter
Tightening Torque
6mm (1/4inch)
15~30N·m (11~22ft.-1b.)
9.5mm (3/8inch)
35~40N·m (26~29ft.-1b.)
12.7mm (1/2inch)
45~50N·m (33~37ft.-1b.)
16mm (5/8inch)
60~65N·m (44~48ft.-1b.)
Be sure to connect the gas pipe after connecting the liquid pipe completely.
4.3.4 Connecting the Pipe to the Outdoor Unit
Tighten the flare nut of the connection pipe at
the outdoor unit valve connector. The tightening
method is the same as that as at the indoor unit.
Fig. 4.13