Nortek DS4BF Скачать руководство пользователя страница 6

6

Start Up & adJUStmentS

pre-Start check list

 Verify the indoor unit is level and allows proper 

condensate drainage.

  Verify the outdoor coil and top of the unit are free from 

obstructions and debris, and all equipment access/

control panels are in place.

  Verify air filters are cleaned and properly installed.

  Verify duct work is sealed to prevent air leakage. 

  Verify line voltage power leads are securely connected 

and the unit is properly grounded.

   Verify low voltage wires are securely connected to the 

correct leads on the low voltage terminal strip.

  Verify power supply branch circuit overcurrent protection 

is sized properly.

  Verify the thermostat is wired correctly.

Start-Up procedures

The thermostat's function mode should be set to OFF and 

the fan mode should be set to AUTO. Close all electrical 

disconnects to energize the sy stem.

Air Circulation - Indoor Blower

1. Set the thermostat system mode on OFF and the fan 

mode to ON.

2. Verify the blower runs continuously. Check the air delivery 

at the supply registers and adjust register openings for 
balanced air distribution. If insufficient air is detected, 
examine ductwork for leaks or obstructions.

3. Set the thermostat fan mode to AUTO and verify the 

blower stops running.

System Cooling

1. Set the thermostat’s system mode to COOL and the 

fan mode to AUTO. Gradually lower the thermostat 
temperature setpoint below room temperature and verify 

the outdoor unit and indoor blower energize.

2. Verify blower wheel is spinning in direction indicated by 

arrow. Feel the air being circulated by the indoor blower 
and verify that it is cooler than ambient temperature. 
Listen for any unusual noises. If unusual sounds occur, 
determine the source of the noise and correct as 
necessary.

3. Verify HI and LO refrigerant pressures.
4. Allow the system to operate for several minutes and then 

set the temperature selector above room temperature. 
Verify the fan and compressor cycle off with the 
thermostat. 

note:

 The blower should also stop unless 

fan mode is set to the ON position.

System Heating (optional)

1. Set the thermostat's system mode to HEAT and the 

temperature mode above room temperature.

2. Verify the optional heating equipment (furnace or 

electric heat) and indoor blower energize. Feel the air 

being circulated by the indoor blower and verify that 
it is warmer than ambient temperature. Listen for any 
unusual noises. If unusual sounds occur, determine the 
source of the noise and correct as necessary.

NOTE: FOR THE MATCH 
*S4BF-024KA + C6B(A,H)-X30(C,U)-C + *G7T-C
*S4BF-024KA + C6B(A,H)-X30(C,U)-C + *G7S-C+*SHE

 Only connect Y2 from thermostat to OD Y2

Furnace

Air Conditioner 

OD Section

(Without CoreSense)

W2 

W1 

Y/Y2 

Thermostat

O Y2 Y G RC RH C W2 W/E

Y1

Y/Y2 

Y1

Figure 3. typical 2-Stage air conditioner 

(without coreSense) with gas Furnace

thermostat connections

•  Thermostat connections should be made in accordance 

with the instructions supplied with the thermostat and 

the indoor equipment. Typical AC and thermostat 

hookups are shown in 

Figure 3, (page 6)

.

•  The outdoor unit is designed to operate from a 24 VAC 

Class II control circuit. The control circuit wiring must 

comply with the current provisions of the NEC (ANSI/

NFPA 70) and with applicable local codes having 
jurisdiction.

•  The low voltage wires must be properly connected to 

the units low voltage terminal block. Recommended 

wire gauge and wire lengths for typical thermostat 

connections are listed in 

Table 2

.

•  The  thermostat  should  be  mounted  about  5  feet 

above the floor on an inside wall. DO NOT install the 

thermostat on an outside wall or any other location 

where its operation may be adversely affected by radiant 

heat from fireplaces, sunlight, or lighting fixtures, and 

convective heat from warm air registers or electrical 

appliances. Refer to the thermostat manufacturer’s 

instruction sheet for detailed mounting and installation 

information.

table 2. thermostat Wire gauge

thermoStat

Wire gaUge

maXimUm recommended

 thermoStat Wire length (Ft)

24

25

22

45

20

70

18

110

Содержание DS4BF

Страница 1: ...ckage for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE Installation Instructions important SAFETY INFORMATION 2 Air conditioner INSTallATION 3 Genera...

Страница 2: ...tions in the literature on tags and on labels provided with the equipment Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operation...

Страница 3: ...g the unit Locating the Air Conditioner Survey the job site to determine the best location for mounting the outdoor unit The outdoor unit should be installed no closer than 18 inches from the outside...

Страница 4: ...of the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code CSA C22 1 and or local codes Pre E...

Страница 5: ...is also imprinted on the side of the module to quickly direct the technician to the root cause of a problem Alert identification codes are also listed in Table 3 page 15 Compressor Protection TheCoreS...

Страница 6: ...e fan and compressor cycle off with the thermostat NOTE The blower should also stop unless fan mode is set to the ON position System Heating optional 1 Set the thermostat s system mode to HEAT and the...

Страница 7: ...ded Deviationsfromratedairflowsor non listedcombinationsmayrequiremodificationtothe expansion device and refrigerant charging procedures for proper and efficient system operation The refrigerant charg...

Страница 8: ...abel Charging charts are valid for a variety of indoor return air conditions and are most influenced by the outdoor ambienttemperature outdoorfanoperationandtheunit operatingvoltage Beforeusingthesech...

Страница 9: ...onductors suitable for 105 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circu...

Страница 10: ...R C S S C R L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR OUTDOOR FAN MOTOR Y2 Y L R C P DC SOL CSC C R Y2 Y LPS HPS CORESENSE COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC Contactor Coil CCH Cr...

Страница 11: ...le Phase 60 Hz WIRING DIAGRAM 7110150 1209 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE BLACK BLUE YELLOW BLUE BLACK 208 230V H C F CCH R C S S C H L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR FAN MOTOR...

Страница 12: ...tection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avan...

Страница 13: ...ACTS L1 T1 COMPRESSOR CSC C Y2 Y LPS HPS COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC 208 230V Two Stage Split System Air Conditioner Outdoor Section With ECM Outdoor Motor Single Phase 60 Hz...

Страница 14: ...class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avant de faire letretien 8 Employez uniquement des conducte...

Страница 15: ...functioning Check thermostat sub base or wiring for short circuit Check thermostat installation location level Yellow ALERT Flash Code 2 Compressor Pressure Trip High Refrigerant Charge Discharge pres...

Страница 16: ...seized Measure compressor oil level Red LOCKOUT Flash Code 5 Yellow Off Compressor Moderate Run Trip 1 Evaporator blower is not running Check blower relay coil and contacts Check blower motor capacito...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...______________________ Unit Installed Minimum clearances per Figure 1 page 3 YES NO INSTALLER NAME CITY________________________ STATE_________________ REFRIGERATION SYSTEM Was unit given 24 hr warm up...

Отзывы: